4 T.S.6.9.1.6 PHILADELPHIA FLECTRIC COMPANY LIMERICK GENERATING STATION P. O. BOX 2300 SANATOGA PA 19464-2300 l
l November 9, 1993 Docket Nos. 50-352 i
50-353 License Nos. NPF-39
)
NPF-85 U.
S. Nuclear Regulatory Commission Attn:
Document Control Desk Washington, DC 20555
Subject:
Limerick Generating Station Monthly Operating Report For Units 1 and 2 Enclosed are the monthly operating reports for Limerick Units 1 and 2 for the month of October, 1993 forwarded pursuant to l
Technical Specification 6.9.1.6.
l l
Very truly yours,
/
t' James A. Muntz Director - Site Engineering jjm Enclosures cc:
T.
T. Martin, Administrator, Region I, USNRC (w/ enclosures)
N.
S.
Perry, USNRC Senior Resident Inspector LGS (w/ enclosures)
D.
R. Helwig, Vice President, Limerick Generating Station l
l 9311150311 931031 W
gDR ADOCK 05000352 fl
/
3 l l
PDR y
Docket Wo. 50-352 Attachment to Monthly Operating Report for October 1993 Limerick Generating Station Unit 1 October 1 through October 31, 1993 I.
Narrative Summary of Operatino Experiences Unit 1 began this operating period at 100% of rated thermal i
power (RTP).
On October 8, 1993 power began to decrease as a result of end of cycle coastdown.
On October 10, 1993 at 1015 hours0.0117 days <br />0.282 hours <br />0.00168 weeks <br />3.862075e-4 months <br /> power was reduced to 92%
of RTP for Main Turbine Valve testing.
Power was restored to 98% RTP at 1203 hours0.0139 days <br />0.334 hours <br />0.00199 weeks <br />4.577415e-4 months <br />.
On October 15, 1993 extraction steam was removed from the sixth Feedwater Heaters and power was restored to 100% RTP.
Unit i ended this operating period at 99% rated' thermal power in end of cycle coastdown.
II.
Challences to Main Steam Safety Relief Valves There were no challenges to the Main Steam Safety Relief Valves during the month of October.
l l
4 i
i i
+*
~
AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50 - 352 s
UNIT LIMERICK UNIT 1 1
1 DATE NOVEMBER 9, 1993 COMPANY PHILADELPHIA ELECTRIC COMPANY 3
JOHN J.
MCMENAMIN i
REPORTS ENGINEER SITE ENGINEERING LIMERICK GENERATING STATION TELEPHONE (215) 327-1200 EXTENSION 3794 1
MONTH OCTOBER 1993 i
DAY AVERAGE DAILY POWER LEVEL DAY AVERAGE DAILY POWER LEVEL i
( M'n E-N ET )
(MWE-NET) 1 1050 17 1030 1
2 1042 18 1030 3~
1049 19 1037 4
f-4 1043 20 1031 5
1053 21 1031 4
~047 22 1037 1
6 i
7 1043 23 1038 8
1035 24 1041 9
1034 25 1030 i
10 1031 26 1034' y
11 1041 27 1035 28 1038 12 1035' r
13 1031
.29 885 14 1028 30 1181 15
.1033 31 1074 i..
16 1032 T
1-1 i
~
_____..__.__....__._m..m_....u..___.,._..._.._.L.__..
'.~i..J
OPERATING DATA REPORT DOCKET NO. 50 - 352 DATE NOVEMBER 9.
1993 COMPLETED BY PHILADELPHIA ELECTRIC COMPANY JOHN J.
MCMENAMIN REPORTS ENGINEER 4
SITE ENGINEERING LIMERICK GENERATING STAT:ON TELEPHONE (215) 327-1200 EXTENSION 3794 OPERATING STATUS 1.
