Monthly Operating Rept for Dec 1982
ML20064J462
Person / Time
Site: Fort Calhoun 
Issue date: 01/10/1983
From: Mathews T
OMAHA PUBLIC POWER DISTRICT
To:
Shared Package
ML20064J460 List:
References
NUDOCS 8301180082
Download: ML20064J462 (8)


Text

_ _ _ _ _ _

l l

AVERAGE DAILY UNIT POWER LEVEL 50-285 DOCKET NO.

Fort Calhoun Station LwlT DATE January 10, 1983 T. P. Matthews COMPLETED BY (402)536-4733 TELEPHONE December, 1982

,g DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWe-Net)

(ywe.Neti 378.1 0.0

,7 377.8 0.0 2

,3 3

345.5 0.0 39 4

0.0 0.0 20 5

0.0 0.0 21 0.0 0.0 6

22 0.0 0.0 7

23 0.0 0.0 g

24 9

0.0 25 0.0 to 0.0 0.0 26 II 0.0 0.0.

27 12 0.0 0.0 28 33 0.0 0.0 29 0.0 0.0 3o is 0.0 0.0 3

16 0.0 INSTRUCTIONS On this format. list the average dady unit power levelin MWe-Net for each day in the reporting month. Compute to the nearest whole megawatt.

(9/77 )

8301180082 830110 PDR ADOCK 05000285 R

PDR g

dk Be 44

OPERATING DATA REPORT 50-285 DOCKET NO DATE January 10, 1983 COMPLETED BY T. P. flatthews TELEPlf0NE fan? W 6-4733 OPERA TING STATUS F rt Calhoun Station Notes

1. Unit N.ime:

Deceder, M

2. Reporting Period:
3. Licenwd Ihermal Power tMWti:

1500

4. Nameplate Rating (Gross MWe):

501

5. Design Electrie.al Rating (Net MWe):

470 bU1

6. Masimum Dependable Capacity (Gross MWe):

470

7. Masimum Dependable Capacity (Net MWe):
8. If Changes Occur in Capacity Ratings fltems Number 3 Through 7)Since Last Report. Gise Reasons:

N/A

9. Power Lesel To which Restricted,if Any (Net MWe):

N/A

10. Reasons For Restrictions. lf Any:

None This Month Yr. to-Date Cumulative

11. Ilours in Reporting Period 744.0 8,760.0 81,241.0
12. Number Of flours Reactor Was Critical 70.0

/,8/1.5 b4,11U.d

13. Reactor Resene Shutdown flours 0.0 0.0 1,309.5
14. Ilours Generator On Line 70.0 7,857.5 62,94/.5
15. Unit Rewne Shutdown flours 0.0 0.0 U.U
16. Grow Thermal Energy Generated (MWil) 81,785.6 10,914,718.3 77,616,548.4 17 Grow Electrical Energy Generated IMWil) 28,014.0 3.661,387.9 25,/35,333.5 l

1h. Net Electrical Energy Generated (Mwit:

26.433.3 3,482,165.9 24,330,034.4

19. Unit Senice Factor 9.4 89.7 77.5
20. Unit Asailability Factor 9.4 89.7 77.5
21. Unit Capacit> Factor tUsing MDC Neti 7.4 83.2 65.0 l
22. Unit Capacity F. actor (Using DER Neti 7.4 83.2 64.7 l
23. Unit Forc(d Ouraee Rare 49.3 3.6 3.9 l
24. Shutdowns Scheduled Oser Nest 6 Months (Tv e.Dde and QuratioOecembhl-ofFa 1983 refueling outage cornhence early on er 6, 1982.
25. If Shut Down At End Of Report Period Estimated Date of 5 artup:

March 20, 1983

26. Umts In Test Status (Prior to Commercial Operation):

iA Forecast Achieved INITIA L CRITICA LITY INITIA L ELECTRICITY CO\\tMERCI \\ L OPER A TION (9/77) 1

a 50-285 UNIT SilUTDOWNS AND POWER REDUCTIONS DOCKET NO.

