Text
. - -
i.
OPERATING DATA REPORT 4
DOCKET NO. 50-302 DATE 9/1/82 COMPLETED RY n nnonre TELEPilONE (904 f795-6486 OPERATING STATUS
- 1. Unit Name:
Crystal River Unit #3 Notes
- 2. Reporting Period:
8/1/82 - 8/31/82
- 3. Licensed Thermal Power (MWt):
2544
- 4. Nameplate Rating (Gross MWe):
890
- 5. Design Electrical Rating (Net MWe):
m
- 6. Maximum Dependable Capacity (Gross MWe):
R45
- 7. Maximum Dependable Capacity (Net MWe):
806
- 8. If Changes Occur in Capacity Ratings (Items Number 3 Through 7) Since Last Report. Give Reasons:
N/A
- 9. Power Level To Which Restricted,If Any (Net MWe):
2475 MM chormn1.
- 10. Reasons For Restrictions,if Any:
Pump Power Monitors in bypass.
This Month Yr.-to-Date Cumulative f
- 11. liours In Reporting Period 744 5831' 47951
- 12. Number Of lionrs Reactor Was Critical 723.4 4799.5 30248.89
- 13. Reactor Reserve Shutdown flours 0
71.1 1280.3
- 14. Ilours Generator on-Line 720.3 4718.6 29530.78'
- 15. Unit Resene Shutdown flours 0
0 0
- 16. Gross Thermal Energy Generated (MWil) 1630568 10624795 65991736
- 17. Gross Electrical Energy Generated (MWil) 555261 3607499 -
22407090
- 18. Net Electrical Energy Generated (MWH) 527888
'1430039 21259337
- 19. Unit Service Factor 96.8%
80.9%
61.6%
- 20. Unit Asailability Factor 96.8%
80.9%
61.6%
- 21. Unit Capacity Factor (Using MDC Net)
'88.0%
73.0%
56.5%
- 22. Unit Capacity Factor (Using DER Net) 86.0%
71.3%
53.7%
- 23. Unit Forced Outage Rate 3.2%
19.1%
25.5%
- 24. Shutdowns Scheduled Oser Next 6 Months (Type. Date,and Duration of Each):
Nnno
- 25. If Shut Down At End Of Report Period. Estimated Date of Startup:
- 26. Units in Test Status (Prior to Commercial Operation):
Forecast Achiesed i
INITIA L CRITICALITY 1/14/77.
INITIAL ELECTRICITY 1/30/77-COMMERCIAL OPER ATION 3/13/77 8209170004 820913 (9/77)
PDR ADOCK 05000302 R
v n
y gn
,e
,, -~
,m_
o AVERAGE DAILY UNIT POWER LEVEL DOCKET NO.
50-302 UNIT Fi_CRP-3 DATE 9/1/82 COMPLETED BY D. Bostart I
TELEPilONE (904) 795-6486-MONTli August 1982 DAY
~ AVER AGE DAILY l'OWER LEVEL DAY AVER AGE DAILY POWER LEVEL (MWe Net)
(MWe-Net) 1 780 17 735 785 2
33 780 81 788 3
,9 4
663 20 785 5
662 21 802 691 795 6
22 1
7 764 23 779 8
295 24 815 9
336 762 25 10 789 26 791 11 785 27 773 12 801 481 yg 13 760 29 507 l
14 767 30 569 15 773 571 3
789 16 I
I INSTRUCTIONS On this format.hst the average daily unit power level in MWe-Net for each day in the reporting inonth. Compute to i
the nearest whole megawatt.
(9 /77 )
.. r
O O
'O
\\
1 1 UNIT SilUTDOWNS AND POWER REDUCTIONS DOCKET NO.
5f.4f I?
UNIT NAME FLCRP-3 DATE _9/?/n?
COMPLETED BY M it en1ver
- REPOR F MONTil 8/82 TELEPilONE (onM 70s AAAA w.
jg 3
[i Licensee h
Cause & Corrective g
No.
Date e-.
E 4
33 Event c; ?
c?
Action to S
[@
3d5 Report rN 0
!0 Present Recurrence e
S L
82-23 820804 F
B N/A N/A HC HTEXCH Reduced power due to turtle grass problems at the circulating water inlets and to clean waterboxes.
82-24 820808 F
23.7 A
3 N/A CB INSTRU Flow indicator in A loop of the RCS failed, causing the system to change FW flow with a final result of a reactor trip on high pressure.
82-25 820827 S
H N/A N/A HH MECFUN Reduced power to the 65% to 70% FP range to replace the temporary condensate pump with the original which has been repaired.
I i
I 2
3 4
F: Forced Reason:
M ?.cd:
Exhibit G - Instructions S: Scheduled A-Equipment Failure (Explain) 1-M.nual for Preparation of Data
.l B-Maintenance of Test 2 Manual Scram.
Entry Sheets for Licensee -
C Refueling 3-Automatic Scram.
Event Report (LER) File INUREG-l D-Regulatory Restriction 4-Other (Explain) 0161)
E-Operator Training & License Examination F-Administrative 5
i G-Operational Error (Explain)
Exhibit I Same Source.
(9/77)
Il-Other (Explain) 1 i
4
MONTHLY OPERATIONAL SUmfARY STATD!Eh7 j
DOCKET NO. 50-302 UNIT FLCRP-3 DATE 9/2/82 COMPLETED BY M.W. Culver TELEPHONE (904) 795-6486 MONTil Att gus t 1982
SUMMARY
STATDfENT:
The unit experienced one shutdown and two significant power reductions this month.
O l
i i
i d