.A March 10, 1982 c.

Ca S

REC 2iggD Florida Power Corporation g

ATTN:

Mr. J. A. Hancock y

022 fgg ;

Vice President Nuclear Operations P. O. Box 14042, Mail Stop C-4 g

//

St. Petersburg, FL 33733 4

Gentlemen:

Subject:

Confirmation of Action This letter confirms the telephone conversation of March 5,1982, between you and Mr. R. C. Lewis of my staff regarding fire doors at the Crystal River 3 facility.

This subject was also addressed in NRC Reports 50-302/81-21 and 302/81-25 and your response #3F-0182-22 dated January 25, 1982. With regard to the matters discussed, it is our understanding that you will undertake the following actions:

1.

Verify operability of fire dampers and perform subsequent inspections of safety related dampers and fire doors in accordance with your existing procedures.

2.

If any fire door or damper is found to be inoperable, the following action will be taken:

a.

Establish a continuous fire watch on at least one side of the affected fire door or damper within one hour.

b.

The continuous fire watch is to be maintained until such time that the inoperable fire door or damper is repaired.

3.

Continue the above actions until the amended technical specifications have been approved by NRR.

Changes to the above actions will have prior concurrence by NRC Region II prior to implementation.

Please inform this office immediately, if your understanding is different from that stated above.

Sincerely, Original signed by JP0'Reilly James P. O'Reilly Regional Administrator c-cc:

See Page 2 l

8204s8o m \\~

sN P

-C63 /G'

. =.

..A Florida Power Corporation 2

March 10, 1982 cc:

D. G. Mardis, Acting Manager Nuclear Licensing T. Lutkehaus, Nuclear Plant Manager bec: B. Grimes, DEP J. Sniezek, RRRI 4

H. Thornburg, SRSI RII List C NRC Resident Inspector R. C. Lewis J. A. Olshinski