ML20063C180

From kanterella
Jump to navigation Jump to search
Third Interim Deficiency Rept Re Environ Qualification of safety-related Electrical Components.Initially Reported on 811021.Util Establishing Qualification Program W/B&W & Completing Corrective Actions.Next Rept Expected by 830805
ML20063C180
Person / Time
Site: Bellefonte  Tennessee Valley Authority icon.png
Issue date: 08/16/1982
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
RTR-NUREG-0588, RTR-NUREG-588 10CFR-050.55E, 10CFR-50.55E, IEB-79-01B, IEB-79-1B, NUDOCS 8208270107
Download: ML20063C180 (12)


Text

r TENNESSEE VALLEY AUTHORITY CHATTANOOG A. TENNESSEE 374of 400 Chestnut Street Tower II August 16, 1982 BLRD-50-438/81-66 BLRD-50-439/81-65 U.S. Nuclear Regulatory Commission Region II Attn:

Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303

Dear Mr. O'Reilly:

BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - ENVIRONMENTAL QUALIFICATION OF SAFETY-RELATED ELECTRICAL COMPONENTS - BLRD-50-438/81-66, BLRD-50-439/81 THIRD INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector R. V. Crlenjak on October 21, 1981 in accordance with 10 CFR 50.55(e) as NCRs BLN NEB 8113 through BLN NEB 8118. This was followed by our first interim report dated November 16, 1981. Related NCRs BLN NEB 8119, 8120, and 8205 and BLN EEB 8203 were reported in our second interim report dated May 10, 1982. Since that time, related NCRs BLN NEB 8208, 8209, 8211, 8213, 8214, and 8215, and GEN QAB 8204 have also been reported. Enclosed 4

is our third interim report. We expect to submit our next report by August 5, 1983 If you have any questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY Y

L. M. Mills,' Manager Nuclear Licensing 4

Enclosure cc:

Mr. Richard C. DeYoung, Director (Enclosure)

[

Office of Inspection and Enforcement

b G

U.S. Nuclear Regulatory Commission Washington, DC 20555

's

[y Mr. James McFarland (Enclosure)

.5

'2 O

'l Senior Project Manager

~~

Babcock & Wilcox Company P.O. Box 1260 c.n Lynchburg, Virginia 24505 i

WFICIALcoby,d

~-

8208270107 820816 e

PDR ADOCK 05000438 I

1 S

PDR An Equal Opportunity Employer

Y ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2

~

ENVIRONMElGAL QUALIFICATION OF SAFETY-RELATED ELECTRICAL COMPONENTS NCRs BLN NEB 8113, 8114, 8115, 8116, 8117, 8118, 8119, 8120, 8205, 8208, 8209, 8211, 8213, 8214, 8215, BLN EEB 8203, AND GEN QAB 8204 BLRD-50-438/81-66, BLRD-50-439/81-65 10 CFR 50.55(e)

THIRD INTERIM REPORT Description of Deficiency During TVA's NUREG-0588 environmental qualification program, the components listed in Table I - Parts A and B (attached) were identified as potentially deficient because of insufficient documentation to verify that the equipment is environmentally qualified. This equipment was procured before the issuance of NUREG-0588.

Interim Progress Since TVA's previous report six additional nonconformances have been generated to identify equipment potentially deficient because of insufficient document. One previous report, NCR BLN NEB 8119, has been revised; and another, NCR BLN EEB 8203, has additional corrective action.

Specific information for these NCRs is included in Table I (attached).

TVA is in the precess of establishing a qualification program with B&W and completing the corrective actions stated in the previous report. TVA has also generated NCR GEN QAB 8204, to document the failure to develop a procedurally controlled system to ensure adequate qualification of electrical equipment during the design, procurement, installation, and operation phases. It is anticipated that resol,ution of this nonconformance will complete the actions necessary to prevent recurrence.

ie s k.

%+

f, TABLE I - Part A 1

Corrective Action /

B&W NCR No.

TVA UNID No.

Component No.

