Text
__
o UStiRC REGIOt1 "
ATL AfiTA, GEC P; B2 JUN 21 A
E Brunswick Steam Electric Plant P. O. Box 10429 Southport, NC 28461-0429 June 18, 1982 fit'd :
B09-13510 SERIAL: BSEP/82-1380 Mr. James P. O'Reilly, Director U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, GA 30303 Brunswick Steam Electric Plant, Unit No. 2 License No. DPR-62 Docket No. 50-324 Reponse Per IE Bulletin 80-13
Dear Mr. O'Reilly:
As required by IE Bulletin 80-13, a visual inspection of the Unit No. 2 core spray spargers has been performed. During this inspection, a crack was located on the A loop upper clockwise sparger arm near the weld to the T-box at 170 azimuth. This crack is circumferential and extends approximately 120 around the pipe. Exhaustive analysis and evaluation of the sparger strut integrity and ECCS performance determined that no corrective action was required for continued operaticn with this crack. However, to allay any potential concerns of safe plant operation, Brunswick has decided to install a clamp over the cracked area. This clamp will ensure that the sparger will retain integrity and the flow injection distribution will not be significantly affected.
Very truly yours,
.Q C. R. Dietz, General Manager Brunswick Steam Electric Plant RMP/tt cc:
Mr. R. C. DeYoung 8207010162 820618 PDR ADOCK 05000
%EM a
a