ML20052E941

From kanterella
Jump to navigation Jump to search
Alternate Shutdown Study, Final Rept Apr 1982
ML20052E941
Person / Time
Site: Comanche Peak  
Issue date: 05/07/1982
From:
GIBBS & HILL, INC. (SUBS. OF DRAVO CORP.)
To:
Shared Package
ML20052E936 List:
References
NUDOCS 8205110557
Download: ML20052E941 (115)


Text

.

I I

L COMANCHE PEAK STEAM ELECTRIC STATION UNITS I & II ALTERNATE SHUTDOWN STUDY 8

FINAL REPORT APRIL 1982 l

ll i

I DI lr l4

]

1 1

GIBBS & HILL, INC.

ENGINEERS, DESIGNERS, CONSTRUCTORS NEW YORK, NEW YORK 8205110557 820507 PDR ADOCK 05000445 F

PDR

I CONTENTS SECTION TITLE PAGE i.

1.O INTRODUCTION 2.0 PURPOSE I

3.0 METHODS AND GENERAL ANALYSIS OF STUDY AND FINAL DESIGN 3.1 METHODS OF STUDY 3.2 GENERAL ANALYSIS OF STUDY 3.3 FINAL DESIGN M

TABLE 1A PROCEDhRES TO BE FOLLOWED FOR FIRE IN CSR/CR TABLE IB TRANSFER SWITCHES LOCATED ON STP TABLE IC VALVES REQUIRED FOR SHUTDOWN CSR/CR TABLE 1D INSTRUMENTATION AND CONTROL U

LOCATED ON HSP, TRAIN "A"

& "C" lUS TABLE 1E INSTRUMENTATION AND CONTROL LOCATED ON HSP, TRAIN "B"

& "C" TABLE 2A PROCEDURE TO BE FOLLOWED FOR FIRE AT HSP TABLE 2B VALVES REQUIRED FOR SHUTDOWN l

(HSP FIRE)

I TABLE 3A PROCEDURE TO BE FOLLOWED FOR i

FIRE AT STP Ig TABLE 3B VALVES REQUIRED FOR SHUTDOWN

TABLE 4 HIGH PRESSURE / LOW PRESSURE INTERFACES TABLE 5 ALTERNATE SHUTDOWN ANNUNCIATORS TABLE 6 JUNCTION BOXES AND LOCATIONS I

I

I CONTENTS (Continued)

SECTION TITLE PAGE 4.0 DETAILED ANALYSIS OF SHUTDOWN LOGIC SKETCH XB-2323-1800 1

4.1 HOT STANDBY (HSB) ANALYSIS 4.2 HOT SHUTDOWN (HSD) ANALYSIS 4.3 COLD SHUTDOWN (CSD) ANALYSIS 4.4 COMPONENT COOLING WATER ANALYSIS lI I

4.5 SERVICE WATER SYSTEM ANALYSIS 4.6 CHILLED WATER SYSTEM ANALYSIS 4.7 g

DIESEL GENERATOR & AUXILIARIES ANALYSIS 4.8 AC POWER AVAILABILITY

5.0 CONCLUSION

6.0 LIST OF ABBREVIATIONS 7.0 REFERENCES ATTACHMENTS 1-SHUTDOWN LOGIC (XB-2323-1800)

J 2-FIGURE 1

E 3-FIGuaE 2 lI E 4-FIGURE 3 4

5-FIGURE 3A 6-FIGURE 4 t

l 7-FIGURE 5 8-FIGURE 6 9-P & IDS II I

.I

l:

I

1.0 INTRODUCTION

A catastrophic fire in the CPSES Unit I or II control room (CR),

I cable spreading room (CSR) or at the hot shutdown panel (HSP) was the basis for this study.

The design basis for such a

catastrophic event was the " transient exposure fire" required to I

be postulated by NRC Branch Technical Position (BTP) APCSB 9.5-1.

Of the three locations, either the CR or CSR area fire was the controlling case regarding design changes as compared to the HSP location.

By circuitry changes and equipment rearrangement at the HSP area, the design was changed to ensure complete isolation of the CR and thus enable safe shutdown of the plant from either the CR or the HSP.

5 It should be noted that the original design of the HSP required only the postulated evacuation of the CR for an unspecified non-catastrophic event.

No damage to equipment in the CR or CSR was t

assumed in the analysis of equipment required to meet General Design Criteria 19: to enable reactor shutdown from outside the

}I CR.

Hence, the transient exposure fire represents a fundamental departure from this concept.

l 2.0 PURPOSE The purpose of this study was:

I To analyze the effect on CPSES Unit I or II control system of a.

a major fire in either the CR, the CSR, the HSP or the new Shutdown Transfer Panel (STP).

b.

To suggest a means of achieving hot standby, and subsequent lr cold shutdown, in spite of the postulated destruction by fire.

c.

To revise the existing control systems with the least impact on construction, existing documentation and interfaces with l

instrument or equipment suppliers.

d.

