Text
-
00 G-0/ 0 S
/ pa re c,o UNITED STATES 8'*
NUCLEAR REGULATORY COMMISSION a
W ASHING TON, D. C. 20555 p
April 20,1982
[
,$/
n, //
g d#?.~.i.' S>/fAfj7 o
k I
2F; q,
-6
- C g:
- Mr. Steven C. Sholly Technical Research Assistant 4
ev s
Union of Concerned Scientists 1346 Connecticut Avenue, N.W.
D 0
0 Dupont Circle Building, Suite 1101 IN RESPONSE REF Washington, DC 20036 TO F01A-82-179
Dear Mr. Sholly:
This is in further response to your letter dated April 7,1982 in which you requested, pursuant to the Freedom of Information Act,10 categories of records referenced in other documents pertaining to NRR generic safety issues.
The enclosed document is responsive to item 7 of your letter, thus completing our response to all categories of requested information.
This completes NRC action on your request.
Sincerely,
-f
/
< !9 -$ - i.f
[fA M/
h 4 2. Felton, Director j
'l Division of Rules and Records
/
Office of Administration
Enclosure:
As stated d
8205130448 820120 PDR FOIA SHOLLYB2-179 PDR
o.
- ff,g=
- reg %
(
UNITED STATES
,, 3 NUCLEAR REGULATORY COMMISSION o
r E WASHING TON, D. C. 20555 e
%*****/
SEP 3 01980 ANDUM FOR:
Stephen H. Hanauer, Director, Division of Human Factors Safety, NRR FROM:
Frank Schroeder, Acting Director, Division of Safety Technology, NRR
SUBJECT:
SAFETY INJECTION SIGNAL RESET The encle",ed memorandum describes our review of a potential problem at the Point Beach ieactors of negating the automatic initiation of containment spray if the Safety Injection Signal (SIS) is reset.
In other reactor plants there may be other safety functions that could be adversely affected by SIS reset.
We recomend that as part of TMI Action Plan Tasks I.C.8 and I.C.9, plant speci-fic procedures be reviewed with s 3ecific attention to the potential problems of SIS reset.
Caution notes should se added where appropriate, to advise the opera-tors of all the implications of SIS reset on that particular plant.
/-
ra Sc r e r, D g Director Division of Safety Technology Office of Nuclear Reactor Regulation
Enclosure:
Memorandum to Gus C.
Lainas from M. Ernst,
" Containment Spray Pump Logic" ces w/ enclosure:
D. Eisenhut F. Rowsome F. Schroeder R. Baer D. Ross T. Cox R. Vollmer S. Israel A. Thadani J. T. Beard R. Bernero
[
(./ L v
,,