a s M V NIAGARA RUMOHAWK l
NIAGARA MOHAWK POWER CORPORATl0N/300 ERIE BOULEVARD WEST. SYRACUSE. N.Y.13202/ TELEPHONE (315) 474-1511 SAMUEL F. MANNO VICE PRESIDENT NUCLEAR CONSTRUCTION September 23, 1982 Office of Inspection and Enforcement Region I Attention: Mr. R. W. Starostecki, Director Division of Project and Resident Prograas U. S. Nuclear Regulatory Commission 631 Park Avenue King of Prussia, PA 19406 Re:
Nine Mile Point Unit 2 Docket No. 50-410
Dear fir. Starostecki:
Enclosed is a final report in accordance with 10CFR50.55(e) concerning Rosemount pressure transmitters flodel No.1152. This condition was reported by telephone to your staff on June 17, 1980.
Very truly yours, NIAGARA 110 HAWK POWER CORPORATION y% / W
)
Samuel F. Manno Vice President -
Nuclear Construction SFM/NLR:saa Enclosure xc: Director of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 fir. R. D. Schulz, Resident Inspector 8210040190 820923 PDR ADOCK 05000410 S
PDR tg
NIAGARA M0 HAWK POWER CORPORATION Nine Mile Point Unit 2 Docket No. 50-410 Final Report Under 10CFR50.55(e) Regarding Rosemount Pressure Transmitters Model No.1152 Description of the Problem The problem concerns Rosemount pressure transmitters Model No.1152 with output codes A and D.
These transmitters provide ambiguous output at pressures over or under the specified pressure range. This condition previously had been reported to the Region V office of Inspection and Enforcement by our nuclear steam system supplier, General Electric (GE), in accordance with the requirements of 10CFR21.
Analysis of Safety Implications GE has now informed NMPC that Model No.1152 pressure transmitters supplied to Nine Mile Point Unit 2 do not use the A or D amplifier boards. Therefore, a deficiency concerning Rosemount pressure transmitters Model No.1152 with output codes A and D does not exist on Nine Mile Point Unit 2.