To incorporate in these changes human factors engineering principles in order to make the operators' work station I

(i.e.,

the HSP) simple and effective in aiding them to shut the plant down safely in the event of this postulated destructive fire.

l I I -

I Major assumptions made in addressing alternate shutdown I

capability per the BTP were as follows:

a.

The

unit, while operating at full power, develops a serious fire in one of the areas postulated.
b. The unit is brought to hot standby (reactor and turbine
tripped, systems at no-load pressure and temperature) immediately, and is, subsequently, capable to proceed to cold shutdown within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

Loss of offsite power may occur with the generator trip.

c.

Fa d.

Shutdown will be achieved using one train of shutdown systems, either Train "A" or "B."

e.

No additional single or multiple failures or events are I

considered concomitant with the postulated fire.

Spurious signals emanating from equipment in the fire zone are considered.

m f.

The alternate shutdown system is important to safety, but is not Class 1E.

It is a

combination of Class 1E and non-Class 1E controls and monitors.

Class 1E control l

systems, if
revised, shall have Class 1E components.

5 Alternate shutdown is primarily intended to overcome fire damage unaccompanied by a LOCA or other accidents that render systems incapable of performing their intended functions.

3.0 METHODS AND GENERAL ANALYSIS OF STUDY AND FINAL DESIGN i

l 3.1 METHODS OF STUDY b

In order to examine alternate shutdown capability, a shutdown

!I logic diagram (Sketch XB-2323-1800, Sh. 0-15), Attachment I, was developed to show the existing control schemes for CPSES I or II.

_l It also shows those portions of systems and components, required for

shutdown, that were disabled by the postulated fire.

A I

detailed discussion of shutdown logic sketch XB-2323-1800 is contained in Section 4 of this report.

In

addition, mini-P ids were also developed to portray essential equipment, instrumentation and flow paths in order to facilitate analysis and understanding of the shutdown capability

.I sought.

Instruments and controls indicated in the P&ID are the actual controls located at the front of the panels and doesn't show complete interlocks.

For details refer to individual ICD's.

l The following attachments are tabulated below:

- I

lI l

f List of P&ID's FIRE Dwg. No.

System CR HSP STP 1A SSW System X

1B SSW System X

~

R IC SSW System X

2A CCW System X

I 2B CCW System X

2C CCW System X

3A SG Inventory Control X

a 3B SG Inventory Control X

7 3C SG Inventory Control X

4A SG Pressure Control X

4B SG Pressure Control X

X 5A RCP Seal Integrity, y

Reactivity Control and

)

RCS Inventory Control X

5B RCP Seal Integrity, g

Reactivity Control and

[

RCS Inventory Control X

SC I

RCP Seal Integrity, Reactivity Control and RCS Inventory Control X

6A RCS Pressure Control X

6B RCS Pressure Control X

C RCS Pressure Control X

7A Chilled Water System, Room Ventilation and rg Diesel Generators X

lI.E 7B Chilled water System, Room Ventilation and

  • )

Diesel Generators X

i 7C Chilled Water System, Room Ventilation and W

Diesel Generators X

3.2 GENERAL ANALYSIS OF STUDY 3.2.1 A

major fire in the CR or CSR, just beneath the CR, could disable systems needed for either hot standby or cold shutdown of the plant.

Most of the instrument I

loops are powered from the CR and all interlocking signals for automatic controls, such as safety injection g lI

l:I 4

or blackout, originate in the CR.

A fire at the HSP area could result in the destruction of transfer switches (local / remote),

normally in the remote I

position, of safe shutdown equipment for both Trains "A" and "B."

g l

3.2.2 A majority of the CPSES Unit I and II control systems reviewed are in a " series" configuration as shown in Figure 1,.

In this arrangement, transmitters send analog signals to the CR where they indicated or monitored and retransmitted to the HSP are to perform the same function as in the CR.

Their power

supply, however, is in the CR.

It, therefore, becomes I

evident that if either the CR or CSR is seriously damaged, the HSP is also inoperative.

I 3.2.3 All of the changes required, as a result of the analysis of safe shutdown paths, were reduced to the four general cases described below.

E Case 1.

For simple indicating

loops, another p

transmitter was added alongside the existing transmitter, and terminated at the HSP.

Existing indicators on the

HSP, provided by G&H or W, were used.

In addition, a new power supply was added at the STP (and, thus I

unaffected by the CR fire) and existing wiring between the CR and the HSP was disconnected.

n.

See Figure 2, Attachment 3.

Case 2.

For complex loops with indication and control d

functions, new transmitters were added (alongside existing transmitters) and were l4 terminated at the HSP.

Final control signals emanating from either the CR or the HSP are now routed to the transfer panel and through a iI local / remote selector switch to the final control element.

Existing instrumentation at the HSP, provided by G&H or W, was used as in IE Case 1 above and existing wiring between the

!g CR and the HSP was disconnected.

See Figure 3, Attachment 4.

Case 2A.

The existing transmitter was rerouted to a selector switch added at the STP.

