PUBLIC SERVICE SEABN STAM EM OMce:
Companyof NewHW 1671 Worcester Road Framinoham, Massachusetts 01701 (617) - 872 - 8100 Ne / ember 12, 1982 SBN-366 T.F. B7.1.2 United States Nuclear Regulatory Commission Washington, D. C. 20555 Attention:
Mr. George W. Knighton, Chief Licensing Branch 3 Division of Licensing Refere nces :
(a) Construction Permits CPPR-135 and CPPR-136, Docket Nos. 50-443 and 50-444 (b) USNRC Memorandum, dated October 14, 1982, " Notice of Meeting Regarding Open Items in the Safety Review,"
L. L. Wheeler to J. D. Kerrigan
Subject:
Response to Open Item (SRP 6.2.1; Containment Systems Branch)
Dear Sir:
As a result of a recent meeting with the NRC Staff [ Reference (b)], we offer the following response to the subject open item.
Item (SRP Section 6.2.1)
Address the design capacity of the limiting containment structural component to withstand differential pressure due to inadvertent containment spray actuation.
Res ponse :
Refer to FSAR Subsection 6.2.1.1.b.5, Protection Against External Pressure. This subsection is being revised to read:
"The containment structure, including its steel components, is designed to withstand a maximum external pressure of 3.5 psi (differential pressure). The most limiting event for establishing the required external pressure is the inadvertent actuation of the containment spray system, which results in a pressure dif ferential of 2.8 psi."
Very truly yours, YANKEE ATOMIC ELECTRIC COMP /
-(su 00l J. DeVincentis Project Manager ALL/fsf 0211230025 821112 PDR ADOCK 05000443 A