UNIT NAME: LIMERICK UNIT 1 NOTES: THERE wER NO LOAD DROPS
- 2. REPORTING PERIOD:
OCTOBER, 1993 GREATER THAN 20% THIS MONTH 3.
LICENSED THERMAL POWER (MWT):
3293 t
4.
NAMEPLATE RATING (GROSS MWE):
1138 2
5.
DESIGN ELECTRICAL RATING (NET MwE):
1055 6.
MAXIMUM DEPENDABLE CAPACITY (GROSS MaE): 1092 7 MAXIMUM DEPENDABLE CAPACITY (NET MnE):
1055 8.
IF CHANGES OCCUR IN CAPACITV RATINGS (ITEMS NUMBER 3 THROUGH 7) SINCE LAST REPORT. GIVE REASON 5.
9.
POWER LEVEL TO WHICH RESTRICTED. IF ANY (NET MWE):
4
- 10. REASONS FOR RESTRICTIONS. IF ANY:
i THIS mot 4TH VR-TO-DATE CUMULATIVE t
- 11. HOURS IN REPORTING PERIOD 745 7.296 67.920
- 12. NUMBER OF HOURS REACTOR WAS CR1TICAL 745.0 7.165.9 54.735.1
'13.
REACTOR RESERVE SHUTDO'nN HOUR 5 0.0 0.0 0.0
- 14. HOURS GENERATOR ON-LINE 745.0 7.162.6 53.720.8 i
+
- 15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0.
- 16. GROSS THERMAL ENERGY GENERATED (MwH) 2.439.754 23.425.170 165.158.635 I
- 17. GROSS ELECTRICAL ENERGY GENERATED (MWH) 800.330 7.697.320
$3.673.460 s
i
- 18. NET ELECTRICAL ENERGY CsENERATED (MwH) 772.297 7.427.814 5h4683,31-3 PAGE 1 0F 2 e
i A
i
.m
_ = _ _
m
.m m
m m..
_.m OPERATING DATA REPORT (CONTINUED)
DOCKET NO. 50 - 352 DATE NOVEMBER 9 1993 T
THIS MONTH VR-TO-DATE CUMULATIVE j.
- 19. UNIT SERVICE FACTOR 100.0 98.2 79.1 a
- 20. UNIT AVAILABILITY FACTOR 100.0 98.2 79.1
- 21. UNIT CAPACITY FACTOR (USING MDC NET) 98.3 96.5
-71.8
- 22. UNIT CAPACITY FACTOR (USING DER NET) 98.3 96.5 71.8 23 UNIT FORCED CUTAGE RATE 0.0 1.8 4-8 24 SHUTDOWNS SCHEDULED OVER NEXT G MONTHS (TYPE. DATE. AND DURATION OF EACH):
STH REFUELING OUTAGE: 1/29/94 45 DAYS 1
- 25. IF SHUTDOWN AT END OF REPORT PERIOD. ESTIMATED DATE OF STARTUPt
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
FORECAST ACHIEVED i
INITIAL CRITICALITV 12/19/84 12/22/84 INITIAL ELECTRICITY MIJ APRIL 85 4/13/85-COMMERCIAL OPERATION IST QTR 86 2/01/86 k
I f
- i. -
4 l -
1 PAGE 2 OF 2 i'
t' 4
9 4
+
_______________._____.___m_.__u,,_.___m_
m
.um
..,,,m.#,
h q.-
.m.,,
mew.,,
.2..g.,w-
,,en-%.,w.