The final j,

element wil be controlled from either the CR or the HSP as selected at the transfer panel.

i See Figure 3A, Attachment 5.

1' l

Case 3.

For train "A" motor operated valves needed for safe shutdown, that are controlled from the l

I

I:

I control

room, wiring was revised so that the final control signal passes through a selector I

switch added to the STP.

A hand switch was added to the

HSP, thus, control of the g ~.

Train "A" valve can be obtained from either the CR or the HSP as selected from the c

transfer panel.

In addition, valve position lights for the Train B valve were added to the HSP.

See Figure 4, Attachment 6.

Case 4.

Train "A" equipment required for safe shutdown already had their selector switches and local control switches located on the HSP.

The l

selector switches were relocated to the STP and control switches remain at the HSP.

In

~

addition,

" equipment running" lights were added to the HSP.

See Figure 5, Attachment 7.

3.2.4 If a

~

CR design basis firs is postulated, offsite power may be lost.

If available, the RC pumps are allowed tc run (forced circulation).

If

lost, cooling without p

forced RC flow (natural circulation cooldown) introduces jg certain simplifications in control system design.

The 3

operator has the option of deciding between forced or N

natural circulation.

In the event of a CR fire, the RCPs can be manually tripped at the switchgear.

To shut down the plant, the Train "A" diesel generator would be manually started along with the component cooling water, service water, and chilled water systems and associated emergency room fan-coolers for this equipment I

(Train "A").

I.}

I Many fluid flow paths, such as component cooling water to and from the reactor containment, consist of either

" parallel" or

" series" valve connections, depending on the design.

Train "A" and Train "B" valves in series

=

are designed to close on a containment isolation signal.

A parallel connection of Train "A" and Train "B" valves is usually designed to open to mitigate the effects of a

.I postulated accident.

In the case of a design basis CR

fire, the objective is to shut down the plant in an orderly manner, assuming only one source of power supply

' [g available.

Reversing the intended function of the valve g

arrangement would now become important.

For

example, flow of component cooling water (CCW) into the reactor p

building for RCP cooling must be maintained even if Train "B" power and control is lost due to the design basis fire causing its Train "B" powered isolation valves to close.

1 I

CCW isolation valves in the fluid flow path are in series, one powered from Train "A" and the other from Train "B."

Although most of these valves are motor-operated and fail "as-is" on loss of

power, the occurrence of a spurious signal from a burning control room must be considered.

To preclude mispositioning of key Train "B" valves, the design changes described below were made.

3.2.5 The problem of transferring control of

circuits, automatically controlled before the postulated fire, to manual control, for all systems involved in this study, has been carefully reviewed.

The bumps associated with transfer are considered of minimal consequence since most of the valves controlled or MOVs, are slow acting.

,3 Bumps associated with pump starts can be mitigated by 5

prescribing procedures to enable regulation of bypass and discharge flow.

3.2.6 Detail analysis of communication

systems, emergency lighting and access are not included in this report.

3.2.7 All high pressure / low pressure interfaces with the RCS have been identified and listed in Table 4.

The design has been modified to ensure that no LOCA would result as a consequence of the postulated catastrophic fires.

3.3 FINAL DESIGN In order to preclude a spurious signal from mispositioning the key Train "A" and "B" valves and to protect n

at least 1

safety

'I train ("A" or "B"), during a CR/CSR or HSP fire the following was accomplished:

1.

Installed a

new Shutdown Transfer Panel (STP) for key train "A",

"C" and associated train "AA" equipment transfer I

switches.

These included

pumps, valves, suitchgears and power supplies for analog instruments.

Control circuits now have 2 sets of readily accessible fuses.

2.

Shutdown control systems of Train "A" were revised to be l

completely independent of the CR.

Essential Train "B" valves

,p in series with vital Train "A" valves now have indicating lights at the HSP.

These lights are independent of A-C power sources (Train "B" or "C" battery) and are not affected by a CR/CSR fire.

3.

Running lights for vital equipment are provided at the HSP.

Process indication, control switches and indicating lights are functionally grouped for ease of operation.

I I

i.

4.

Procedures proposed now incorporate specific actions of the operator in case of a design basis CR, CSR, H3P or STP fire.

Tables 1 through 3 below tabulate procedures to be followed I

for each postulated fire.

The tables provided are for Unit I Instruments and Controls and are typical for Unit II.

Note that procedures proposed are preliminary guides that augment l

this study.

Actual, final detailed procedures will be developed by TUGCo.

I FI I

1 I

,I 1<

l l

l 7

D I

I I

I

I.I TABLE 1A i

PROCEDURE TO BE FOLLOWED FOR FIRE IN CSR/CR (Only Train "A" Equipment Required)

(

OPERATOR'S G

WORK STATION PROCEDURES CR 1.

Prior to evacuating CR, trip the Reactor, Turbine & Generator.

STP 2.

Transfer all Sel-Switches at the STP from " Remote" To " Local." See Table No. 1B and Fig.