Model Manufacturer Resolution BLNNEB8113 1NL and 2NL-ILT-001B-B CF-LT3A2 N2BQ75221X Bailey Heter Co.

TVA has reviewed all available qualification (Differential

-001A-A CF-LT3A1 documentation for this

-002A-A CF-LT3B1 Pressure equipment and has Transmitter)

-002B-B CF-LT3B2 concluded that the devices are acceptable for their intended use.

BLNNEB8114 1NC and 2NC-IPT-004B-A RC-PT17-3 1152GP9A92PB Rosemount, Inc.

TVA has reviewed all (Pressure

-004A-B RC-PT17-4 available qualification documentation for this Transmitter) equipment and has concluded that the devices are not acceptable for their intended use. To establish full equipment qualification, TVA will replace the devices with fully qualified units or will type-test the devices j

to qualify fully per the NUREG-0588 guidelines.

BLNNEB8115 1CF and 2CF-ILT-916B-B SP-LT9A2 N1BQ74221 Bailey Meter Co.

TVA has reviewed all available qualification (Differential

-916A-A SP-LT9A3 documentation for this Pressure

-925A-A SP-LT9B3 equipment and has I

Transmitter)

-925B-B SP-LT982 concluded that the devices are acceptable for their intended use.

N,

i F

2 TABLE I - Part A B&W Corrective Action /

NCR No.

TVA UNID No.

Component No.

Model Manufacturer Resolution l

BLNNEB8116 1NL and 2NL-IPT-001A-A CF-PT4A1 N2BQ68221X Bailey Heter Co.

TVA has reviewed all (Differential

-001B-B CF-PT4A2 available qualification Pressure

-002A-A CF-PT4B1 documentation for this Transmitter)

-002B-B CF-PT4B2 equipment and has concluded that the devices are not acceptable for their intended use. To establish full equipment qualification, TVA will replace the devices with fully qualified units. No type-test of this device will be undertaken as it is not designed to survive a loss-of-coolant accident.

BLNNEB8118 1NC and 2NC-IFT-907E-D RC-FT1 A1 N1BQ86221 Bailey Meter Co.

TVA has reviewed all l

(Differential

-907F-F RC-FT1 A2 available qualification Pressure

-907A-E RC-FT1 A3 documentation for this Transmitter)

-907B-G RC-FT1 A4 -

equipment and has

-913E-D RC-PT1B1 concluded that the devices

-913F-F RC-FT1B2 are not acceptable for

-913A-E RC-FT1B3 their intended use. To

-913B-G RC-FT1B4 establish full equipment (Pressure Transmitter)-IPT -903D RC-PT2A1 N1KS69221 Bailey Meter Co.

qualification, TVA will

-904F RC-PT2A2 replace the devices with

-906D RC-PT2A3 fully qualified units or

-905F RC-PT2A4 type-test the devices to

-S14G RC-PT2B1 qualify fully per the 4

-915E RC-PT2B2 NUREG-0588 guidelines.

-916G RC-PT2B3

k li t TABLE I - Part A 3

Corrective Action /

B&W NCR No.

TVA UNID No.

Component No.

Model Manufacturer Resolution l

BLNNEB8117 1NC and 2NC-ITE-900A-A RC-TE3A1 177 HW Rosemount, Inc.

TVA has reviswed all (Resistance

-902A-D RC-TE3A2 available qualification Temperature

-900B-A RC-TE3A3 documentation for this Detector)

-901A-F RC-TE3A4 equipment and has con-

-919B-B RC-TE3B1 cluded that the devices

-917A-E RC-TE3B2 are not acceptable for

-919A-B RC-TE3B3 their intended use. To

-918A-G RC-TE3B4 establish full equipment

-911B-B RC-TE4A3 qualification, TVA will

-911A-B RC-TE4A4 replace the devices with

-908A-D RC-TE4A5 rully qualified units or

-926A-F RC-TE4A7 type-test the units to

-910A-E RC-TE4A9 qualify rully per the

-912A-G RC-TE4A11 NUREG-0588 guidelines.