UNIT N AM E fort Calhnnn Station DATE January 10. 1983 REPORT MON Hf December, 1982 COMPLET ED BY T. P. Ma t t hnt.m TEl.EPilONE (402)5?6-4731 "E

f

!E 3

Yh Licensee h

Cause & Corrective No.

Date g

3g 4

2g5 Event 3?

j'?

o.

Action to 3.

5 j g5 g Repor'

  • 64 0 H

Pieveni Recurrence di 82-05 821203 F

68 A

3 N/A HA TUP. BIN The reactor tripped on December 3, 1982 because of high turbine vibra-tion. After investigation, it was determined that the first stage rotor of the H.P. turbine had I

broken blades and wiped bearings.

82-06 821206 S

606 C

4 N/A XX XXXXXX Subsequently, it was decided as of December 6, 1982 to commence the 1983 refueling outage approxi-

)

mately one month early.

I i

I 2

3 4

F: Forced Reason:

Method:

Exhibit G -Instructions S: Scheduled A Equipment Failure (Explain) 1 Manual for Preparation of Data

?

ll-Maintenance or Test 2-Manual Serain.

I:nity Sheets for 1.icemee C-Refueling 3 Automitie Serain.

Event Repor t (Lt.lO I'ile (NURI.G.

D Regulatory Restriction 4 Other(Explain) 0161)

E-Operator Training & License Examination F Administrative S

G-Operational Error (Explain)

Exhibii I - Same Source (9/77) ll-Other ( Explain )

(

t

Refualing Information Port Calhoun - Unit No. 1 Peport for the month ending December 1982 1.

Scheduled date for next refueling shutdown.

March 1984 2.

Scheduled date for restart following refueling.

May 1984 3.

Will refueling or resumption of operation thereafter require a technical specification change or other license amendnent?

Yes a.

If answer is yes, ohat, in general, will these be?

A Technical Specification Change b.

If answer is no, has the reload fuel design and core configuration been reviewed by your Plant Safety Review Comittee to deter-mine whether any unreviewed safety questions are associated with the core reload.

c.

If no such review has taken place, when is it scheduled?

4.

Scheduled date(s) for submitting proposed licensing Methodology - Dec. 1983 action and support information.

Tech. Specs. - Feb.1984 5.

Inportant liwnsing considerations associated with refueling, e.g., new or different fuel design or supplier, unreviewed design or performance analysis l

nethods, significant changes in fuel design, new operating procedures.

6.

The number of fuel assenblies: a) in the core 133 assmblies b) in the spent fuel pool 237 l

c) spent fuel pool storage capacity 483 d) planned spent fuel pool storage capacity 728 7.

'Ihe projected date of the last refueling that can be-discharged to the spent fuel pool assuming the present licensed capacity.

1985 Prepared by o2 Date January 4, 1983 y

O!!AHA PUBLIC POWER DISTRICT Fort Calhoun Station Unit No.1 December, 1982 Monthly Operations Report I.

OPERATIONS

SUMMARY

Fort Calhoun Station entered the month of December at 78% power.

On December 3, 1982, the plant tripped off line due to high vi-bration of the turbine bearings. Upon investigation, the turbine was found to have lost six buckets off the first stage high pres-sure rotor and wiped several of the bearing facings.

It was then resolved to move up the scheduled date of the maintenance / refueling I

outage.

Presently, the control rods have been uncoupled, the reactor coolant system is at the middle of the hot leg and steam generator eddy current testing has been completed.

In preparation for the full off load of the reactor core to the spent fuel pool, cutting up of used int _re flux detectors for proper storage has been completed and the shuffle of spent fuel already in the pool has commenced for allotment of room.

Annual licensed operator requalification examinations were com-pleted by December 2, 1982.

No safety valve or PORV challenges occurred.

A.

PERFOR}iANCE CHARACTERISTICS LER Number Deficiency NONE B.

CHANGES IN OPERATING METHODS NONE C.