6, Attachment No.

8.

3.

Start Essential Equipment D.G. Local A.

Diesel Gen.

"A" and Auxiliaries Control Panel A.1 Emergency start switch for DG "A" 5b (No Tag No.) and HS-3375A F.O.

Transfer Pump HSP A.2 CCW PP No. 1 HS-4518C HSP A.3 SW PP No. 1 HS-4250C

<I lq HSP A.4 Chilled Water Recirculation l

PP No. 6700, HS-6700 FL HSP B.

Charging PP APCH 1/1-APCHIL I1 HSP B.1 Boric Acid Transfer PP l -

No. APBA1 1/1-APBA1L HSP C.

Aux. Feedwater PP No. 1 HS-2450C 1

l Local Panel D.

Emergency Fan Room Coolers (Local Area) such as n

Local Panel D.1 Diesel Generator "A" i

Room Fans HS-5691A3, HS-5691B3 5691C3, 5691D3, and 5691E3 i 1

' I l I

1 i

I l

Table 1A (Continued)

WORK STATION PROCEDURES Local Panel D.2 Electrical Area Train "A" I

Room Coolers El-810'-O" HS-5684B3 (SE-17) HS-5684A3 1

(SE-18)

Local Panel D.3 CCW Pump Room Cooler HS-5800C(SE-07)

Local Panel D.4 Aux. Feedwater PP Room Cooler 1

HS-5676C (SE-07)

_I Local Panel D.5 Charging PP Emergency Fan HS-5802C (SE-03)

I Local Panel D.6 RHR PP 01 Room Cooler (CSD HS-5668 (SE-01)

I HSP E.

RHR PP No. 01 (CSD 1/1-APRHlL) h Local Panel 4.

While the above equipment is being started, other operators at the same time are

.I tripping the Power Circuit Breakers at the MCC of all Train "B" motor operated valves that are in flow line of safe

,3 3

shutdown systems to preclude spurious signals from mispositioning these valves s

HSP 5.

i Verify position of Train "B" valves

~

using monitor light box MLB-63 at the HSP Train "B."

If any of these valves are out of alignment (light on), the l!

operator shall direct other operators to manually operate the misaligned valves.

See Table 1 C.

e l..

1

  • I

llI TABLE IB

{

TRANSFER SWITCHES LOCATED ON STP I

[.

ITEM NO.

TAG NO.

FUNCTION / DESCRIPTION 1.

HS-2450B MOT DRVN AFWP-1 REMOTE LOCAL 2.

HS-2453AF MOT DRVN AFWP-1 TO SG-1 CNTR VLV REMOTE LOCAL 3.

HS-2453BF MOT DRVN AFWP-1 TO SG-2 CNTR VLV REMOTE LOCAL 4.

HS-2456FT MOT DRVN AFWP-1 RECIRC VLV REMOTE LCCAL 0

5.

HS-2452B TURB DRVN AFWP STM SPL*/

HDR #1 VLV REMOTE LOCAL

[

6.

HS-4250B SSW PMP-1 REMOTE LOCAL 7.

HS-4286FT SSW PMP-1 DSCH VLV REMOTE LOCAL 8.

HS-4393FT DSL GEN-A SER WTR CENTR VLV REMOTE LOCAL 9.

HS-4699FT f"

CCW TO RC PMP COOLERS ISO VLV REMOTE LOCAL 10.

HS-4701FT RCP MOT AIR AND LUBE OIL t.,

COOLERS CCW RETURN HDR ISO rl VLV REMOTE LOCAL 11.

HS-4518B CCW PMP-1 REMOTE LOCAL

.. I 12.

HS-4514FT CCW HX TO NON-SAFETY LOOP-1 CNTR VLV REMOTE LOCAL Q

13.

HS-4524FT NON-SAFETY LOOP RET TO CCW HDR "E

ISO VLV REMOTE LOCALt+1 14.

H5-4526FT CCW TO NON-SAFETY LOOP

'I ISO VLV REMOTE LOCAL 15.

SPARE I

I I

I.I TABLE IB (Continued)

ITEM NO.

TAG NO.

FUNCTION / DESCRIPTION 16.

43/1-APCHlL CENT CHRG PUMP-1 REMOTE LOCAL 17.

43/1-APBAlL BORIC ACID TRANS PUMP-I REMOTE LOCAL 18.

43/1-TCV-129 LTDN TO DEMINER OR VOL CNTR TK REMOTE LOCAL u

19.

43/1-8106FT CHRG PMPS TO RCS ISO VLV REMOTE LOCAL 3

20.

43/1-8801AF CHRCr PfAPS TO RC,$ 51$ ~

q ISO VLV REMOTE LOCAL

21. ~

43/1-8149AL CVCS LTDN ORFC ISO VL'V REMOTE LOCAL a

22.

43/1-8149BL CVCS LTDN ORFC ISO VLV REMOTE LOCAL 23.

43/1-8149CL CVCS LTDN ORFC ISO VLV

,I REMOTE LOCAL 24.

