I (9SMUD SACRAAMNTO MUNCPAL UTMJTy DISTRK:7 O E203 3 Stest, Bos 15430, SacramenECafNbmle 35413; SIS) 452-32?l 2...

RJR 80-561 y

l

%embeg33/ M80?3 3 CO i 'l.

-.~-(

c It e

i t

.~

= pd NMES Mr. R. H. Engelken, Director t.

I':: ~

" I Cil Region V Office. of Inspection & Erfforcement.

U. S. Nuclear Regulatory' Commission 1990 North California Boutavard Walnut Creek Plaza, ' Suite 202 Walnut Creek, California 98 936 6

Re:

Operating License BPR-54 Docket No.56-312 Reportable.0ccurrence 80.

-Decr Mr. Engelken:

l In accordance with Technical Specifications Section 6.S.4.1(1), the I

Sacramento'thsitcipal Utility District is hereby submitting the following written confirmation of a 24-hour Licensee Event Report initially reported to Mr. E. Zwetzit, i of your office on October ~31,1980.

As a result of ' LEE Bulletin '73-Cl3 review, it was determined that at present no qualification docunentation'is available for the pressure switches utillaed in the mein steam system. 'These pressure switches are manufactured by i

Meletron Corporation and are utilized to initiare isolation of the steam generator fross the main feedwater following a low pressure ' indication.

Due to the : requirements of IIUREG 0660, the District is presently design-

[

ing a new system in the e.res of Main Steam Lir.c failure Logic.

The new system l

will be designed with components meeting all the required qualifications.

Instal-l lation of the new system will alleviate the necessity of requiring qualification documentation of the Heletron pressure switches.

Elther the new systest will be Installed and operational or the existing Meletron switches will be. replaced l

within the time frame specified in the bulletin.

A followup report wl11 he submitted within T4 days.

R**'

i

'/

I l

sb It. J.

ris i

Manar

, Nuct r Operstions RJR:HH:.}r THIS DOCUMENT CONTAINS POORQUAUTYPAGES

[>Yq do 8C11120 NO

~