November 2,1978 j
g Docket No.: 50-302 Mr. W. P. Stewart Director, Power Production Florida Power Corporation P. O. Box 14042, liail Stop C-4 T' '
St. Petersburg, Florida 33733
Dear Mr. Stewart:
We are reviewing your submittal of July 27, 1978, regarding'a permanent solution to the ECCS small break analysis problem, and have determined that the additional infonnation identified in the enclosure is necessary to continue our review. You are requested to provide this information within 20 days of the date of this letter.
Sincerely, O
Q
'f> C J-h
$-NWJ Robert W. Reid, Chief Operating Reactors Branch #4 Division of Operating Reactors t
Enclosure:
Additional Information Request cc w/ enclosure: See next page 18112003c;(
p i
~,,,s
.~w-an
-~.o ww w ww
-w-wa--sm-
.m em-am---n..
-. Men.-
n.
...eu.-
P Florida Power Corporation cc: Mr. S. A. Brandimore Vice President and General Counsel P. O. Box 14042 i
St. Petersburg, Florida 33733 Crystal River Public Library Crystal River, Florida 32629 es
(
l i
9 F
l G
..--mm--.,
_,___-.-v.y,
,-,m-- -...
v.--,
ADDITIONAL INFORMATION REQUEST 1.
Please provide schematic diagrams showing controls and indications related to motor-operated molded case breakers and electro-mechanical transfer switches.
2.
Label Figure 2 to show the normally open (NO) and normally closed (NC) alignment of the breakers in MCC's that supply the MUV's.
3.
To meet single failure criteria the motor-operated molded case breakers that are connected to separate ES HCC's should be physically separated. Verify that this will be the case.
4.
What is the earliest date by which this modification could be completed?
l l