Amends 145 & 176 to Licenses DPR-71 & DPR-62,respectively, Changing Tech Specs to Add Footnote to Action Requirement 3.8.1.1.a That Allows Flexibility Required to Perform Extended Maint on Offsite Circuit
ML20065G571
Person / Time
Site: Brunswick  
Issue date: 10/05/1990
From: Adensam E
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20065G573 List:
References
NUDOCS 9010220143
Download: ML20065G571 (12)


Text

_.__ _ _._ _ ____ _ __ _.

l i

!se me:

i umTEp states l

NUCLEAR REGULATORY COMMISSION n

i s

r nAnwiwovow, c. c. neses l

J CAROLINA POWER & LIGHT COMPANY. et al.

DOCKET NO. 50-325 I

BRUNSWICK STEAM ELECTRIC PLANT. UNIT 1 l

)

i AMENDMENT TO FACILITY OPERATING LICENSE i

' Amendment No.14 5 l

l License.No. DPR-71 l

1.

The Nuclear Regulatory Comission (the Comission) has found that:

)

i A.

The application for amendment filed by Carolina Power & Light Company i

(the licensee), dated July 9, 1990, as supplemented August 16, August 21, and Sestember 18, 1990, complies with the standards and

{

requirenants of tie Atomic Energy Act of 1954, as amended (the Act),

and the Commission's rules and. regulations ret forth in 10 CFR t

i Chapter I; i

4 B.

The facility will operate in confomity with the application, the provisions of the Act, and the rules and regulations of the 4

i Consnission; i

)

C.

There is reasonable assurance (1) that the activities authorized by this tandment can be conducted without endangering.the health-and safety of the public, and (ii) that such activities will be-

-l conducted in compliance with the Comission's regulations; i

D.

The issuance of this amendment will not be-inimical to the connon defense and security.or to the health and safety of the public; and E.

The issuance of this amendment is in accordance with'10 CFR Part 51 of the Comission's regulations and all' applicable requirements have been satisfied.

2.

Accordingly, the license is amended by changes to the Technical i

Specifications, as indicated in the attachment to this license amendment;-

u and saragraph 2.C.(2) of Facility Operating License No. DPR-71 is l

here)y amended to read as follows:.

J i

i i

[

k 4

e.

y

...L,....

l i

2 l

i (2) Technical Soecifications j

The Technical Specifications contained in Appendices A and 8, as I

revised through Amendment No.145, are hereby incorporated in the license. Carolina Power & Light Company shall operate the facility in accordance with the. Technical Specifications j

a 3.

This license amendment is effective as of the date of its issuance and.

shall be implemented within 60 days of issuance.

FOR THE NUCLEAR REGULATORY C0 MIS $10N Original Signed.By:

Elinor G. Adensam, Director

-l Project Directorate II-1 Division of Reactor Projects - I/II-Office of Nuclear Reactor Regulation

)

i

Attachment:

Changes to the Technical Specifications Date of Issuance: October 5, 1990 l

l l

-1 1

l A

orc :LA:Pi n:PM:PD ORPR:

Osc...'..:..

0:

si RPR :.

1 NAME :,PAh8 son :NLe:d -

EA sam

...y......:

DATE M /Lb.......::6 A*/90'

/ / 3/90-

. AC/h/90-

/

90 i

s

'0FFICIAL RECORD COPY l

.. _ ~ + _... - _. _ _ - - _ _, ---. _ - - -

. ~.

t i

t l

ATTACHMENT TO LICENSE AMENDNENT N0.14 5 l

FACIllTY OPERATING LICENSE NO. DPR-71 i

DOCKET NO. 50-325 f

t Replace the following pages of the Appendix A Technical Specifications with l

the enclosed pages. The revised areas are indicated by marginal lines, t

Retnqve.P H f.5 Insert Panes 3/4 8-1 3/4 8-1 i

3/4 8-la i

3/4 8-5 3/4 8-5 i

t

-i r

i 2

e 9

L

(

i 1

l I

i l

.f

.u

.c.