RESULTS OF SURVEILLANCE TESTS AND INSPECTIONS Surveillance tests as required by the Technical Specifications Section 3.0 and Appendix B, were performed in accordance with the annual surveillance test schedule. The following is a summary of the surveillance tests which resulted in Operation Incidents and are not reported elsewhere in the report:

Operation Incidents Deficiency 01 1615 ST-ES F-3, During the performance of ST-ESF-3, F. 2 F.2, pressure switches / sensors were found out of calibration, A/PC-742-2, B/PC-742-2, C/PC-742-2, D/742-2, A/PC-742-1, C/PC-742-1, D/PC-742-1 O

i Monthly Operations Report December, 1982 Page Two C.

RESULTS OF SURVEILLANCE TESTS AND INSPECTIONS (continued)

Operation Incidents Deficiency 01 1612 ST-MSSV-1 During the performance of ST-MSSV-1, F.1 F.1, valves MS-275, 278, 280 and 282 failed to actuate within tolerance of setpoints.

01 1616 ST-RM-4 During performance of ST-RM-4, F.1, F.1 sampler OAA was found to be inoperable due to a blown fuse.

01 1617 ST-FW-2 During performance of ST-FW-2, F.2, F.2 flow indicators FI-1109/FI-1100 lo-cated on AI-66A/B were found to be operating out of setpoint tolerance.

D.

CHANGES, TESTS AND EXPERIMENTS CARRIED OUT WITHOUT C0K4ISSION APPROVAL Procedure Description SP-PORV-2 PORV Setpoints. Completed per procedure.

The performance of this procedure did not constitute an unreviewed safety question as defined in 10CFR 50.59 because it was performed using normal plant ' operating procedures ensuring the operability of redundant equipment during setpoint changes.

10/23/82 PORV Setpoints. Completed per procedure.

The performance of this procedure did not constitute an unreviewed safety question as defined in 10CFR 50.59 because it was performend using normal plant operating procedures ensuring the operability of redundant equipment during setpoint changes.

10/27/82 PORV Setpoints. Completed per procedure.

The performance of this procedure did not constitute an unreviewed safety question as defined in 10CFR 50.59 because it was performend using normal plant operating procedures ensuring the operability of redundant equipment during setpoint changes.

s O

Monthly Operations Report December, 1982 Page Three D.

CHANGES, TEST AND EXPERIMENTS CARRIED OUT WITHOUT COMMISSION APPROVAL Procedure Description SP-ECT-1 Eddy Current Testing of Heat Exchanger Tubes. Completed per procedure.

This procedure did not constitute an unreviewed safety question as defined by 10CFR 50.59 since it only involved eddy current testing of feedwater heaters.

SP-IC-ll Disposal of Irradiated Incore Detector.

Completed per procedure.

This procedure did not constitute an unreviewed safety question as defined by 10CFR 50.59 since it only involved the cutting and loading of incore de-tectors. Appropriate radiation pro-tection procedure were followed.

E.

RESULTS OF LEAK RATE TESTS Local leak rate tests conducted during refueling outages were performed during December. A summary report will be submitted as required by the Technical Specifications.

F.

CHANGES IN PLANT OPERATING STAFF NONE G.

TRAINING Training in December was directed at General Employee initial and refresher badge certification. Classes were included to handle the influx of personnel due to the forced outage in early December. Topics include security, tagging, procedural compliance, radiation protection, crane operator certification, hydrotesting and fire barriers.

H.

CHANGES, TEST AND EXPERIMENTS REQUIRING NUCLEAR REGULATORY COMMISSION AUTHORIZATION PURSUANT TO 10CFR 50.59.

NONE e

Monthly Operations Report December, 1982 Page Four II.

MAINTENANCE (Significant Safety Related)

M.0. #

DATE DESCRIPTION CORRECTIVE ACTION 17298 11/16/82 RM-056 will not cal check properly.

Replaced high alarm switch.

17408 12/3/82 AC-3B component cooling water Completed per MP-AC-3-1.

pump - inboard seal leaks.

].

17500 12/9/82 Raw water strainer will not run Cleaned and lubed breaker.

j electrically.

N.

W. G. Gates Manager Fort Calhoun Station i