' TABLE 3.3-5 ENGINEERED SAFETY FtATURES RESPONSE TIMES
--t INITIATINC SIGNAL AND FUNCTION RESPONSE TIME IN SECONOS
'l.. Manual a._.SIAS j
St.fety Injection (ECCS)
Not Applicable b.
-Containment Spray Not Applicable c.
CIS Containment Isolation Not Applicable d.
RAS Containment Sump Recirculation Not Applicable e.
AFAS Auxiliary Feedwater Initiation Not Applicable 2.
Pressurizer Pressure-Low a.
Safety injection (ECCS) 1 30*/30**
3.
Containment Pressure-High, a.'- Safety Injection (ECCS) 3 1 0*/30**
b.
Containment Isolation 1 30 c.
Containment Fan Coolers 1 35*/10**
4.-
Containment Pressure-High 60*/60**II) a.
5.
Containment Radiation-High a..
Containment Purge Valves Isolation 1'S CALVERT CLIFFS-UNIT 1 3/4 3-20 Amendment No. AS, 5A. 8 8 9102140195 910201 PDR ADOCK 05000317 P
PDR r
TABLE 3.3-5 (Continued)
ENGINEERED SAFETY FEATURES RESPONSE TIMES-IN!TIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS 6.
Steam Generator Pressure-Low a.
Main Steam Isolation 5,6. 9 b.
Feedwater Isolation 3,80 7.
Refueling Water Tank-Low a.
Containment Sump Recirculation 5,80 8.
Reactor Trip a.
Feedwater Flow Reduction to 5%
120 9.
Loss of Power a.
4.16 kv Emergency Bus Under-voltage (Loss of Voltage)
- t.2***
2 b.
4.16 kv Emergency Bus Under-voltage (Degraded Voltage)
- s8.4***
- 10. Steam Generator Level - Low a.
Steam Driven AFW Pump 154.5 b.
Motor Driven AFW Pump-154.5*/14.5**
- 11. Steam Generator a P-High a.
Auxiliary Feedwater Isolation 120.0 TABLE NOTATION Diesel generator starting and sequence loading delays included.
Diesel generator starting and sequence loading delays not included.
,0ffsite power available.
- Response time measured from the incidence of the undervoltage condition
- to the diesel generator start signal.
(1) Header fill time not included.
l l
CALVERT CLIFFS - UNIT 1 3/4 3-21 Amendment No. fD, SJ, 7J. 72, g g l
l MW
~
TABLE 3.3-5 ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS 1.
Manual a.
Not Applicable b.
CSAS Containment Spray Not Applicable c.
CIS
- =
Containment Isolation Not Applicable d.
RAS Containment Sump Recirculation Not Applicable 4
e.
.AFAS Auxiliary Feedwater Actuation Not Applicable
'2.
Pressurizer Pressure-Low a.
Safety Injection (ECCS)
' < 30*/30**
2 3.
Containment Pressure-High 3
a.
Safety Injection (ECCS) 1 30*/30**
i b.
Containment Isolation 1 30 j
j c.
Containment Fan Coolers 1 3S*/10**
4.
Containment Pressure--High a.
Containment Spray 1 60*/60**
l j
)
3 5.
Containment Radiation-Hioh 4
i a.
Containment Purge Valves Isolation 15 5
1
(.-
1-CALVERT CLIFFS - UNIT 2 3/4 3-20 Amendment No. 6, 3Z, 61 j
9 i
~,- m y n-res -.,evry r,- 7 -n a-> r
- w',~-".
-~~
~ - ~
' ' ~ ~ ~ '
- ' ' ~ ~ '"
..c, '
.s
. as se.
.-=ss_
- e *~, - --
+
- 3*,[ =* ' v,
~,.
- ~*,,
i TABLE 3.3-5 (Continued)
ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS
~
6.
Steam Generator Pressure-Low a.
Main Steam Isolation
< 6.9 b.
Feedwater Isolation 5, 80 C
- 7..