~1 3/4.8 ELECTRICAL POWER SYSTEMS i

3/4.8.1 A.C. SOURCES OPERATING l

l LIMITINC CONDITION FOR OPERATION i

3.8.1.1 As a minimum, the f ollowing A.C. electrical power sources shall be OPERABLE:

i Two physically independent circuits, per unit, between the offsite l

a.

transmission network and the onsite Class lE distribution system, and b.

Four separate and independent diesel generators, each with 1.

A separate engine-mounted fuel tank containing a minimum of 100~

gallons of fuel, i

2.

A separate day fuel tank containing a minimum of 22.650 gallons of fuel, and 3.

A separate fuel transfer pump.

c.

A plant fuel storage tank containing a minimum of 74,000 gallons =of

~

fuel.

APPLICABILITY: OPERATIONAL CONDITIONS 1, 2, and 3.

ACTION With one of f site circuit of the above. required A.C. electrical powgg a.

sources not capable of supplying the Class lE distribution systemt l

1.

Demonstrate the OPERABILITY. of the remaining A.C.. of fsite. source.

i by performing Surveillance Requirement 4.8.1.1.1.a within 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> lthereafterl 2.

Demonstrate the OPERABILITY of the diesel generators by performing Surveillance Requirements 4.8.1.1.2.a.4 and J

4.8.1.1.2.a.5 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and at least once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> thereaftert i

3.

Restore the inoperable offsite circuit to OPERABLE status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at least HOT SHUTDOWN within'the nextL12 hours l

and in COLD SHUTDOWN within the following 24' hours.

With Unit 2 in OPERATIONAL CONDITION 4 or 5 and one-of the required -

Unit 2 off site power circuits not capable of ' supplying the Unit 2 Class IE distribution system,'either restore the inoperable Unit 2 offsite circuit to OPERABLE status' within 45 days or place Unit 1-in at least HOT SHUTDOWN within the next-12 hours and in COLD SHUTDOWN within the.following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. ;The provisions of ACTIONS 3.8.1.1.a.1, 3.8.1.1.a.2, and 3.8.1.1.a.3 are not applicable.

BRUNSWICK - UNIT 1 3/4 8-1 Amendment, No.19(,.14 5 I

l i

ELECTRICAL POWER $YSTEMS J

l LIMITING CONDITION FOR OPERATION (Cont inued) 1 ACTION (Continued):

i b.

With a siesel gengrator of the above required A.C. electrical power I

source inoperable 1 i

I i

I i

t i

i 4

i.

A diesel generator shall be considered to be inoperable from the time of failure until it satisfies the requirements of Surveillance Requirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5.

BRUNSWICK - UNIT 1 3/4 8-la.

, Amendment No. fggg 14c, l

1

)

ELECTRICAL POWER SYSTEMS SHUTDOWN LIMITINC CONDITION FOR OPERATION 3.8.1.2 As a minimum, the following A.C. electrical power sources shall be OPERABLE a.

One circuit per Unit between the of f site transmission network and the onsite Class lE distribution system, and i

b.

Two diesel generators, one of which shall be diesel generator 1 or 2, as required to operate ECCS systems in accordance with Specifications 3.5.3.1 and 3.$.3.21 1.

Each with a separatet a) Engine-mounted fuel tank containing a minimum of 100 gallons of fuel, i

b) Day fuel tank containing a minimum of 22,650 gallons of

~

fuel, and t

r c) Fuel transfer pump.

2.

With a fuel storage tank containing a minimum ot 37,000 gallons of fuel.

APPLICABILITY OPERATIONAL CONDITIONS 4 and 5.

i ACTIONI t

With less than the above minimum required' A.C. elect rical power sources OPERABLE, suspend all operations involving-irradiated fuel' handling, CORE.

ALTERATIONS, positive reactivity changes, or operations that have the potential of draining the reactor vessel. The~ provisions'of Specification 3.0.3 are not applicable.

