Informs That Response to TMI Action Item II.K.3.25 Re Integrity of Reactor Coolant Pressure Seals During Loss of Offsite Power Event Is Acceptable
ML20054L378
Person / Time
Site: Beaver Valley
Issue date: 06/24/1982
From: Varga S
Office of Nuclear Reactor Regulation
To: Carey J
DUQUESNE LIGHT CO.
References
TASK-2.K.3.25, TASK-TM TAC-48414, NUDOCS 8207070495
Download: ML20054L378 (2)


Text

DISTRIBUTION Docket Filo

/

(<-

NRC PDR Local PDR ORB #1 Rdg i

@ 2 4 1982 D. Eisenhut C. Parrish P. Tam OELD I

Docket tio. 50-334

,4 C

ACRS (10) ffr. J. J. Carey, Vice President Duquesne Light Company fluclear Division rost Office Box 4 Shippingport, Penna.15077 9

Dear ifr. Carey:

~

SUBJECT:

TMI Action Item II.K.3.25, Integrity of RCP Seals Re:

Letter, J. Carey to S. Varga, December 30, 1981 He have reviewed your response to TMI Action Item II.K.3.25.

This Action Item requires you to demonstrate that the integrity of your reactor coolant pump (RCP) seals is maintained (e.g., adequately cooled) during a loss-of-offsite-power event.

Your response stated that the reactor coolant pump seals are cooled by two independent methods:

(1) The chemical and volume control system, and (2) The component cooling water system. During a loss of offsite power event, the RCP motor is de-energized and both cooling systems to the seals are terminated. However, the diesel generators are automatically initiated and the seal injection flow and the component cooling water to the themal barrier heat exchanger are automatically restored within seconds.

Either of these cooling supplies is adequate to provide seal cooling and prevent seal failure during a loss of offsite power event.

i We find your submittal acceptable to c16secutt Action Plan Item II.K.3.25 i

for Beaver Valley Unit 1.

Sincerely, priginal signed by:

S. A. Varga Steven A. Varga, Chief Operating Reactors Branch #1 Division of Licensing cc:

J. Hegner J. Guttman 8207070495 820624 PDR ADOCK 05000334 P

pnD omcq.Dk.i.0.RB #1 D

B#1 DL: oAA(Z

..u.a.m.f, iT,., S 45.'.hiks.'.W""-

-a

.6..........

.pg.a......

..sm2........

2

-o nac ronu sis om uscu oaa OFFICIAL RECORD COPY usam mi-mm

/

Mr. J. J. Carey Duquesne Light Company cc:

Mr. H. P. Williams Mr. J. D. Sieber, Manager Station Superintendent Nuclear Safety and Licensing Duquesne Light Company Duquesne Light Company Beaver Valley Power Station Nuclear Division Post Office Box 4 Post Office Box 4 Shippingport, Pennsylvania 15077 Shippingport, Pennsylvania 15077 Mr. T. D. Jones, Manaoer Resident Inspector Nuclear Operations U. S. Nuclear Regulatory Commission Post Office Box 298 Duquesne Light Company Post Of fice Box 4 Shippingport, Pennsylvania 15077 Shippingport, Pennsylvania 15077 Ronald C. Haynes B. r. Jones Memorial Library Regional Administrator - Region I U. S. Nuclear Regulatory Commission 663 Franklin Avenue Aliquippa, Pennsylvania 15001 631 Park Avenue King of Prussia, Pennsylvania 19406 Gerald Charnof f, Esauire Jay E. Silbero, Esquire Shaw, Pittman, Potts and Trowbridge 1800 P. Street, N.W.

Washington, D.C.

20036 Karin Carter, Esquire Special Assistant Attorney General Bureau of Administrative Enforcenent 5th Floor, Executive House Harrisburg, Pennsylvania 17120 Marvin Fein Utility Counsel City of Pittsburah 313 City-County Building Pittsburgh, Pennsylvania 15219 Mr. John A. Levin Public Utility Commission P.O. Box 3265 Harrisburg, Pennsylvania 17120 Irwin A. Dopowsky, Esquire Of fice of Consumer Advocate 1425 Strawberry Square Harrisburg, Pennsylvania 17120 Charles A. Thomas, Esquire Thomas and Thomas 212 Locust Street Box 999 Harrisburg, Pennsylvania lN