_ _ _ _ _ _ _ _ _ _ _ _ - _ - - - _ - _ _ -
ATTACHMENT II DUKE POWER COMPANY CATAWBA NUCLEAR STATION l
l PROPOSED CHANGES TO TECHNICAL SPECIFICATIONS SUPPLEMENT 2 1
l l
9308190231 930811 9
PDR ADOCK 05000413 1
P PDR 3
~......
RADIDACTIVE EFFLUENTS 3/4.11.1 LIQUID EFFLUENTS LIQUID HOLOUP TANKS LIMITING CONDITION FOR OPERATION 3.11.1.1 The quantity of radioactive material contained in each temporary l
unprotected outdoor tank shall be limited to less than or equal to-10 Curies, excluding tritium and dissolved or entrained noble gases.
APPLICABILITY: At all times.
ACTION:
a.
With the quantity of radioactive material in any of the above tanks exceeding the above limit, immediately suspend all additions of radioactive material to the tank, within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> reduce the tank contents to within the limit, and describe the events leading to this condition in the next M' nnual Radioactive Effluent Release Report, pursuant to Specification 6.9.1.7.
b.
The provisions of Specification 3.0.3 are not applicable.
SURVEILLANCE REQUIREMENTS 4.11.1.1 The quantity of radioactive material contained in each of the above tanks shall be determined to be within the above limit by analyzing a representative sample of the tank's contents at least once per 7 days when-radioactive materials are being added to the tank.
CATAWBA - UNITS 1 & 2 3/4 11-1 Amendment No.hEF (Unit 1) l Amendment No. 4EL (Unit 2)
RADI0' ACTIVE EFFLUENTS GASEOUS EFFLUENTS l
GAS STORAGE TANKS
. LIMITING CONDITION FOR OPERATION 3.11.2.2 The quantity of radioactivity contained in each gas storage tank l
shall be limited to less than or equal to 97,000 Curies of noble gases (con-sidered as Xe-133 equivalent).
APPLICABILITY: At all times.
ACTION:
With the quantity of radioactive material in any gas storage tank a.
exceeding the above limit, immediately suspend all additions of radioactive material to the tank and within 48 hours5.555556e-4 days <br />0.0133 hours <br />7.936508e-5 weeks <br />1.8264e-5 months <br /> reduce the tank l
contents to within the limit and describe the events leading to this condition in the next M' nn,ual Radioactive Effluent Release Report pursuant to Specification 6.9.1.7.
b.
The provisions of Specification 3.0.3 are not applicable.
SURVEILLANCE REQUIREMENTS 4.11.2.2 The quantity of radioactive material contained in each gas storage l
tank shall be determined to be within the above limit at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> when radioactive materials are being added to the tank.
r CATAWBA - UNITS 1 & 2 3/4 11-3 Amendment No. t&&(Unit 1) l Amendment No. "97(Unit 2).
- -. -