Forwards Safety Evaluation & Supporting Lll Technical Rept Re Degraded Grid Protection Class IE Power Sys.Safety Sys Available to Place Plant in Safe Shutdown Status Acceptable.W/O Encl
ML20054M694
Person / Time
Site: Haddam Neck File:Connecticut Yankee Atomic Power Co icon.png
Issue date: 07/09/1982
From: Crutchfield D
Office of Nuclear Reactor Regulation
To: Counsil W
CONNECTICUT YANKEE ATOMIC POWER CO.
References
NUDOCS 8207140235
Download: ML20054M694 (3)


Text

l Q

. July 9, 1982 Disttibution Docket File NRC PDR Local PDR ORB Read &ng Docket No. 50-213 NSIC D. Crutchfield Mr. W. C. Counsil, Vice President H. Smith Nuclear Engineering and Operations C. Tropf Connecticut Yankee Atomic Power Company OELD Post Office Box 270 OI&E Hartford, Connecticut 06101 ACRS (10)

SEPB

Dear Mr. Counsil:

R. Dudley SUBJECrt HADDAM NECK - DECRADED CRID PROTECTION FOR CLASS lE POWER SYSTEMS By letter dated June 3, 1977, you were provided staff positions pertaining to degraded grid voltage protection. You responded with letters dated within the period August 1, 1977 to April 21, 1982.

i The presently installed design incorporates features that require coincident undervoltage and a safety injection signal (LOCA) 13. order to actuate the undervoltage protection circuitry. This is in conformance with the staff's position and is, therefore, acceptable. However, for an undervoltage con-dition without a LOCA, manual operator action wf11 be required to assure that the Class 1E systems are not degraded for this grid transient. This approach deviates from the staff position which requires automatic iso-lation of offsite power for such undervoltage conditions after a time delay.

Acceptability of this alternate approach requires demonstration by you that adequate safety systems will be available to enable safe reactor shutdown under these conditions and that appropriate plant operating procedures are daveloped and made available to the operator for the required manual operator action.

To address these concerns, you have provided a list of safety systems which are not exposed to degraded grid voltage and are, therefore, available to place the plant in a safe shutdown status. We have reviewed this list of systems and concur that this equipment provides the capability for safe plant shutdown under non-accident conditions.

Based upon the fact that protection devices (such as breakers, fuses and relays) are provided to prevent damage to operating equipment that may be exposed to a degraded grid, the low probability of this event occurring (no alarm alerts have occurred since 1976 in the licensee's grid system),

installed alarms that will alert the operator to these abnormal conditions, and the availability of redundant safety systems to permit a dafe plant shutdown under non-accident conditions, we find this alternate approach acceptable.

9 pol OhKOhhohf3 MMM PDR OFFICE )

...........ua aan a a..* *

  • a n a e a n a

a nau.a...

SURNAME) e nun

.a

.*""."*a

....u...

.o onE)

... ~

- ~

NRC FORM 318 (10-80) NRCM 0ao OFFICIAL RECORD COPY us eo ni-ma

I

(.

Mi You should provide appropriate plant operating procedures to cover operator actions during a degraded grid under non-IACA conditions. The procedures will be considered as an unresolved issue in the integrated assessment for IIaddam Neck. This request relates to an issue specific to Haddam Neck and, therefore, does not re.tuire OMB clearance under P.L.96-511.

Enclosed is our related Safety Evaluation Report and the supp,eting Technical Report prepared by our consultant, Lawrence Livermore Laboratory (LLE Report UCID 19139).

Original Signed By Dennis M. Crutchfield, Chief Operating Reactors Branch #5 Division of Licensing

Enclosures:

1.

Safety Evaluation Report 2.

LLL Report - UCID 19139 cc w/ enclosures:

See next page t

1 i

i p..---

L.-

\\

omer >

..B....DL10RM,5.,,p suRN#MEh...C[hp)f.

.kCI D[,121d A

82

,(,...(.f.7..t// ~ 2...././.

6/ 8 ous>

sac rosu ais oo-so/nacu eno OFFICIAL RECORD COPY usom ini-aasm

~,

Mr. W. G. Counsil CC Day, Berry & Howard Counselors at Law One Constitution Plaza Hartford, Connecticut 06103 Superintendent Haddam Neck Plant RFD #1' Post Office Box 127E East Hampton, Connecticut 06424

. Mr. Richard R. Laudenat Manager, Generation Facilities Licensing Northeast Utilities Service Company P. O. Box 270 Hartford, Connecticut 06101 Board of Selectmen Town Hall Haddam, Connecticut 06103 State of Connecticut 0Ffice of Policy and Management ATTN: Under Secretary Energy Division 80 Washington Street Hartford, Connecticut 06115

'U. S. Environmental Protection Agency Region I Office ATTN:

Regional Radiation Representative JFX Federal Building.

Boston, Massachusetts 02203 Resident Inspector Haddam Neck Nuclear Power Station c/o'U. S..NRC 2ast Haddam Post Office East Haddam, Connecticut 06423 Ronald C. Haynes, Regional Administrator Nuclear Regulatory Commission, Region I 631 Park Avenue King of Prussia, Pennsylvania 19406