-924B-A RC-TE4B3

-924A-A RC-TE4B4

-922A-D RC-TE4BS

-920A-F RC-TE4B7

-925A-E RC-TE4B9

-923A-G RC-TE4B11,

-9018-F RC-TE3A6 These devices have been

-902B-D RC-TE3AS added to this NCR by

-917B-E RC-TE3B5 revision 2.

They are

-918B-G RC-TE3B6 recent additions to the latest Class IE equipment list.

t.

i 4

TABLE I Dart A B&W Corrective Action /

NCR No.

TVA UNID No.

Component No.

Model Manufacturer Resolution BLNNEB8119 1NC and 2NC-IPT-906-D RC-PT2A3 N1KS69221 Bailey Meter Co.

TVA is reviewing (Pressure

-905-F RC-PT2A4 this NCR Transmitter)

-916-G RC-PT2B3 in conjunction with other

]

-004B-A RC-PT17-3 1152GP9A92PB Rosemount, Inc.

NCits covering these

-004A-B RC-PT17-4 devices in order to 1NC and 2NC-IFT-907B-G RC-FT1A4 N1BQ86221 Bailey Meter Co.

determine the alternatives (Differential

-913B-G RC-FT1B4 and their impact on Pressure achieving full equipment Transmitter) qualification.

l 1NL and 2NL-IPT-001A-A Not Not Bailey Meter Co.

-001B-B available available

-002A-A at this at this

-002B-B time.

time.

BLNNEB8120 1NC and 2NC-ITE-900A-A RC-TE3A1 177HW Rosemount, Inc.

TVA has reviewed all (Resistance

-900B-A RC-TE3A3 available qualification Temperature

-919B-B RC-TE3B1 documentation for this Detector)

-919A-B RC-TE3B3 equipment and has con-

-911B-B RC-TE4A3 cluded that the devices are not suitable for their

-911A-B RC-TE4A4

-924B-A RC-TE4B3 intended use. Since NCR

-924A-A RC-TE4B4 BLNNEB8117 concerns these same devices, this NCR will be closed and further resolution of this problem I

will be addressed in NCR BLNNEB8117.

.s

I:

E

{

5 TABLE I - Part A B&W Corrective Action /

NCR No.

TVA UNID No.

Component No.

Model Manufacturer Resolution

~,

BLNNEB8205 NV-EMOT-001A NA 900 HP Motor Westinghouse TVA will continue to NV-EMOT-002A search for documentation NV-EMOT-003B to demonstrate adequacy of ND-EMOT-001A 700 HP Motor Westinghouse the motors to meet or ND-EMOT-002B exceed the requirements of j

KC-EMOT-001A 700 HP Motor Allis-Chalmers the environment to which KC-EMOT-002B they may be subjected.

I KC-EMOT-003A Motor NV-EMOT-856A was NS-EMOT-001A 500 HP Motor Allis-Chalmers inadvertently included in NS-EMOT-002B this NCR and is being ND-EMOT-216 A 1 HP Motor General Electric deleted.

ND-EMOT-221B NV-EMOT-838B 1 HP Motor General Electric NV-EMOT-858A NV-EMOT-860A 9

+4 i

TABLE I - Part B 1

i B&W NCR No.

TVA UNID No.

Component No.

Model Manu facturer Correction Action / Resolution BLNNEB8208 VJ-EMOT-034-B 66-26-1170 Reliance TVA.dces not have sufficient documentation 600287-14 to permit full qualification of these l

-035-A 66-26-1170 Reliance electric motors per NUREG-0588. TVA is 600287-14, making efforts to obtain additional data.

1

-036-B 66-26-1170 Reliance If sufficient additional data cannot be 600287-14 obtained, TVA will perform additional analysis or type tests as required to meet l

NUREG-0588.

l l

BLNNEB8209 KC-IFCV-147-A CC-HV22 SMB-00-5 Limitorque TVA does not have sufficient documentation l

Limitorque to verify that these KC-IFCV-212-A CC-HV2 Limitorque Limitorque operators are fully qualified KD-IFCV-045-B CC-HV3 KD-IFCV-054-A CC-HV4 Limitorque per NUREG-0588. TVA is making efforts to NV-IF CV-101-A MU-HV-51A SMB-00-7.5 Limitorque obtain additional qualification data.

