Text
.
APPENDIX A NOTICE OF VIOLATI,0N Carolina Power and Light Company Docket No. 50-261 H. B. Robinson 2-License No. OPR-23 As.a result of the. inspection conducted on February 22-26, 1982, and in accord-ance with the Interim Enforcement Policy, 45 FR 66754 (October 7, 1980), the following violation was identified.
Technical Specification 6.8.1 in concert with ANSI N18.7-1972, paragraph 5.1.7, requires appropriate evaluation of test results.
Contrary to the above, appropriate evaluation of the results of measurement -
of reactor coolant system leakage could not be assured in that in PT-8,
" Reactor Coolant System Leakage Evaluation", the constant used to equate volumetric change with a change in average system temperature was based upon an incorrect system volume.
Further, the constant was not calculated for current operating conditions or sufficiently universal to apply to all modes for which surveillance is required.
This is a Severity Level IV Violation (Supplement I.D.3).
Pursuant to the provisions of 10 CFR 2.201, you are hereby required to submit to this office within thirty days of the date of this Notice, a written statement or explanation in reply, including: (1) admission or denial of the alleged viola-tions;_(2) the reasons for'the violations if admitted; (3) the corrective steps which have been taken and the results. achieved; (4) corrective steps which will be taken to avoid further violations; and (5) the date when full compliance will be achieved. Consideration may be given to extending your response time for good cause shown.
Under the-authority of Section 182 of the Atomic Energy Act of 1954, as amended, this response shall be submitted under oath or affirmation.
Date:
MAR 3 0 1982 I
gDRADocx0500o261 205140458 820430 o