b i
CONTAINMENT SYSTEMS OXYGEN CONCENTRATION LIMITING CONDITION FOR OPERATION 3.6.6.3
- The primary containment atmosphere oxygen concentration shall l
be less than 4% by volume during the period from:
a.
Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after THERMAL POWER > 15% of RATED THERMA'L POWER, to b.
Within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> prior to a scheduled reduction of THERMAL
~ POWER to < 15% of RATED THERMAL POWER.
APPLICABILITY: CONDITION 1.
ACTION:
With the oxygen concentration in the primary containment exceeding the limit, be in at least STARTUP within 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.6.6.3 The oxygen concentration in the primary containment shall be i
verified to be within the limit within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after THERMAL POWER
> 15% of RATED THERMAL POWER and at least once per 7 days thereafter.
- For the period commencing at 1800 on December 6,1982, a temporary exemption is allowed to operate BSEP-2 in Condition 1 with contain-3 ment oxygen concentration exceeding 4% by volume for 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.
l 8212100085 821206 PDR ADOCK 05000324 P
PDR l BRUNSWICK-UNIT 2 3/4 6-29
.