43/1-8110FT CHRG PMP MINIFLOW/ ISO VLV

[

REMOTE LOCAL L

25.

43/1-121-FT PRZR LVL CNRL VLV REMOTE LOCAL 26.

43/1-APRH1F RHR PMP-1 REMOTE LOCAL

~

t+1 jg 27.

43/1-8701AF RHR LOOP 1 INLET ISO VLV

'l REMOTE LOCAL 28.

43/1-8701BF RHR LOOP 2 INLET ISO VLV REMOTE LOCAL

.3 29.

SPARE 30.

HS-5405B CONT RECIRC FAN 01 REMOTE LOCAL 31.

HS-2333FT MS LOOP 1 ISO AND BYPASS VLVS T

REMOTE LOCAL

. I

1:

I TABLE 1B (Continued)

ITEM NO.

TAG NO.

FUNCTION / DESCRIPTION k

32.

HS-2334FT MS LOOP 2 IS AND BYPASS VLVS c

REMOTE LOCAL 0

33.

HS-2335FT MS LOOP 3 ISO AND BYPASS VLVS f

REMOTE LOCAL i

34.

HS-2336FT MS LOOP 4 ISO AND BYPASS VLVS REMOTE LOCAL 35.

HS-5413B Col,I RECIRC FAN 03 REMOTE LOCAL 36.

43/1-455 AFT PRZR PWR REIEF VLV REMOTE LOCAL 37.

43/1-PCPRIL PRZR HTR BACKUP GROUP-A

,_a REMOTE LOCAL j

38.

1-HS-XT WTR CHILLER CNTR REMOTE LOCAL 39.

HS-6700FT CH WTR RECIRC PMP-5 REMOTE LOCAL 40.

SPARE 41.

43/1EAl-1 INCOMING BKR 1EAl-1 REMOTE LOCAL 43.

43/1EAl-2 INCOMING BKR 1EAl-2 REMOTE LOCAL 42.

43/1EG1 DIESEL GEN BKR 1EG1 J

REMOTE LOCAL 44.

43/BT-1EA1 TIE BKR BT-1EA1 REMOTE LOCAL 45.

SPARE 46.

43/TIEB1 BUS 1EA1 TRANSFER T1EB1 FEEDER BKR REMOTE LOCAL 47.

43/1EB1-1 INCOMING BKR 1EB1-1 REMOTE LOCAL 48.

43/TIEB3 BUS 1EA1 TRANSFER 1EB3 I

FEEDER BKR REMOTE LOCAL l

l TABLE 1B (Continued)

ITEM NO.

TAG NO.

FUNCTION / DESCRIPTION 49.

43/1EB3-1 INCOMING BKR 1EB3-1 REMOTE LOCAL 50.

43/BT-1EB13 TIE BKR BT-1EB13 REMOTE LOCAL I

1 Fl' s

I m

rl I

i I

- I

l' I.

t TABLE 1C i

VALVES REQUIRED FOR SHUTDOWN (CR FIRE)

REQUIRED HSP INDICATION VALVES TRAIN DESCRIPTION POSITION OR CONTROL 1.

HV-2491B "B"

AFW to STM GEN No. 1 Open WL-2491BF**

2.

HV-2492B "B"

AFW to STM GEN No. 2 Open WL-2492BF**

3.

PV-2453A "A"

Aux. Feedwater Press Control Open FK-2453C p

4.

PV-2453B "A"

Aux. Feedwater Press Control Open FK-2453D p

5.

HV-4393 "A"

SW from Diesel GEN.

"A" Open HS-4393FL 6.

1/1-8351A "B"

Seal Inj. Inlet RCP i

No. 1 Open WL-8351AF**

lI 7.

1/1-8351B "B"

Seal Inj. Inlet RCP No. 2 Open WL-8351BF**

a 8.

1/1-8351C

'B" Seal Inj. Inlet RCP No. 3 Open WL-8351CF**

9.

1/1-8351D "B"

Seal Inj. Inlet RCP No. 4 Open WL-8351DF**

10.

1/1-8110 "A"

Charging PPs Min.

Recir. Valve Open 1/1-8110FL i

11.

1/1-8111 "B"

Charging PPs Min.

Recir. Valve Open WL-8111F**

)

12.

1/1-8801A "A"

Charging PP Disch Isol.

Close 1/1-8801AF Valve 13.

1/1-8801B "B"

Charging PP Disch Isol.

Close WL-8801BF**

7 Valve 14.

1/1-8104 "B"

Charging PPs Inlet I

Control Valve Open WL-8104BF**

i

(,

Local Manipulation of Valve Required

, I

    • Monitor Lights on MLB-63
      • Alternate Power (TR."A") Capability is Being Provided..-

l.

TABLE 1C (Continued) h.I REQUIRED HSP INDICATION VALVES TRAIN DESCRIPTION POSITION OR CONTROL n

8 15.

1/1-8106 "A"

Charging PPs Disch to

[

CVCS Isol. Valve Close 1/1-8106FL 16.