u,,,_,.r-r,
,,,_.r
,,,,.,y,._.-,r, y,,3,4sy..,
1 UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50 - 352 UNIT NAME LIMERICK UNIT 1 DATE NOVEMBER 9 1993 REPORT MONTH OCTOBER. 1993 COMPLETED BV PHILADELPHIA ELECTRIC COMPANY r
JOHN J. MCMENAMIN REPORTS ENGINEER SITE ENGINEERING LIMERICK GENERATING STATION TELEPHONE (215) 327-1200 EXTENSION 3794 l METHOD OF LICENSEE SYSTEM COMPONENT CAU$E AND CORRECTIVE l
TYPE DURATION REA50NISHUTTING DOnN EVENT CODE CODE ACTION TO
+
1 NO.
DATE (1)
(HOURS)
(2) l REACTOR (3)
REPORT a (4)
(5)
PREVENT RECURRENCE i
B 4
N/A HA INSTRU REACTOR POWER WAS REDUCED TO 92% FOR 1
25 931010 5
000.0 MAIN TURBINE TESTING.
1 I
I (1)
(2)
(3)
(4)
F - FORCED REASON METHOD EXHIBIT G = INSTRUCTIONS 5-SCHEDULED A - EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA i-B - MAINTENANCE OR TEST 2 - MANUAL SCRAM.
ENTRY SHEETS FOR LICENSEE j
C - REFUELING 3 - AUTOMATIC SCRAM.
EVENT REPORT (LER)
D - REGULATORY RESTRICTION 4 - OTHER (EXPLAIN)
FILE (NUREG-0161)
E - OPERATOR TRAINING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)
G - OPERATIONAL ERROR (EXPLAIN)
H - OTHER(EXPLAIN)
. EXHIBIT I - SAME SOURCE T
l 4
h 4
i e.w.=
--~ue -
.we-c
._-m=.-e,-
--iww-.,-r--er.--.r e w.m
- mrme..-.-e,--=rm,- em.r.-rw w
--*,w.w-+w--
- <-+---w
-~%.-<--=,4w--%.-r--
-.---m.e.i----.--
vi-,,r
i
~
Docket No. 50-353 Attachment to Monthly 1
Operating Report for l
October 1993 Limerick Generating Station Unit 2 October 1 through October 31, 1993 l
I.
Narrative Summary of Operatina Exoeriences Unit 2 began this operating period at 100% of rated thermal power (RTP).
On October 1, 1993 at 1050 hours0.0122 days <br />0.292 hours <br />0.00174 weeks <br />3.99525e-4 months <br /> power was reduced to 90%
RTP for a control rod pattern adjustment and then restored to 100% RTP shortly thereafter.
On October 1, 1993 at 2043 hours0.0236 days <br />0.568 hours <br />0.00338 weeks <br />7.773615e-4 months <br /> power was reduced to 75%
RTP to perform Main Steam Isolation Valve testing and limit switch troubleshooting.
Power was restored to 100% RTP at 2340 hours0.0271 days <br />0.65 hours <br />0.00387 weeks <br />8.9037e-4 months <br />.
On October 10, 1993 at 1216 hours0.0141 days <br />0.338 hours <br />0.00201 weeks <br />4.62688e-4 months <br /> power was reduced to 98.4%
RTP for a control rod exercise test and then restored to l
100% RTP shortly thereafter.
l On October 17, 1993 at 0836 hours0.00968 days <br />0.232 hours <br />0.00138 weeks <br />3.18098e-4 months <br /> power was reduced to 90%
RTP for a control rod pattern adjustment.
Power was restored to 100% RTP at 1112 hours0.0129 days <br />0.309 hours <br />0.00184 weeks <br />4.23116e-4 months <br />.
s Unit 2 ended this operating period at 100% of rated therral power.
II.
Challences to Main Steam Safety Relief Valves There were no challenges to the Main Steam Safety Relief Valves during the month of October.