SURVEILLANCE REQUIREMENTS 4.8.1.2 The above required A.C. electrical power sources shall be demonstrated OPERABLE per surviillance requirements of Specifications-4.8.1.1.1 and 4.8.1.1.2, except f or the requirement: of 4.8.1.1.2.a.5.

k BRUNSWICK - UNIT l' 3/4'8-5 Amendment No.' 14 5 1

l

[g UNITED STATES l

'[

NUCLEAR RECULATORY COMMISSION o

WASHINGTON, D. C. 30006 L

e, CAROLINA POWER & LIGHT COMPANYi et al.

DOCKET NO. 50-324 l

BRUNSWICK STEAM ELECTRIC PLANT UNIT 2 AMENDMENT TO FACILITY OPERATING LICENSE Amendment No.176 j

License No. DPR-62 i

1.

The Nuclear Regulatory Comission (the Comission) has found that:

A.

The application for amendnent filed by Carolina Power & Light Company-(the licensee), dated July 9, 1990, as supplemented August 16 August 21. and September 19, 1990, complies-with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act) and the Comission's rules and regulations set forth in 10 CFR Chapter I; B.

The facility will operate in confomity with the application, the provisions of the Act, and the rules and regulations of the-Comission; C.

There is reasonable assurance (1) that the activities authorized by this amendnent can be conducted without endangering the health and safety of the public, and (ii) that such; activities will be conducted in compliance with the Comission's-regulations; D.

The issuance of this amendment will not be inimicel to'the comon defense and security or to the health and safety of the public; and i

E.

The issuance of this amendment is in accordance with 10 CFR Part 51 i

of the Commission's regulations and all applicable requirements have been satisfied.

~' '

2.

Accordingly, the license-is amended by changes'to the Technical Specifications as indicated in the attachment to this license amendment; and paragraph 2.C.(2) of Facility Operating License No. DPR-62 is hereby amended to read as follows:

i I

i i

i

\\

l 2

(2) Technical Specifications The Technical Specifications contained in Appendices A and B, as

)

l revised through Amendment No.176, are hereby incorporated in the license. Carolina Power & Light Company shall-operate the facility in accordance with the Technical Specifications.

3.

This license amendment is effective as of the date of its~ issuance and shall be implemented within 60 days of issuance.

_j 1

FOR.THE NUCLEAR REGULATORY COMMISSION I

i Original Signed By:

Elinor G.'Adensam, Director Project Directorate II.1 i

Division of-Reactor Projects I/II

~i Office of Nuclear Reactor Regulation

]

I Attachment

  • i Changes to the Technical l

Specifications Date of Issuance: October 5,1990 t

i t

l

(.

t k

I I

1

/)

Drc :I.

DRPR:PM:PDZI RPR:

06C;

.. :......&./7 '

, D:P

DRPR_:

NAME :

. :NLe:d

E em-i DATE:S..........:$M.._.......:u #/ 3190

/i /90

/90

/0/L'/90 __.

0FFICIAL RECORD COPY-t

.a 1

ATTACRNENT TO LICENSE AMENDMENT NO.176 FACILITY OPERATING LICENSE NO. DPR-62 DOCKET NO. 50-324 Replace the following ptges of tt.e Apptno1x A lectr.ical Specifications with the enciesed pages. The revised areas are iridicated by marginal lines.

Remove Pages Insert Paoes 3/4 8-1 3/4 8-1 3/4 8-la 3/4 8-5 3/4 8-5 9

+

I t

h i

1 L

l

3/4.8 ELECTRICAL POWER SYSTEMS i

3/4.8.1 A.C. SOURCES OPERATINC LIMITINC CONDITION FOR OPERATION 3.8.1.1 As a minimum, the f ollowing A.C. electrical power sources shall be OPERABLEt l

t Two physically independent circuits,- per unit, between the offsite l

a.

transmission network and the onsite Class lE distribution system, and b.

Four separate and independent diesel generators, esch with:

1.

A separate engine-mounted fuel. tank containing a minimum of 100 gallons of fuel, 2.

