Proposed TS Tables 3.2.1, ECCS Actuation Instrumentation & 4.2.1, Min Test & Calibr Frequencies ECC Actuation Instrumentation
ML20069B467
Person / Time
Site: Vermont Yankee File:NorthStar Vermont Yankee icon.png
Issue date: 05/20/1994
From:
VERMONT YANKEE NUCLEAR POWER CORP.
To:
Shared Package
ML20069B466 List:
References
NUDOCS 9405270231
Download: ML20069B467 (2)


Text

_

~

VYNPS TABLE 3.2.1 True E$

EMERGENCY CORE COOLING SYSTEM ACTUATION INSTRUMENTATION 88 Eni

^"

Core-Spray - A & B (Note 1) o,o Minimum Number of Required Action When 3,gg Operable Instrument Minimum Conditions enco Channels per Trip for Operation "d

System Trio Function Trio level Settina Are Not Satisfied 2

High Drywell Pressure 12.5 psig Note 2 2

Low-Low Reactor Vessel Water 182.5" above top of Note 2 Level enriched fuel 1

Low Reactor Pressure 300 < P < 350 psig-Note 2 (PT-2-3-56C/D(S1))

2 Low Reactor Pressure 300 < P < 350 psig Note 2 (PT-2-3-56A/B(S1) & 52C/D(M))

1 Time Delay (14A-K16A & B) 110 seconds Note 2 2

Pump (P-46-1A/B). Discharge 1100 psig Note 5 Pressure 1

Auxiliary Power Monitor Note 5 1

Pump Bus Power Monitor Note 5 1

Trip System Logic Note 5 Amendment No. 44, 60, 140, ist 35

VYNPS 2

..t TABLE 4.2.1 MINIMUM TEST AND CALIBRATION FRE00ENCIES' EMERGENCY CORE COOLING ACTUATION INSTRUMENTATION-e Core Spray System Trio Function Functional Test (8)

Calibration (8)

,4 Instrument Check'

'High Drywell Pressure (Note 1)

Once/ Operating Cycle-Once Each Day Low-Low Reactor Vessel-(Note 1)

Once/ Operating Cycle OncelEach Day Water-Level.

Low Reactor-Pressure (Note 1)

Once/ Operating Cycle-(PT-2-3-56C/D(SI))

t Low Reactor Pressure (Note 1)

.0nce/ Operating Cycle (PT-2-3-56A/B(S1) &

52C/D(M))

Pump (P-46-1A/B),

(Note'1)

Every Three Months Discharge Pressure Auxiliary Power Monitor (Note '1).

Every Refueling Once Each Day Pump: Bus Power Monitor (Note 1)

None Once Each-Day

-Trio System. Logic Once/ Operating Cycle Once/ Operating Cycle 1

(Note 3)

Amendment No. 50. M. W6. H6 50

=

..