1CS-8444 "B"

Charging PPs Inlet i

Isol, Valve Close None*

17.

FCV-121 "C"

Pressurizer Level Control Open FK-121A 18.

HV-4515 "B"

CCW Train "B" Isol.

Valve Close WL-4515F**

19.

HV-4525 "B"

CCW Flow From Non Safe-Guards Loop Open WL-4525F**

20.

HV-4527 "B"

CCW Flow to Non Safe-Guards Loop Open WL-4527F**

21.

HV-4700 "B"

CCW Flow Inlet Header to RCP Coolers Open WL-4700F**

22.

HV-4708 "B"

CCW Flow Return Header From RCP Open WL-4708F**

23.

HV-4514 "A"

CCW Train "A" Isol.

Valve Open HS-4514FL 24.

HV-4524 "A"

CCW Flow to Non Safe-guard Loop Open HS-4524FL lr 25.

HV-4526 "A"

CCW Flow From Non Safeguard Loop Open HS-4526FL i

26.

HV-4699 "A"

CCW Inlet Flow to RCP Coolers Open HS-4699FL

,e 27.

HV-4701 "A"

CW Return Flow From RCP Coolers Open HS-4701FL 3

28.

HV-4286 "A"

SW Disch. Isol. Valve Open HS-4286FL Local Manipulation of Valve Required

    • Monitor Lights on MLB-63
      • Alternate Power (TR."A") Capability is Being Provided. -

TABLE IC (Continued)

REQUIRED HSP INDICATION j-VALVES TRAIN DESCRIPTION POSITION OR CONTROL 29.

1/1-8702A "B"

RHR Suction Isol. Valve None (HSD, HSB)

Close 1/1-8701A (TR"A" CLOSE)

(CSD)

Open 30.

1/1-8702B "B"

RHR Suction Isol. Valve None (HSD, HSB)

Close 1/1-8701B (TR"A" i

CLOSE)

(CSD)

Close 31.

1/1-8701A "A"

RHR Inlet Isol. Valve

,I (HSD, HSB)

Close 1/1-8701AF (CSD)

Open 1/1-8701AF 3

32.

1/1-8701B "A"

RHR Inlet Isol. Valve 3

(HSD)(HSB)

Close 1/1-8701BF (CSD)

Close 1/1-8701BF 33.

HCV-606 "C"

RHR Disch Control Valve Open HC-606 See Table 6 34.

FCV-618 "C"

RHR Min. Flow Valve Close HC-618

g See Table 6 35.

FCV-610 "A"

RHR Min. Flow Valve Close None*

j 36.

1/1-8809A "A"

RHR Disch Isol. Valve Open None*

37.

1/1-8716A "A"

RHR Cross Connect Close None*

4l;.

Valve I

38.

1/1-8812A "A"

RHR Suction Cross-connect Close None*

1 I

Local Manipulation of Valve Required

    • Monitor Lights on MLB-63 l
      • Alternate Power (TR."A") Capability is Being Provided.

Il I

TABLE 1C (Continued)

REQUIRED HSP INDICATION VALVES TRAIN DESCRIPTION POSITION OR CONTROL 39.

1/1-8808A "A"

S1 Accumulator Tank Isol. Valve (CSD) Close None-Manually By 1

Jumpering @

MCC Indicating Lights 40.

1/1-8808B "B"

S1 Accumulator Tank Isol. Valve (CSD) Close None-Manually By

[.

Jumpering @

1 MCC Indicating Lights Provided @ MC'C 41.

1/1-8808C "A"

S1 Accumulator Tank Isol. Valve (CSD) Close None-Manually By Jumpering @

MCC Indicating Lights p

Provided @ MCC 42.

1/1-8808D "B"

S1 Accumulator Tank Isol. Valve (CSD) Close None-Manually By Jumpering @

MCC Indicating Lights l

Provided @ MCC 43.

PV-2325 "A"

SG No. 1 PORV Close HC-2325 See Table 6 44.

PV-2327 "A"

SG No. 3 PORV Close HC-2327 l

See Table 6 45.

PV-2326 "B"

SG No. 2 PORV Close HC-2326 See Table 6 i

l

-De

-I Local Manipulation of Valve Required

    • Monitor Lights on MLB-63
      • Alternate Power (TR."A") Capability is Being Provided.

I I

TABLE 1C (Continued)

REQUIRED HSP INDICATION

[

VALVES TRAIN DESCRIPTION POSITION OR CONTROL 46.

PV-2328 "B"

SG No. 4 PORV Close HC-2328 See Table 6 PV-5180 "C"

SG Blowdown Drains Close HS-5180F 46.

HV-4395 "A"

3W to Aux Feedwater PP Close None*

49.

1/1-8149A "A"

Letdown Isol. Valve Close 1/1-8149AL 50.

1/1-8149B "A"

Letdown Isol. Valve Close 1/1-8149BL 51.