i l
AVERAGE DAILY UNIT POWER LEVEL S
DOCKET NO. 50 - 353 UNIT LIMERICK UNIT 2 DATE NOVEMBER 9, 1993 COMPANY PHILADELPHIA ELECTRIC COMPANY 1
JOHN J. MCMENAMIN REPORTS ENGINEER SITE ENGINEERING j
i LIMERICK GENERATING STATION
,r TELEPHONE (215) 327-1200 EXTENSION 3794 1
A MONTH OCTOBER 1993' I
DAY AVERAGE DAILV POWER LEVEL DAY AVERAGE DAILY POWER LEVEL (MWE-NET)
(MWE-NET) 1 1040 17 1054 2
1062 18 1061 l
3 1027 19 1070 4
1103 20 1063 5
1074 21
- 1061-6 1067 22 1069 1
7
-1064 23 1070 4
8 1061 24 1068 i
9 1064 25 1066 l
10 1065 26 1065 11 1075 27 1066 i
12 1069 2B 1071 i
i 13' 1071 29 1069 14 1070 ~
30 1071 i
l-15
-1069 31 1115 16 1067 i
e I
4 1
4 eve.<we.- ei T Tger
+ 4,%
3MM'.
,_Tm--4.s..
ye-,-a-
+.em
%s e--
w-T-teh' e-'t e e e w e
-ih++t++w%te w r wi-e, mm.-sengme w +v-w-m+Mm?
et - M
-. me w-9-- eh a 9 v -wlt'PM%N ers b e v mE1 P awm+ere tr 4% +5 W wNe'y w d e e. e M We -T v a
OPERATING DATA REPORT DOCKET NO. 50 - 353 DATE NOVEMBER 9.
1993
---...___..____.___~___---__
COMPLETED BY PHILADELPHIA ELECTRIC COMPANY JOHN J.
MCMENAMIN REPORTS ENGINEER SITE ENGIt4EERING LIMERICK GENERATING STATION TELEPHONE (215) 327-1200 EXTENSION 3794 OPERATING STATUS g,y g g fL NOTES: THERE WA5 ONE LOAD DROP l
LIMERICK e
- g. _.. ---.
1.
UNIT NAME: ____-..__.__-__..._._..f.0 2.
REPORTING PERIOD:
OCTOBER, 1993 GREATER THAN 20% THIS 3.
LICENSED THERMAL POWER (MWT):
3293 MONTH TO PERFORM MAIN 4
NAMEPLATE RATING (GROS 5 M*E):
113S STEAM ISOLATION TESTING 5.
OE51GN ELECTRICAL RATING (NET MnE):
1055 AND LIMIT SWITCH TROUBLE-6.
MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): 1092 SHOOTING.
g 7,
MApIMUM DEPENDABLE CAPACITY (NET MWE):
1055
?
8, IF CHANGES OCCUR IN CAPACITV RATINGS (ITEMS NUMDER 3 THROUGH 7) SINCE LAST REPORT. GIVE REASONS:
9.
PCwER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE):
- 10. REASONS FOR RESTRICTIONS, IF ANV:
THIS MONTH VR-TO-DATE CUMULATIVE
- 11. MOURS IN REPORTING PERIOD 745 7.296 33.432
- 12. NUMBER OF HOUR 5 REACTOR WAS CRITICAL 745.0 5.937.8 29,178.6
- 13. REACTOR RE5ERVE SHUTDOWN HOURS 0.0 0.0 0.0 14 HOURS GENERATOR ON-LINE 745.0 5,826.2 28,482.7
- 15. UNIT RESERVE SHUTDOWN HOURS 0.0 0.0 0.0
- 16. GROS 5 THERMAL ENERGY GENERATED (MAH) 2.446,342 18,532.542 90.498,692
- 17. GROS 5 ELECTRICAL ENERGY GENERATED (MnH) 821.020 6,123,810 29.876,916
- 18. NET ELECTRICAL ENERGY GENERATED (MnH) 794,065 5.903.343 28,766.390 PAGE 1 OF 2-
.m c-u-
- --=
y m
-~
~
OPERATING DATA REPORT (CONTINUED)
DOCKET NO. 50 - 353 5
I i
)'
DATE NOVEMBER 9.