A separate day fuel tank containing a minimum of 22,650 gallons of fuel, and 3.

A separate fuel tr.tnsfer pump.

c.

A plant fuel storage tank containing a minimum of 74,000 gallons of fuel.

1 APPLICABILITY OPERATIONAL CONDITIONS'1, 2, and 3.

ACTION With one of f site circuit of the above required A.C. electrical powg g

a.

sources not capable of-supplying the_ Class IE distribution systems' l.

Demonstrate the OPERABILITY of the remaining A.C. offsite source by performing Surveillance Requirement 4.8.1.1.1.a 'within. 2 hours2.314815e-5 days <br />5.555556e-4 hours <br />3.306878e-6 weeks <br />7.61e-7 months <br /> and at least once per 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> thereafterl 2.

Demonstrate the OPERABILITY of the diesel generators by performing Surveillance Raquirements 4.8.1.1.2.a.4 and 4.8.1.1.2.a.5 within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> and at least once per 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> i

therea f t eri j

3.

Restore the inoperable offsite circuit to' OPERABLE status within.

72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be in at_least HOT SHUTDOWN within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.'

With Unit 1 in OPERATIONAL CONDITION 4 or 5 and. one.of-the required Unit 1 of f site power circuits not capable of supplying the Unitil Class IE.

distribution system, either restore the inoperable Unit 1 offsite circuit to OPERABLE status within 45 days or place = Unit 2 in at least. HOT SHUTDOWN' l

within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br /> and in COLD SHUTDOWN within the following.

24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />. The provisions of ACTIONS 3.8.1.1.a.1, 3.8.1.1.a.2, and '

3.8.1.1.a.3 are not applicable.

BRUNSWICK - UNIT 2 3/4 8 AmendmentL No. f 3(, - 176

'd

~

i ELECTRICAL POWER SYSTEMS LIMITINC CONDITION FOR OPERATION (Continued)

ACTION (Continued):

b.

With a diesel gengratcr of the above required A.C. electrical power source inoperable !

I i

i i

f 4

i i

i I

1 i

I I

1 J

.i A diesel generator shall'be considered to_ be inoperable. from the time of

-f ailure until it satisfies: the requirements of Surveillance Requirements i

4.8.1.1.2.a.4 and 4.8.1.l'.2.a.5.

. BRUNSWICK - UNIT-2

3/4 8-la'

' Amendment. No. 176l

~

i i

I ELECTRICAL POWER SYSTEMS 1

SHUTDOWN LIMITINC CONDITION FOR OPERATION 3.8.1.2 As a minimum, the f ollowing A.C. electrical power sources shall be OPERABLEI I

a.

One circuit per Unit between the of f site transmission network and the onsite Class lE distribution system, and b.

Two diesel generators, one of which shall be diesel generator 3 or 4, as required to operate ECCS systems in accordance with Specifications 3.5.3.1 and 3.5.3.2 1.

Each with a separatet a) Engine-mounted fuel tank containing a minimum of 100 gallons of fuel, b) Day fuel tank containing a minimum of 22,650. gallons of fuel, and e

c) Fuel transfer pump.

I 2.

With a fuel storage tank containing a minimum of'37,000 gallons i

of fuel.

APPLICABILITY OPERATIONAL CONDITIONS 4 and 5.

ACTION r

With less than the above minimum required A.C. electrical power sources OPERABLE, suspend all operations involving irradiated fuel handling, CORE ALTERATIONS, positive reactivity changes, or operations that have the potential of draining the reactor vessel. The provisions of Specification 3.0.3 are not applicable.

SURVEILLANCE REQUIREMENTS i

s 4.8.1.2 The above required A.C. electrical power. sources shall be demonstrated OPERABLE per surveillance - requirement s of Specifications 4.8.1.1.1 and 4.8.1.1.2, except for the requirement of 4.8.1.1.2.a.5.

.)

i i

' BRUNSWICK - UNIT 2 3/4.8-5 Amendment No.176 I

,