ML20053B969
| ML20053B969 | |
| Person / Time | |
|---|---|
| Site: | Hope Creek |
| Issue date: | 05/21/1982 |
| From: | Martin T Public Service Enterprise Group |
| To: | Haynes R NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I) |
| References | |
| 10CFR-050.55E, 10CFR-50.55E, NUDOCS 8206010384 | |
| Download: ML20053B969 (1) | |
Text
.
j Thamas J. Martin Public Service Electric and Gas Company 80 Park Plaza Ne.vark, N.J. 07101 201/4304316
%ce Pradet i
Ereneering and Construction May 21, 1982 Tu-5% %
p -l'; 7 Mr.
R. C. Haynes, Administrator U.
S.
Nuclear Regulatory Commission Of fice of Inspection and Enforcement Region 1 631 Park Avenue King of Prussia, Pennsylvania 19406
Dear Mr. Haynes:
SIGNIFICANT CONSTRUCTION DEFICIENCY VARGLASS WIRE TIES HOPE CREEK GENERATING STATION On July 17, 1981, a verbel report was made to Region 1, Office of Inspection and Enforcement representative, Mr.
L.
Briggs, advising of a potential significant construction deficiency.
On August 17, 1981, a written report was sub-mitted to your office.
The following supplemental informa-tion is provided in accordance with the requirements of 10CF R5 0.5 5 ( e ).
t 1.
Bechtel has verified that the use of varglass cable ties is limited to those Motor Control Centers supplied by General Electric's facility in Mebane, North Carolina.
2.
To preclude tie wrap slippage as well as unravelling, we have elected to replace the varglass cable ties rather than add silicon sealer to the existing varglass ties.
Documentation of the results of our actions will be availa-ble on site for review by your inspectors.
Very truly yours, l
CC: Office of Inspection and Enforcement Division of Reactor Construction Inspection Washington, DC NRC Resident Inspector - Hope Creek P.O.
Box 241 Hancocks Bridge, NJ 08038 820 6 010 3sy, o
.