Limitorque When the data search is complete, TVA will

-113-A

-51B Limitorque perform additional analysis or type tests

-213-B

-51C Limitorque as required to meet NUREG-0588.

-225-B

-51D ND-IFCV-010-A DH-HV-7A SB-005-15 Limitorque Limitorque N D-IFCV-104-B

-7B Limitorque ND-IFCV-192-B

-9B NV-IFCV-077-A MU-HV-49A SBM-00-25 Limitorque Limitorque

-411-B

-49B Limitorque

-419-B

-47B

-450-A

-47A Unknown

  • Limitorque BLNNEB8211 NL-IZS-076-A EA740-40110 Namco TVA does not have sufficient documentation to NV-IZS-119A-A EA170-32100 Namco verify that these zone switches are NV-IZ3-119B-A EA170-32100 Namco qualified per NUREG-0588. TVA is making CA-IZS-052A-B EA170-100 Namco efforts to obtain additional qualification Namco data. In addition, investigations are CA-IZS-052B-B Namco being made to remove the Startup and CA-IZS-053A-A Namco Recirculation System from the Auxiliary Building CA-IZS-053B-A e.,*

Namco in order to produce a less harsh environ-CA-IZS-062A-B Namco ment. When the data search is complete, CA-IZS-062B-B Namco TVA will perform additional analysis or CA-IZS-063A-A Namco type testa as required to meet NUREG-0588.

CA-IZS-063B-A Namco ND-IZS-064A-A

2 TABLE I - Part B B&W NCR No.

TVA UNID No.

Component No.

Model Manufacturer Correction Action / Resolution Namco i

BLNNEB8211 ND-IZS-064B-A Namco (Cont'd.) ND-IZS-158A-B Namco ND-IZS-158B-B Namco NV-IZS-036A-A Namco

-036B-A Namco WL-IZS-067A-A

-067B-A BLNNEB8213 KC-IFCV-148B CC-HV24 SMB-00-5 Limitorque TVA does not have sufficient documentation Limitorque to verify that these Limitorque operators

-211B CC-HV1 Limitorque are qualified per NUREG-0588. TVA is KD-IFCV-053B CC-HV5 NC-IFCV-010 A RC-HV2 SMB-00-10 Limitorque making efforts to obtain additional

-012A SMB-005-10 Limitorque qualification data. When the data search

-057A RC-HV11 SMB-00-10 Limitorque is complete, TVA will perform additional NL-IFCV-076A SB-4-250 Limitorque analysis or type tests as required to meet

-079B SB-4-250 Limitorque NUREG-0588.

NV-IFCV-022B MU-HV-1C SMB-00-10 Limitorque Limitorque

-026B MU-HV-2A Limitorque

-029B

-1D Limitorque

-033B

-2B

-062B

-37A SMB-000-5 Limitorque Limitorque

-065B

-37B

-c68B

-37C Limitorque

-071B

-37D Limitorque WG-IFCV-011B WD-HV-1 SMB-000-2 Limitorque WL-IFCV-068B

-3 SMB-00-10 Limitorque

-090B

-5 SMB-005-10 Limitorque BLNNEB8214 KC-IFT-006 A CC-FT21A N2BQ74221 Bailey Meter Co TVA does not have sufficient documentation Bailey Meter Co to verify that these pressure transmitters KE-IFT-962B-A RBC-FT1A2 Bailey Meter Co are qualified per NUREG-0588. TVA is

,h-NV-ILT-004A-A MU-LT16-2 KD-ILT-003A-A CC-LT11-1 N2BQ73221 Bailey Meter Co making efforts to obtain additional NV-IFT-844A MU-FT30A N2BQ85221 Bailey Meter Co qualification data.