1/1-8149C "A"

Letdown Isol. Valve Close 1/1-8149CL 52.

PCV-455A "A"

Pressurizer PORV Close 1/1-455AFL 53.

PCV-456 "B"

Pressurizer PORV Close 1/1-456FL 54.

1/1-8153 "B"

RCS Excess Letdown Isol.

Valve Close 1/1-8153 FL 55.

HV-2333A&B "A"

Main Steam Isol. & By-Pass Valve Close HS-2333FL I

56.

HV-2334A&B "A"

Main Steam Isol. & By-L Pass Valve Close HS-2334FL 1

'nI 57.

HV-2335A&B "A"

Main Steam Isol. & By-Pass Valve Close HS-2335FL

,t 58.

HV-2336A&B "A"

Main Steam Isol. & By-Pass Valve Close HS-2336FL 59.

HV-4512 "A"

CCW Isol. Valve Open None

  • 60.

HV-4513 "B"

CCW Isol. Valve Close None *

[i f

j Local Manipulation of Valve Required

,E

    • Monitor Lights on MLB-63 l
      • Alternate Power (TR."A") Capability is Being Provided. lI

.~

l TABLE 1D INSTRUMENTATION AND CONTROL LOCATED ON HSP TRAIN "A"

& "C" I

ITEM NO. TAG NO.

TRAIN FUNCTION / DESCRIPTION 1

HS-4250C "A"

SSW Pump 01 - Local Control

]

2 HS-4518C "A"

CCW Pump 01 - Local Control 3

HS-4286FL "A"

SSW PMP 01 Disch. to Strainer Isol VLV 4

HS-4514FL "A"

CCW HX to Non-Safety Loop 01 Control VLV 5

HS-4526FL "A"

CCW HX Non-Safety Loop Isol. VLV 3

6 HS-4699FL "A"

CCW to RC PPs Coolers Motor Operated Isolation VLV 1

)'

7 HS-4524FL "A"

Non-Safety Loop Return to CCW HER Isol. VLV i

8 HS-4701FL "A"

CCW from RCP Motor Air & Lube Oil Coolers Motor Operated Isol. VLV 9

HS-4393FL "A"

Diesel Gen A Service WTR Isolation VLV 10 FK-121A "C"

Pressurizer Level Control Valve (Charging Flow Control) 11 1/1-8149AL "A"

Letdown Valve 8149A - Control 12 1/1-8149BL "A"

Letdown Valve 8149B - Control h

13 1/1-8149CL "A"

Letdown Valve 8149C - Control I

$y 14 SK-2452B "AA" Turbine-Driven AFW Pump - Speed Control I

15 SI-2452B "AA" Turbine-Driven AFW Pump - Speed Indication I

I I

l' TABLE ID (Continued)

ITEM NO. TAG NO.

TRAIN FUNCTION / DESCRIPTION

(;

16 HS-2452C "A"

Turbine-Driven AFW Pump - Local Control U

17 FK-2453C "A"

Motor-Driven AFW Pump 01 to SG No. 1 Valve Control 18 FK-2453D "A"

Motor-Driven AFW Pump 01 to SG No. 2 Valve Control 19 FK-2461B "A"

Turbine-Driven AFW Pump to SG No. 3 Valve Control 20 HS-2333-FL "A"

Main STM Loop 1 Isolation & Bypass VLV P

21 HS-2334-FL "A"

Main STM Loop 2 Isolation & Bypass VLV 22 HS-2335-FL "A"

Main STM Loop 3 Isolation & Bypass VLV

,n 23 HS-2336-FL "A"

Main STM Loop 4 Isolation & Bypass VLV

~

24 FK-2462B "A"

Turbine-Driven AFW Pump to Steam Generator 4 Valve Control 2

25 1/1-PCPRIL "AA" Pressurizer Heater Backup - Group A Control J

26 FI-121B "C"

Charging Pump to CVCS Charging and l

RCP Seals - Flow f

l, 27 FI-132B "C"

Letdown - Flow 28 1/1-TCV-129L "A"

Letdown Divert Valve TCV-129 -

Control 29 HS-5405C "AA" Containment Recirculation Fan 01 Control Switch l0 30 TR-413F/423F "C"

(2 Pen Recorder) Wide Range Reactor Coolant Temp. Hot Leg Loop 1 &

Loop 2 I

. I

I-I TABLE 1D (Continued)

ITEM NO. TAG NO.

TRAIN FUNCTION / DESCRIPTION 31 1/1-8701AF "A"

RCS Hot Leg Loop 1 to RHR Pump 01 Inlet Isol. VLV Control Switch 32 1/1-8701BF "A"

RCS Hot Leg Loop 4 to RHR Pump 02 Inlet Isol. VLV Control Switch 33 1/1-8801AF "A"

ChRG PMP5 TO RCS S15' Isol.