1993 THIS MONTH VR-TO-DATE CUMULATIVE
)
- 19. UNIT SERVICE FACTOR 100.0 79.9 85.2
- 20. UNIT AVAILABILITV FACTOR 100.0 79.9 85.2 t
21 UNIT CADACITV FACTOR (USING MDC NET) 101.0 76.7 81.6
- 22. UNIT CADACITY FACTOR (USING DER NET) 101.0 76.7 81.6 4I3 i
- 23. UNIT FORCED OUTAGE RATE OO 3 0 1
i j
24 SHUTDOWNS SCHEDULED OVER NEAT 6 MONTHS (TVPE DATE. AND DURATION OF EACH)r i
- 25. IF SHUTDOciN AT END OF REPORT PERIOD. ESTIMATED DATE OF STARTUP:
- 26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION):
FORECAST ACHIEVED f
INITIAL CRITICALITY 08/12/89 08/12/89 INITIAL ELECTRICITY 09/Ot/89 09/01/89 i
I COMMERCIAL CPERATION 02/01/90 01/08/90 1
1 s
I 1-4
'I b
i 3
PAGE 2 OF 2 4
a f
5 4
t
.---._.---.--.-.-----_-_.-__-__--____,,.---,,_.,_w-vam,-.e,..+,--w,w-,,e-,--+.-a_,vem,-,,.,-wa,w.n,,,~-m-
,,-wn,
.e
,,..-n, we mr., w, e n n,
-,-,.m.
.nm.,
,-w.~,
UNIT 5HUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50 - 353 UNIT NAME LIMERICK UNI-*-
DATE NOVEMBER 9.
1993 REPORT MONTH OCTOBER. 1993 COMPLETED BY PHILADELPHIA ELECTRIC COMPANY JOHN J.
MCMENAMIN REPORTS ENGINEER SITE ENGINEERING LIMERICK GENERATING STATION TELEPHONE (215) 327-1200 EXTENSION 3794
....__....w.__
I i METHOD OF LICEN$EE SYSTEM COMPONENT CAUSE AND CORRECTIVE l
TVPE DURATION REASONASHUTTING DOWN EVENT CODE CODE ACTION TO NO.i DATE (1)
(HOURS)
(2) l REACTOW (3)
REPORT a (4)
(5)
PREVENT RECURRENCE lCONROD I
l REACTOR POWER WAS REDUCED TO 90% FOR 39 931001 l 5 000.0 B
4 N/A RB CONTROL RCD PATTERN ADJUSTMENTS.
I 40 l 931001 5
000.0 i
B l
4 N/A CD VALVEX REACTOR POWER WAS REDUCED TO 75% FOR l
l l
MAIN STEAM ISOLATION VALVE TESTING l
l l
AND LIMIT SWITCH TROUBLESHOOTING.
I 41 931010 S
000.0 0 l 4
N/A RB CONROD REACTOR POWER WAS REDUCED TO 98.4% FOR CONTROL ROD EXERCISE TESTING.
42 931017 5
000.0 B
.4 N/A RB' CONROD REACTOR POWER WAS REDUCED TO 90% FOR A CONTROL ROD PATTERN ADJUSTMENT.
(1)
(2)
(3)
(4)
F - FORCED REASON METHOD EXHIBIT G - INSTRUCTIONS S-SCHEDULED A - EQUIPMENT FAILURE (EXPLAIN) 1 - MANUAL FOR PREPARATION OF DATA 8 - MAINTENANCE OR TEST 2 - MANUAL SCRAM.
ENTRY SHEETS FOR LICENSEE C --REFUELING 3 - AUTOMATIC SCRAM.
EVENT REPORT (LER) 0 - REGULATORY RESTRICTICN 4 - OTHER (EXPLAIN)
FILE (NUREG-0161)
E - ODERATOR TRAINING + LICENSE EXAMINATION F - ADMINISTRATIVE (5)~
G - OPERATIONAL ERROR (EAPLAIN)
H - OTMER(EXPLAIN)
EXHIBIT I - SAME SOURCE i