Rev 2 to Tech Spec Interpretation 003 on TS Section 1.0, Subsection 1.19, Operable - Operability
ML20066L262
Person / Time
Site: Comanche Peak  
Issue date: 01/17/1991
From:
TEXAS UTILITIES ELECTRIC CO. (TU ELECTRIC)
To:
References
CPSES-9101876, PROC-910117, TUS-91045, NUDOCS 9102060367
Download: ML20066L262 (6)


Text

-

4

?"!1UELECTRIC O

OFFICE MEMORANDUM CPSES 9101876 TUS 91045 January 29.-1991' Response ~ Required-T0: Technical Specification Interpretation Copy Holders

SUBJECT:

TECHNICAL SPECIFICATION INTERPRETATION MANUAL Enclosed is-Technical Specification Interpretations-003. revision-2=for insertion into the CPSES Technical' Specification-Interpretations. Manual.

Please insert this-interpretation into your-controlled manual, remove interpretation 003 revision 1. and replace the List of Effective:

Interpretations with the revised List of Effective-Interpretations.

Additionally, please. review the interpretations contained in your controlled manual against the revised List of Effective Interpretations to ensure ~you have all current interpretations.

If you have any questions, please call J. D. Seawright-.at (214) 812 4375.

K

0. R. Woodlan-Docket Licensing Manager JDS/gj Enclosure c - CCS E06 File #916
1 0

\\\\

9102060367 910117 gDR ADOCK0500g5

-.~- -.- - -

i

()

LIST OF EFFECTIVE INTERPRETATIONS Section Interpretation Revision 1.0 Definitions i

1.19 OPERABLE 0PERABILITY (Missile Shields)L 003 2

3/4.0 Aeolicability 3.0.3 Limiting Condition for-Operation 002 0:

4.0.4 Surveillance Requirements 001 1

3/4.3 Instrumentation Table 4.3 2 Engineered Safety Features--

Loss of Power (Undervoltage) 004 0

3.3.3.4 Explosive Gas Monitoring-Instrumentation 005 0

3/4.4 Reactor Coolant System.

l 4.4.5.2.2d Operational Leakage -

007 0

l()

Surveillance Requirements 3/4.6 Containment Systems 3.6.1.7 Containment Ventilation System 014-0 3/4.7 Plant Systems 4.7.1.1 Turbine Cycle.

Safety Valves 008 0.

4.7.7b/4.7.8b Control Room HVAC/ Primary Plant-012 0

Ventilation System - ESF Filtra-tion Units 3.7.8 Primary Plant Ventilation System -

010 0

ESF Filtration Units 3/4.10 Soecial Test Exceptions 3.10.5 Position Indication System-Shutdown.

-006 0

.i January 29.'1991

e T/s Section 1.0 Interp/ctation No. 003 subsection 1.19 R3vtsion 2 TECHNICAL SPECIFICATION INTERPRETATION O

Number:

003 Revision:

2 Check for Withdrawal Technical Specification Revision:

0 Technical Specification Section Number:

1.0 Title

Definitions Technical Specification Subsection:

Number:

1.19

Title:

Ooerable - Ooerability LCO / Surveillance Requirements Affected:

Various LCOs containino OPERABILITY reouirements cotentiallv imoacted bv missile shield removal. See Interoretation for related Soecifications for each shleid.

Interpretation:

Attached SRO review completed with comments resolved:

YES X NO Manager, Nuclear Licensing Concurs:

YES X NO

%-004

%%dQ[

j j,7 79 j SORC Meeting No.

Plant Manager Date O

Page 1 of 5 STA 7391 R0

. fnterpretation No. 003 TS Section 1.0 Revision No. 2 Subsection 1.19 Technical Specification Internretation No. 003 Rev. 2 O

l l

Because the purpose of missile shields is to protect equipment from tornado i

generated missiles, and given the fact that adequate warning is available for I

tornado conditions, it is not necessary to consider protected equipment inoperable solely due to its missile shield being removed. This interpretation provides conservative pre planned allowances for control of missile shields without further consideration of equipment OPERABILITY. Removal of missile shields not contained herein, or exceeding the bounds of this interpretation require additional assessment of equipment OPERABILITV. The conservative option to declare affected equipment inoperable and compty with the provisions of Technical Specifications is always available.

The following allowances have considered the impact on HVAC pressure l

boundaries, but do not address Security and Fire Protection requirements.

i The capability to immediately re-install missile shields as used in the following allowances is deemed to exist when the necessary equipment to perform the installation is located on site and is available for use. Personnel necessary to operate the equipment shall be onsite and available when weather conditions exist such that a potential for a Tornado Watch or Warning exists. If weather conditions pose no immediate potential for adverse weather, then personnel G

associated with the operation of the equipment shall be available and within 90 V

minutes of the site. The shield shall also be in such condition and location to support reinstallation.

Removal and installation of missile shields shall be conducted in accordsc.ce with MDA-304, " Heavy Loads Program".

Installation of each removed shield shall begin immediately upon the associated notification (Tornado Watch, Tornado Warning, etc.) otherwise the affected system (s) shall be declared inoperable.

Shields:

S-27 Door, Unit 1 Safeguards Corridor El. 810' -6" S-38B Door, Auxiliary Bldg. El. 852' -6" S-38D Door, H2 Recombiner Control Panel El. 852' -6" Related Soecifications: 3.7.8; 3.6.4.2 (S-38D only)

Allowance:

May be open in Modes 5 or 6 under administrative control provided a.

g the capabilitt to close immediately on notification of a Tornado y

Warning exists.

