Forwards Safety Evaluation Accepting Modified Recirculation Pump Trip (RPT) Logic Design & Alternate Rod Insertion/Rpt Logic Testing Features Based on Review of 900423 Submittal
ML20058P428
Person / Time
Site: FitzPatrick 
Issue date: 08/13/1990
From: Labarge D
Office of Nuclear Reactor Regulation
To: Brons J
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
Shared Package
ML20058P431 List:
References
TAC-59095, NUDOCS 9008170040
Download: ML20058P428 (3)


Text

~

'.. <?

UNITED STATES j-j

[k

- i; NUCLEAR REGULATORY COMMISSION

.' j-

.g W ASHINGTON. D C. 20bb5

,/

August 13, 1990

%q w

...,+

Docket No. 50-333 Hr. John C. Brons Executive Vice President -

Nuclear Generation Power Authority of the State of New York I?3 Main Street Phite Plains, New York 10601

Dear Mr. Brons:

SUBJECT:

ANALOG TRIP UNIT DIVERSITY FOR ANTICIPATED TRANSIENTS WITHOUT SCRAM (A1WS) RULE - JAMES A. FITZPATRICK NUCLEAR POWER PLANT (TAC NO. 59095)

By [[letter::JPN-88-063, Comment on Proposed Rule 10CFR26 Re Fitness for Duty Program.Util Has Constitutional Concerns Re Proposed Random Testing Which Should Be Fully Addressed Prior to Rule Being Promulgated.Endorses NUMARC & EEI Comments|letter dated November 18, 1988]], the staff forwarded the results of our review of your submittals concerning the Alternate Pod Insertion (ARI) and Recirculation Pump Trip (RPT) designs concerning the James A. FitzPatrick Nuclear Power Plant. The letter indicated that the design was not completely acceptable, but that the issues were not of significant safety significance that modifications to address these issues be completed prior to startup from the next (i.e., 1990) refueling outage. Three specific issues were described in the safety evaluation included with the letter, in order to coirply with the ATWS Rule,.it was recuested that you provide an ARI System with instrument components that are civerse from the reactor trip system, modify the RPT initiation logic, and provide logic testing features.

By letter dated April 23, 195 you provided the ATWS implementation status for the FitzPatrick plant whh... described the changes made during the 1990 refueling outage. The letter described changes to the RPT logic, including.

changes to allow logic testing while the reactor is at power. Since you have not provided the diverse Analog Transmitter Trip Units (ATTVs), the diversity 1

issue remains unresolved. However, because this issue is being resolved generically with the BWR Owners Group and will be addressed independently, it remains open but does not affect the at:tus of this evaluation for compliance 1

with the ATWS Rule, j

l i

(

(, qn23

$ib t

e

l O

-2 The staff has evaluated your submittal and determined that the modified design conforms to the requirements of 10 CFR 50.62, and is, therefore, acceptable.

flowever, the staff requests that changes be submitted to Technical Specification Table 3.2-7, " Instrumentation That Initiates Recirculation Pump Trip" to reflect the RPT System logic change and that the Final Safety Analysis Report (FSAR)beupdatedasappropriate. The safety evaluation supporting this conclusion is attached.

This action closes TAC No. 59095.

Sincerely, ORIGNAL $1GNED BYs David E. LaBarge, Project Manager-Project Directorate I-1 Division of Reactor Projects - 1/II Office of Nuclear Reactor Regulation

Enclosure:

As stated cc w/ enclosure:

See next page DISTRIBUTION Decket File ACRS(10)

NRC PDR GPt./PA Local PDR PD Plant File PDI-1 R/F JLinville SVarga RCapra RWessman SNewberry CVogan OGC DLaBarge EJordan PD Plant File t

t FDI-1 PDI-1 PDI-1 M CVogan# '

DlaBarge SN b y

RCapra l

3 'S -9 +

8/r/90

/

O O hW 1

DOCUMENT HAltE: BRONS LETTCP,59095 1

4

}

- Mr. John C, Brons James A. FitzPatrick Nuclear

' Power' Authority of the State of New York Power Plant 1.

CC:

Mr. Gerald C. Goldstein Ms. Donna Ross Assistant General Counsel New York State Energy Office l

Power Authority of the State 2 Empire State Plaza of New York 16th Floor 1633 Broadway Albany, New York 12223 i

New York, New York 10019 Resident Inspector's Office Pegional Administrator, Region I U. S. Nuclear Pegulatory Commission U. S. Nuclear Regulatory Commission Post Office Box 136 a75 Allendale Road Lycoming, New York 13093 King of Prussia, Pennsylvania 19406 Mr. William Fer'wndez Mr. A. Klausman Resident Manager Senior Vice President - Appraisal James A. *itzh' Hd Huclear and Compliance Services Power flant Power Authority of the State l

Post Offi.e Fox 41 of New York Lycoming, New York 13093 1633 Broadway New York, New York 10019 tir. J. A. Gray, Jr.

Mr. George Wilverding, Manager l

Director Nuclear Licensing - BWR Nuclear Safety Evaluation Power Authority of the State Power Authority of the State i

of New York of New York 123 Main Street 123 Main Street White Plains, New York 10601 White Plains, New York 10601 Supervisor Mr. R. E. Beedle Town of Scriba Vice President Nuclear Support R. D. (4 Power Authority of the State Oswego, New York 13126 of New York 123 Main Street Mr. J. P. Bayne, President Power Authority of the State of New York Mr. S. S. Zulla 1633 Broadway Vice President Nuclear Engineering New York, New York 10019 Power Authority of the State of New York 123 Main Street Mr. Richard Patch White Plains, New York 10601 Qualit:t Assurance Superintendent James d. FitzPatrick Nuclear Power Plant Post Office Box 41 Mr. William Josiger, Vice President Lycoming, New York 13093 Operations and Maintenance Power Authority of the State of New York 123 Main Street Charlie Donaldson, Esquire White Plains, New York 10601 Assistant Attorney General New York Department of Law bN w York 10271

.