,.fe nog)=
UNITED STATES
.g NUCLEAR REGULATORY COMMISSION
- y v.,
5-WASHINGTON, D. C. 20656 k...* #
July 18,1990
- Docket Nos. 50-317' f
and 50-318 l
4 Mr. G. C. Creel
)
Vice President - Nuclear Energy baltimore Gas and Electric Company Calvert Cliffs Nuclear Power Plant MD Rts 2 & 4 P. O. Box 1535 Lusby, Maryland 20657 i
Dear Mr. Creel:
)
SUBJECT:
NRC BULLETIN NO. 88-11. " PRESSURIZER SURGE LINE THERMAL STRATIFICATION" EVALUATION OF COMBUSTION ENGINEERING OWNERS GROUP BOUNDING ANALYSIS RELATING TO CALVERT CLIFFS, UNITS 1 AND 2. TAC 72119 (UNIT 1)
AND72120(UNIT 2)
By letters dated March 3, June 6, and July 31, 1989, Baltimore Gas and Electric Company (BG&E) responded to item 1.b of NRC Bulletin No. 88-11
" Pressurizer Surge Line Thermal Stratification." The letter stated that a t
bounding analysis performed by the Combustion Engineering Owners Group (CE0G) is applicable to Calvert Cliffs, Units 1 and 2.
It further indicated that the integrity of the pressurizer surge line (PSL) satisfies the American Society.
of Mechanical Engineers (ASME)Section III Code criteria for the life of the plant, taking into account the effects of thermal stratification.
The staff has completed its review of the CEOG bounding analysis and finds i
that although sufficient information has been provided to justify continued plant operation until BG&E completes its final report in accordance with the' schedule delineated by the Bulletin' adequate bases have not been provided for the staff to conclude that the PSL meets all.ap)ropriate Code limits for l
40-year plant life. A copy of the evaluation w11ch was sent to the CEOG is enclosed for your information. Also enclosed is the staff's evaluation of CE's l
response to items discussed during a September 1989 audit at CE's office.
l l
Portions of the enclosed evaluation have been deleted. The deletions are due to propriatary information included in the Combustion Engineering Report, CEN 387-P, " Combustion Engineering Own n croup Pressurizer Surge Line Flow Stratification Evaluation."
l BG8E may work collectively through the CEOG effort to address the issues identified in the evaluation, but BG&E is responsible to-ensure that the i
Bulletin requested actions are fully implemented at the Calvert Cliffs i
facility.
i 9007250214 900718 FDR ADOCK 05000317 P
PDC l
bf I[1
i Mr. G. C. Creel
-P-The staff will assess the conformance of the PSL to applicable Codes and regulatory requirements for 40-year plant life when the CEOG report regarding Item 1.d of the Bulletin is submitted.
Sincerely, QltiotNAL SloNro ev Daniel G. Mcdonald, Senior Project Mancger Project Directorate I-1 Division of Reactor Projects - I/II OfficeofNucleprReactorRegulation
Enclosures:
/
As stated cc w/ enclosures:
See next page Distribution:
Docret Fue EJordan NRC/ Local PDRs ACRS(10)
PDI-1 Reading Plant File SVarga JLinville RWessman RACapra CVogan DMcDonald OGC f
PD -1 w PDI sC ga cDonald:rse RACapra 7I 30 7[G[qo 1/181 9 DOCUMENT NAME: LTR TO CREEL 72119/72120 I
l
e Mr. 4. C. Creel Saltimore Gas & Electric Company Calvert Cliffs Nuclear power Diant Cc:
Mr. William T..Dowen. Dreticent Calvert County Board of Mr. Oostoh W. Walter Comissioners Ergineering Division Drince Frederick, Maryland 20678 Dublic Service Cemission of Maryland American 8vilding 231 E. #altimore Street
- 0. A. Brune Esc.
Saltimore, Maryland 21202-3456 General Counsel 8
61timore Gas and Electric Company Ms. Kirsten A. Burger. Esq.
~l D. O. Pox 1475 Baltimore, Maryland 21203 Maryland Deeple's Counsel American Building, 9th Floor Mr. Jay E. Silberg, Esq, 231 E. Baltimore Street Shaw, Pittman, Potts and Trowbridge Baltimore, Maryland 21202 2300 N Street, NW Washington, OC 20037 Ms. Patricia Birnie Co Director Maryland Safe Energy Coalition Ms. G. L. Adams, ticensing P. O. Box 902 Calvert Cliffs Nuclear Power Plo t Columbia, Maryland 21044 MD Rts 2 & 4, p. O. Box 1535 i
1,usby Maryland 20657 Resident inspector
\\
c/o U.$. Nuclear Regulatory Comission D. O, Dox 437 tusby, Maryland 20657 Mr. Richard McLean Administrator - Radioecology Department of Natural Resources 580 Taylor Avenue Tawes state Office Building DPER 83 Annapolis, Maryland 21401 c gional Administrator, Region i e
U.S. Nuclear Regulatory Comission 475 Allendale Road King of Prussia, Pennsylvania 19a06 t
!