Final Deficiency Rept Re Water in Rock Anchor Tendon Head Protective Grease Cans.Initially Reported on 790523.Ground Water Will Not Prevent Prestressing Sys from Performing Intended Functions.Components Tested for Corrosion
ML20067A660
Person / Time
Site: Bellefonte  Tennessee Valley Authority icon.png
Issue date: 11/23/1982
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8212020139
Download: ML20067A660 (3)


Text

,

TENNESSEE VALLEY AUTHORITY I

CH ATTANOOGA. TENNESSEE 37401 400 Chestnut Street Tower II November 23, 1982 U.S. Nuclear Regulatory Commission

[

g Region II 6

Vo Attn: Mr. James P. O'Reilly, Regional Administrator 4

.7 s 101 Marietta Street, Suite 3100 fp Atlanta, Georgia 30303 y

y

Dear Mr. O'Reilly:

ty BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - WATER FOUND IN ROCK ANCHOR TENDON cp HEAD PROTECTIVE GREASE CANS - NCR 1005 - FINAL REPORT On May 23, 1979, R. W. Wright, NRC-0IE Region II, was informed that the subject nonconformance was determined to be reportable in accordance with 10 CFR 50.55(e). This was followed by our interia reports dated June 22 and November 23, 1979; March 21 and September 24, 1980; August 24, 1981; and January 21 and May 10, 1982. As discussed with R. V. Crlenjak by telephone on November 22, 1982, the response to this deficiency was delayed. Enclosed is our final report.

If you have any questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Licensing Enclosure oc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C.

20555 C

efR 1 1 s'

$$h2ggo poggasgg oc S

An Equal Opportunity Employer

_ = -.

i

~*

i 1

1 ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 WATER FOUND IM. ROCK ANCHOR TENDON HEAD PROTECTIVE GREASE CANS NCR 1005 10 CFR 50.55(e)

FINAL REPORT l

Description of Deficiency Inspection of approximately 20 (10 randomly chosen on each unit) rock anchor tendon head protective grease cans indicates ground water is infiltrating up along the grouted tendon through the grout hole in the shim stack and into the grease cans. The grease cans are filled with grease to protect the tendons and anchorheads from corrosion. Any water entering the j

grease cans has the potential for causing corrosion problems.

I 1

\\

Safety Implications l

TVA's original concern with this deficiency was that the groundwater intrusion into the grease cans could result in corrosion of the rock anchor tendons and tendon heads. This could have adversely impacted the posttensioned containment vessel.

However, as a result of the investigations detailed in this report, it is evident that corrosion of the tendons and tendon heads is not a significant concern. Consequently, there is no condition adverse to the safety of operations of the plant.

Corrective Action 1

Because of the potential corrosion problem associated with ground water in l

the grease cans, TVA initiated and performed a testing program to determine the effect of ground water on the rock anchor components.

i Based on results of this testing program, TVA has concluded that infiltrating ground water will not prevent the prestressing system from f

performing its intended function for the life of the plant.

TVA bases this on the following facts obtained from the testing program:

4 i

1.

The general corrosion rate of steels depends largely on the amount of dissolved oxygen in the ground water.

Investigations have shown that the dissolved oxygen content of the ground water near the rocks anchors is essentially zero.

2.

Although ground water in the vicinity of the rock anchor tendons has a pH of approximately 7.2, the grout and grease will increase the long term stabilized pH of the ground water in the grease cans to approximately 11.5 where tests have shown that little or no corrosion will occur.

3 Grease provided superior protection on all tendon steels allowing immeasurable corrosion on all samples tested, i

t

, - - - -.,.. - _ - _,,, - -... - -, - ~ ~ -, - - _. -. - - -, - - - -

~ - - - - - - - - -. -.,,,, -...

0 Page 2 The rock anchor components will be inspected for corrosion in accordance with Babcock and Wilcox Standard Technical Specifications, section 4.6.1.7.

No physical corrective action is mquired and the tendons will be used as-is.

Therefore, the 23 dewatering holes will not be drilled in unit 2, and the existing unit 1 pumps will be removed.

TVA has no other nuclear plants with a prestressed containment. Therefore, no other TVA plants are affected.