Telecopy of Ro:On 820415,surveillance Test 3PC-R4 Indicated That Pressure Transmitters PT456,PT457 & PT454 Were Out of Spec Nonconservatively.Cause Not Stated
ML20052H180
Person / Time
Site: Indian Point Entergy icon.png
Issue date: 05/12/1982
From: Brons J
POWER AUTHORITY OF THE STATE OF NEW YORK (NEW YORK
To: Haynes R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
NUDOCS 8205200038
Download: ML20052H180 (1)


Text

O]'

pew NEd YORK STATE P0aER AUTH0u1TY R d

O Q

Eck 00X 215 e N E N' -

M. c$ o.,. J m j%M g

, -x, BUCHANAN NY 10511

(

iMM n

e v

4-0430eeS132003 05/12/62 ICS IPPMTZZ CSP PHAb 2 9147Do200 HGM TDHT BUCHANAN NY 05-12 0350P EST O

e NUCLEAR REGULATURY COMMISSION ATTN RONALD C MAYNEb UIRECTOR n

REGION 1 0FFICE OF INSPECIION AND ENFORCEMENT g

631 PARK AVE KING UF PRUSSIA PA 19406 O

e O

e THIS IS A CONFIRMATION COPY CF A TELEGRAH ADDRESSED TO YOU g

(d ON APNIL 15, 1982 aITH THE PLANT IN THE COLD SHUTD0aN CONDITICN FCR THE RtFUELING OUTAGE PERFORMANCE OF SURVEILLANCE TEST 3PC-R4 (PRESSURIZER PRESSURE CALI6 RATION) INDICATED TMAT PRESSURE g

p#

TRANSMITTERS PT456 PT457 AND PT474 aEat OUT OF SPECIFICATION NON-CUNSERVATIVELY AT A TEST PRESSURE 1800 PSIG. SUBSEQUENT q"

ENGINtEHING ANALYSIS COMPLETED ON MAY 12 DETERPINED THAT LNDER TFESE g

CONDITIONS THE L0a PRESSURIZER PRESSURE REACTOR TRIP SIGNAL *CULC OCCUR AT A SYSTEM PRESSURE OF 1797 PSIG WHICH IS BELOW TrE LIPIT OF 1800 PSIG SET bY TECHNICAL SPECIFICATION 2.3.1,8.3 HESIDENT AND RC g

q'-

INSPECTOR T KENNY aAS NOTIFIED AT 1400 MOURS ON MAY 12 1982 THIS TELEGHAM SERVES THE 24 NOUR NCTIFICATION HEGUIRED BY TECHNICAL (a

SPECIFICATION o 9.1,7,6 g

J C 6 HUNS HESIDENT NGR INDIAN POINT 3 NUCLEAR POWER PLANT (80x 215 eUCHANAN NY 10511) dox 215 p'-

g 6UCnANAN NY 10511 0

15:53 EST g