Refueling Water Tank-Low a.
Containment Sump Racirculation y, 80 8.
Reactor Trip a.
Feedwater Flow Reduction to 5%
5, 20 9.
Loss of Power a'.
4.'16 kv Emergency B.us
< 2.2 Undervoltage (Loss of Voltage) b.
4.16 kv Emergency Bus
< 8.4
~
Undervoltage (Degraded Voltage)'
10.
Steam Generator Level - Low a.
Motor Dr.iven AFW Pump.
< 54.5.* / 14.5**
b.
Steam Driven AFW Pump
< 54.5-
- 11. Steam Generator 6P-High a.
Auxiliary Feedwater Isolation
< 20.0 TABLE NOTATION
- 0iesel generator starting and sequence loading delays included.
-** Diesel generator starting and sequence loading delays not included.
Offsite power available.
- Response time measured from the incidence of the undervcitage condition to the diesel generator start signal.
CALVERT CLIFFS - UNIT 2 3/4 3-21 Amendment No. 22, 37, 6 1
- W s' 04
- M' 4
3' pag,a4,g W =
,.**g.E eg
-e,*9,),
4 eed ee-qp --_e ce pe+ 4 g= ag'P.*
- aN 9, ehree ui
TABLE 3.3-5 (Continued)
ENGINEERED SAFETY FEATURES RESPONSE TIMES
- lNITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECONDS 6.
Steam Generator Pressure-Low a.
Main Steam Isolation 1 6.9 b.
Feedwater Isolation s 80 7.
Refuelina Water Tank-Low a.
Containment Sump Recirculation s 80 8.
Reactor Trio-a.
Feedwater Flow Reduction to 5%
s 20 9.
Loss of Power a.
4.16 kv Emergency Bus Under-voltage (Loss of Voltage) s 2.2***
b.
4.16 kv Emergency Bus Under-voltage (Degraded Voltage) 5 8.4***
10.
Steam Generator Level-Low a.
Steam Driven AFW Pump
$ 180
=b.
Motor Driven AFW Pump 5 180-11.
Steam Generator A P-Hiah a.
Auxiliary Feedwater Isolation s 20.0 TABLE NOTATION Diesel generator starting and sequence loading delays included.
Diesel generator starting and sequence loading delays n21 included.
1 Offsite power available.
Response time measured from the incidence of the undervoltage conditiori to the diesel generator start signal.
-(l) Header fill time not included.
L L
L CALVERT CLIFFS - UNIT 1 3/4 3-21 Amendment No. f9/E//7J////
EE,149-L-
l TABLE 3.3-5 (Continued)
ENGINEERED SAFETY FEATURES RESPONSE TIMES INITIATING SIGNAL AND FUNCTION RESPONSE TIME IN SECON_[$
6.
Steam Generator Pressure-Low
.a.
Main Steam Isolation 1 6.9 b.
Feedwater Isolation 1 80 7.-
Refuelino Water Tank-Low a.
Containment Sump Recirculation 1 80 l
8.
Reactor Trio a.
Feedwater Flow Reduction to 5%
s 20 9.
Loss of Power a.
4.16 kv Emergency Bus Under-voltage (Loss of Voltage) s 2.2***
4.16 kv Emergency Bus Under-
~b. -
voltage (Degraded Voltage) s 8.4***.
i 10.
Steam Generator level - Low a.
Motor Driven ATW Pump s_180
- b.
Steam Driven AFW Pump s.180
- 11. Eteam Generator A P-Hioh a.
Auxiliary. Feedwater Isolation s 20.0 l
TABLE NOTATION Diesel generator starting and sequence loading delays included.
-Diesel generator starting and sequence loading delays Eglincluded.
Offsite power available.
Response time measured from the incidence of the undervoltage; condition to the-diesel generator start signal.
CALVERT CLIFFS - UNIT 2 3/4 3-21 Amendment No. JJ/JHEJ,130