Page 2 of 5

  1. Interpretdion No. 003-
  • Revisi,a No. 2_

_ TS Section 1.0~

- Subsection 1,19_

[.-

b.

May be removed in MODES'5 or 6 under administrative control--

provided the capability exists ~ to re install immediately on-notification of a National Weather Service issued Tornado Warning.

Tornado watch, or other Special Weather Statement with winds in:

excess of 60 mph affecting CPSES.

c.

May be open in MODES 1,2i3 and.4 under administrative controlL for up to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> provided:

q 1)

It is continuously-manned, with direct communicat'lons-established to the control room, and i

2)

It is capable'of immediate closure upon notification from' the--

Control Room (for Tornado Warning or Safety _ Injection);

Shields:

Access Cover Plates (4), El."852' -6",' above Safeguard Bldg. -

Corridor.

Related Specifications: _ (For MODES 5 or 6 only) -3.4.1.4.1: 3.4.1.4.2:-

3.9.8.1;i3.9.8.2 (Note: Part of Specification 3.7.8_ HVAC-pressure boundary):

O

^>> - " e :

  • v de re=ovea ia =ooes 5 #a e== der a-i=> trativc ="etrot -

provided_ either: -

a The floor plugs (El. 831' -6" corridor) over each-OPERABLE RHR :

heat exchanger shall be in place, or -

b.

'Ihe capability exists to re-install the missile shield or floor-plugs

-immediately upon notification of a National Weather Service issued Tornado Warning, TornadoLWatch. or other Sp'ecial_ Weather Statement with winds-in excess'of 60. mph affecting-CPSES.c If only one RHR' system is OPERABLE,.either its missile shield or floor 1

1 plug shall be in place. -

Shields:

E-40A Door, Control Room Related Specification:. 3.7.7

- Allowance: LIn all MODES may be open under administrative control for up to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> provided:

a It is continuously-manned, with direct-communications established to the control room, and:

O Page 3 of 5

___.m m_._

m

' Interpretation No. 003 TS Section 1.0-

-l

' Revision No.' 2

^ Subsection 1.19-y O

b.

It is capable ofimmediate closure upon' notification from the Control Room (for Tornado Warning, Safety Injection, less-of-Offsite Power, or Intake Vent-High Radiation) _

r Shield:

Containment Equipment' Hatch Cover Related Soecification: 3.6.1.1 A!!awance: May be removed when containment integrity is not required.

Shields: -

Related 'Snecifications Access Cover Plate, Diesel FO Truck Fill Station' 3.8.1.1/3.8.1'.21 Access Cover, RWST 3.1.2.5/3.1.2.6/3.5.4 :

Access Cover,' CST 3.7.1.3 '

l Access Cover, RMWST None

' Service Water Tunnel, Manhole Cover 3.7.4-

{(

(Common) El. 810' -6" L

Removable Slab (Hatch Cover),

(Fire Protection ' Report).

Electric Fire Pumps.CPX-FPAPFP-01 and CPX-FPAPFP-03=

-i Allowance: May be removed under administrative control provided the _

capability exists to re-install _the missile; shield:immediately upon l-notification of a National Weather Service issued Tornado Warning,-

. Tornado _ Watch, o'r other Special: Weather Statementiwith winds in -

' excess of 60 mph affecting CPSES.

l Shields:

Related' Snecifications Cover Plates (2), Diesel FO Storage Tanks.

3.8.1.1/3.8.1.2' Access Cover Plate (2), Diesel FO Storage Tanks; 3.8.1.1 /;3.8.1.2 :

Removable Slab SW Piping (Train B) El.L 810' -6"-

(Ref. Dwg._ A-1100)

3.7.4 Removable Slab (Hatch-Cover),

3.7.4 SW Pump, CP1-SWAPSW-02 Page-4 of 5 l

I i

,,,,,m-v-,

,,,-+.-,,,.~....,4=,

._,,.w.,m

~,..<

,_c.

.v,...,

y

Interpretation.No. 003 TS Section l.0:

Revision No. 2 Subs:ction 1.19 a

O (cont.)

Shields:

Related Soecifications Removable Slab (Hatch Cover),

3.7.4 SW Pump, CP1-SWAPSW-01 i

Removable Slab (Hatch Cover).

TRM 3.2 SW Pump, CP2-SWAPSW-02 Removable Slab (Hatch Cover),

TRM 3,2 SW Pump, CP2 SWAPSW-01 Manhole Cover, MH#E1A1, SW Train A -

3.7,4 Manhole Cover, MH#E1A2, SW Train A 3.7,4 Manhole Cover, MH#ElB1, SW Train B 3.7,4 Manhole Cover, MH#ElB2, SW Train B 3.7,4 Allowance: May be removed under administrative control for up_to 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> provided:

The capability exists to re-install _the missile shield immediately a

upon notification of a National Weather Service-issued Tornado Warning, Tornado Watch,-or other Special Weather Statement with winds in excess of 60 mph affecting CPSES.

b, No more than one OPERABLE train of a system shall have its missile shields removed at one time.

Reference:

Technical Evaluation SE-90-615 O

Page 5 of 5 1