Text
.
UNITED STATES 4,[
og NUCLEAR REGULATORY COMMISSION y
3 y, g
wAsMiNcTon. o. c. 20sss g
. r t
e
%g '
p*
o....
CAROLINA POL'ER & LIGHT COMPANY DOCKET NO. 50-325 ERUNSWICK STEAM ELECTRIC PLANT, UNIT NO.1 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No. 50 License No. DPR-71 1.
The Nuclear Regulatory Commission (the Commission) has found that:
A.
The application for Amendment by Carolina Power & Light Company dated July 3, 1982 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; The facility will operate in conformity with the application, B.
the provisions of the Act, and the rules and regulations of the Commission; There is reasonable assurance (i) that the activities' authorized C.
by this amendnent can be conducted without endangering the health and safety of the pubTic, and (ii) that such activities will be conducted in compliance with the Commission's regulations; The issuance of this amendnent will not be inimical to the common v.
defense and security or to the health and safety of the public; and The issuance of this amendnent is in accordance with 10 CFR Part
. E.
51 of the Commission's regulations and all applicable requirenents have been satisfied.
Accordingly, Facility Operating License No. DPR-71 is hereby amended by 2.
adding paragraph 2.C.(2)(b) to read as follows:
Effective July 1, 1982, through July 8, 1982, Action statement 2.C.(2)(b)
"a" of Technical Specification 3.8.1.1 shall read as follows:
ACTION:
With either one offsite circuit or one diesel generator of the a.
above required A.C. electrical power sources inoperable, demonstrate the.0PERABILITY of the remaining A.C. sources by performing 8209270005 820909 PDR ADOCK 05000324 P
2-Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.4 within two hours and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter; restore at least two offsite circuits and four diesel generators to OPERABLE status within 7 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
3.
This license amendment is effective as of July 1, 1982.
FOR THE NUCLEAR REGULATORY C0tMISSION Domenic B. Vassallo, Chief Operating Reactors Branch #2 Division of Licensing Date of Issuance: September 9,1982 l
i l
l l
i n
a,n.
w,-
.--,=,--m
-.e-r. -- -
' aua UNITED STATES o,
NUCLEAR REGULATORY COMMISSION y
3.s,
g a
wasmucTON. D. C. 20555 g
8 t.,*.....o CAROLINA PCEER & LIGHT C0f9ANY
~
DOCKET N0. 50-324 BPURSWICK STEAM ELECTRIC PLANT, UNIT NO. 2 A G D C T TO FAC!LITY OPERATING LICENSE Amendment No. 75 License No. DPR-62 1.
The Nuclear Regulatory Comnission (the Commission) has found that:
A.
The application for Amendment by Carolina Power & Light Company dated July 3, 1982 complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Commission's rules and regulations set forth in 10 CFR Chapter I; S.
The facility will operate in conformity with the application, the provisions of the Act, and tbe rules and regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this anendnent can be conducted without endangering the health and safety of the pub.lic, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amerdment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51 of the Commission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, Facility Operating License No. OPR-62 is hereby amended by adding paragraph 2.C.(2)(c) to read as follows:
2.C. ( 2)( c) Effective July 1, 1982, through July 8, 1982, Action statement "a" of Technical Specification 3.8.1.1 shall read as follows:
l ACTION:
1 With either one offsite circuit or one diesei generator of the I
a.
above required A.C. electrical power sources inoperable, demonstrate the OPERABILITY of the remaining A.C. sources by performing Surveillance Requirements 4.8.1.1.1.a and 4.8.1.1.2.a.4 i
l
within two hours and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafter; restore at least two offsite circuits and four diesel generators to OPERABLE status within 7 days or be in at least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
3.
This license amendment is effective as of July 1, 1982.
t FOR THE NUCLEAR REGULATORY COMMISSION Domenic B. Vassallo, Chief Operating Reactors Branch #2 Division of Licensing Date of Issuance:
September 9,1982 6
9 9
-