1~

i,

[,*~'

TABLE 15.4.1-1 (2 of.4)-

l-Channel No. Desc-iption Check Calibrate Test Remarks

- 10. Rod Position Bank Counters S(1)**

N.A.

N.A.

(1) With analog rod position

11. Steam Generator Level S**

R M(1,2)**'

(1) Includes test of logic for l

reactor trip on low-low level and automatic actuation logic for auxiliary feedwater pumps

'Ujj (2) Includes test of logic for-

n o high steam generator level.

i

$$12.SteamGeneratorFlowMisraatch S**

R M**

SS E 13. Charging Flow N.A.

R N.A.

oo

$814. Residual Heat Removal Pump Flow N.A.

R-

-N.A.

15. Boric Acid Tank Level D

R N.A.

O$

16. Refueling Water Storage Tank Level N.A.

R N.A.

17. Volume Control Tank Level N.A.

R N.A.

18. Reactor Containment Pressure S

R M(1)**'

.(1) Isolation valve signal

19. Radiation Monitoring System D

R M

(1) Radioactive Effluent Monitoring Instrumentation Surveillance Require-ments are specified in 15.7.4.

20. Boric Acid Control N.A.

R N.A.

21. Containment Water Level M

R N.A.

22. Turbine Overspeed Trip
  • N.A.

R M(1)**

(1) Block trip

23. Accumulator Level and Pressure S

R N.A.

  • Overspeed Trip Mechanism, and Independent. Turbine Speed Detection and Valve Trip System
    • Not required during periods of refueling shutdown, but must be performed prior to starting up if it has-not been performed during the previous surveillance period.

Unit 1 Amendment No.

Unit 2 Amendment No.