In addition,

-845A MU-FT30B Bailey Meter Co investigations are being made to remove

-846B MU-FT30C Bailey Meter Co the Startup and Recirculation System from

-847B MU-FT30D Bailey Meter Co the Auxiliary Building in order to

3 TABLE I - Pcrt B B&W NCR No.

TVA UNID No.

Component No.

Model Manufacturer Correction Action / Resolution BLNNEB8214 NS-ILT-003B-B RBS-LT11-2 N2BQ75221 Bailey Meter Co produce a less harsh environmenh. When (Cont'd.)

NV-IFT-841A M1-FT50A N2BQ86221 Bailey Meter Co the above efforts have been completed, TVA

-848A MU-FT50C Bailey Meter Co will perform additional analysis or type

-IPT-004A MU-PT21 N2KS66221 Bailey Meter Co tests as required to meet NUREG-0588.

SM-IPT-901A-B SP-PT12A1 N2KS69221 Bailey Meter Co

)

-901B-A 2

Bailey Meter Co 1

Bailey Meter Co

-902A-B B1

-902B-A 2

Bailey Meter Co

-903-D A3 Bailey Meter Co

-904-G 4

Bailey Meter Co

-905-F 5

Bailey Meter Co

-910-D B3 Bailey Meter Co

-911-G 4

Bailey Meter Co

-912-F GS N2KS69221 Bailey Meter Co BLNNEB8215 IP-IXE-005 NI-5-NT WL-24061 Westinghouse TVA does not have sufficient documentation

-006 "

Westinghouse to verify tnat these power range detectors

-007 Westinghouse are qualified per NUREG-0588. TVA is

-008 "

Westinghouse making efforts to obtain additional data.

I When the data search is complete, TVA will perform additional analysis or type test as necessary.

BLNEEB8203 III and 2IX-ILPA-004-A

'NA NA York Electro-Additional research has shown that the (Seal-Tite

-052-A Panel Control correct threshhold of failuge for Type EF

-056-A plasticized PVC is 5.5 x 10 rads TID, Flexible

-058-A per EPRI-2129 Therefore, all but 13 f

Conduit on

-070-A of the panels listed can be used as is.

Local Panels)

-072-A

-081-A Thefollowing13panelshaveragiation

-083-A exposures greater than 5.5 x 10 rads TID,

\\

-085-A and the SEAL-TITE Type EF flexible conduit

-086-A must be replaced with environmentally

-094-A qualified stainless steel flexible

-101-A conduit:

-119-B

-120-B IIX and 2IX-ILPA-119-B

-121-A

-120-B

i f-

?

4' TABLE I - P rt B i

B&W NCR No.

TVA UNID No.

Component No.

Model Manufacturer Correction Action / Resolution BLNEEB8203

-122-A NA NA York Electro-

-122-A (Cont'd.)

-123-A Panel Control

-123-A

-141-A

-177-A

-178-A

-177-A

-178-A 2IX-ILPA-179-B 2IX-ILPA-179-B III and 2IX-ILPR-001-D

-002-A

-003-F

_-004-E

-005-B

-006-G

-009-D

-011-B

-012-A

-013-A

-014-B

-016-A

,-019-A

-020-B

-021-A

-022-B

-023-D 4

-024-E

-025-F

-026-G

-027-A

-028-E

-029-A

-034-B r

1

-035-A

-036-B

-038-B

.-039-F

-040-G

-041-A

-042-B

-043-A

-044-B

-045-A

- ~. - -. - _ _.

t f

jl 5

TABLE I - Pert B B&W NCR No.

TVA UNID No.

Component No.

Model Manufacturer Correction Action / Resolution l

1 k

BLNEEB8203

-049-A NA NA York Electro-(Cont'd.)

-050-B Panel Control I

-051-A 1

-058-A I

-060-A

}

-061-A

-062-B

-066-A

-067-B

-017-B i

-059-B 1

l

.s e

i li l

  • N.

i P

?

. -.