_ _ _. __
\\
GPU Nuclear Corporation i S Nuclear
"::e ; = 388 Forked River, New Jersey 08731-o388 l
609 971-4000 Wnter's Direct Dial Number:
l C321-93-2224 August 18, 1993 U. S. Nuclear Regulatory Commission Attention:
Document Control Desk Washington, D.C.
20555 Gentlemen:
Subject:
Oyster Creek Nuclear Generating Station (0CNGS)
Operating License No. DPR-16 Docket No. 50-219 Generic Letter 89-10, " Motor-0perated Valves" Response to Request for Additional Information GPUN letter to NRC (C321-93-2009), dated June 28, 1993, provided information related to operator actions taken during a postulated LOCA on the Isolation Condenser System.
Based on subsequent discussions with the NRC, the OCNGS licensed operator training program is being updated to identify that the Isolation Condenser System (ICS) condensate return line motor-operated isolation valves are sized to close based on the maximum differential pressure across the valve resulting from upstream reactor coolant system pressure decay over the 35 second isolation signal delay time. This training update will be implemented in November,1993, and provides operator clarification regarding the design basis capability of these valves.
l If any further information is needed please contact us.
Sincerely, s
J. J. Barton Vice President and Director,
- Oyster Creek Nuclear Generating Station JJB/DJD/ame cc: Administrator, Region 1 Oyster Creek NRC Project Manager Senior Resident Inspector 9308250309 930g3g m
PDR ADOCK 0500021? pk Qh 4
GPU Nuclea Corpora.
is a subsidiary of General Public Utilities Corporation