LIMITING CONDITIONS FOR OPERATION i

3.9 RADIOACTIVE WASTE STORAGE l

FUEL HANDLING BUILDING / AUXILIARY BUILDING AIR CLEANUP SYSTEMS 3.9.12 The Fuel Handling Building and the Auxiliary Building Air Cleanup Exhaust Systems shall be OPERABLE with exhaust ventilation flow through the HEPA filters during system operation. An Air Cleanup Exhaust System is OPERABLE when two of the four system air cleanup exhaust fans are OPERABLE.

APPLICABILITY: At all times.

ACTION:

With the Fuel Handling Building or the Auxiliary Building Air Cleanup a.

Exhaust System inoperable due to flow requirements, return the flow to within acceptable limits within four (4) hours or:

b.

With the Fuel Handling Building or the Auxiliary Building Air Cleanup Exhaust System inoperable (other than as allowed in paragraph 3.9.12.a above), suspend all operations involving movement of liquid and gaseous radioactive wastes in the affected building (other than sampling evolutions required by the Technical Specifications or Recovery Operations Plan) until the inoperable SYSTEM is restored to OPERABLE status.

EPICOR-II PROCESSED WATER 3.9.13 Discharge of water processed by the EPICOR-II system shall be pro-i hibited until approved by the NRC. Water processed by the EPICOR-Il system shall be discharged in accordance with procedures approved pursuant to Specification 6.8.2.

1 APPLICABILITY:

None except as provided in Specification 3.0.3.

REACTOR BUILDING SUMP WATER 3.9.14 Processing and discharge of water in the Reactor Building sump and Reactor Coolant System shall be prohibited until approved by the NRC. Water in the Reactor Building sump and Reactor Coolant System shall be processed and discharged in accordance with procedures approved pursuant to Specification 6.8.2.

APPLICABILITY:

At all times.

ACTION:

None except as provided in Specification 3.0.3.

THREE MILE ISLAND - UNIT 2 3.9-1 82042600 N