VLV Control Switch 34 1/1-APRH1F "A"

RHR Pump 01 Control Switch 35 HS-5413C "AA" Containment Recirculation Fan 03

- Control 36 FI-2463B "C"

AFW to Steam Generator 1 - Flow 37 FI-2464B "C"

AFW to Steam Generator 2 - Flow 38 FI-2465D "C"

li AFW to Steam Generator 3 - Flow 39 FI-2466D "C"

AFW to Steam Generator 4 - Flow J

40 PI-2477B "C"

Turbine-Driven AFW Pump - Suction Pressure 41 PI-2455B "C"

Turbine-Driven AFW Pump - Discharge (U

Pressure 42 PI-2475B "C"

Motor-Driven AFW Pump 01 - Suction L

Pressure I

43 PI-2453B "C"

Motor-Driven AFW Pump 01 - Discharge Pressure 44 FI-4258B "C"

SSW Pump 01 - Flow 45 HS-6700FL "A"

Chilled Water Recire. PP 05 46 PI-4252B "C"

SSW Pump 01 - Discharge Pressure i

47 V-1EAl-L "A"

6.9 kV Bus 1EA1 - Voltage 48 F-1EAl-L "C"

6.9 kV Bus 1EA1 - Frequency 1 <

I

' I

i.

l TABLE 1D (Continued)

ITEM NO. TAG NO.

TRAIN FUNCTION / DESCRIPTION I

49 A-1EAl-1L "A"

6.9KV Bus 1EA1 - Preferred Offsite Source - Amperes 50 A-1EG1-L "A"

6.9KV Bus 1EA1 - Onsite Source - Amperes 51 A-1EAl-2L "A"

6.9KV Bus 1EA1, Alternate 7

Offsite Source - Amperes 52 CS-1Eni-1L "A"

6.9KV Bus 1EA1, Preferred Offsite

[1 Source Breaker-Control Switch 53 CS-1Eul-L "A"

6.9KV Bus 1EA1, Onsite Source Breaker - Control Switch 1

54 -

CS-1EAl-2L "A"

6.9KV Bus 1EA1, Alternate Offsite Source Breaker-Control Switch 55 CS/BT1EB13L "A"

480 V Switchgear Bus 1EB1 & IEB3 Bus Tie BKR No. BT-1EB13 Control Switch I

56 CS/1EB1-1L "A"

480 V Switchgear Bus 1EB1 Supply BKR No. 1EB1-1 Control Switch 57 CS/1EB3-1L "A"

480 V Switchgear Bus 1EB3 Supply iI BKR No. 1EB3-1 Control Switch w

58 CS/BTIEA1L "A"

6.9 kV Switchgear Bus 1EA1 Bus Tie BKR No. BT-1EA1 Control Switch 59 CS/TIEB1L "A"

(

6.9 kV Switchgear Bus 1EA1 Transfer TIEB1 Feeder BKR Control Switch 60 CS/TIEB3L "A"

6.9 kV Switchgear Bus 1EA1 Transfer I

TIEB3 Feeder BKR Control Switch 61 LI-501A "C"

Steam Generator 1 - Level 62 LI-502A "C"

Steam Generator 2 - Level 63 PI-514B "C"

Steam Generator 1 - Pressure 64 PI-524B "C"

Steam Generator 2 - Pressure 65 LI-459B "C"

Pressurizer - Level I

I

l-TABLE ID (Continued)

ITEM NO. TAG NO.

TRAIN FUNCTION / DESCRIPTION 66 PI-455B "C"

Pressurizer - Pressure 67 LI-2478B "C"

Condensate Storage Tank - Level I

68 HS-2450C "A"

Motor-Driven AFW Pump 01 - Local Control 69 1/1-APCHlL "A"

Charging Pump 1 - Control 70 1/1-APBAIL "A"

Il Boric Acid Transfer Pump 1 -

Control m.

71 1/1-8106FL "A"

Charging Pump to RCS Isol. VLV

~l Control Switch 72 HS-2456FL "A"

Motor Driven Aux FW PP 01 Recire.

73 1/1-455AFL "A"

I Pressurizer PORV Control Switch 74 ZL-2475B "A"

Aux FW PMP Suction h

75 ZL-2453C "A"

Mot Drvn AFW PMP 01 Disch to SG 1 m

Control VLV I

76 ZL-2461B "A"

Turb Dr AFW PMP Disch to SG 3

)

Control VLV Q

77 ZL-2453D "A"

Mot Drvu AFW PMP 01 Disch to SG 2 Control VLV 78 ZL-2462B "A"

Turb Dr AFW PMP Disch to SG 4 Control VLV l

79 TI-443 "C"

W-RNG RCS Temp.

80 NI-31F "C"

Source Range - Neutron PWR

!'I 81 1/1-8110FL "A"

Charging PMPS Bypass VLV l

I e I

}.

I TABLE 1E INSTRUMENTATION AND CONTROL LOCATED ON 3SP TRAIN "B"

& "C" ITEM NO TAG NO.

TRAIN FUNCTION /LZSCRIPTION 1

1/1-APBA2L "B"

Boric Acid Transfer Pump 2 Control 2

43/1-APBA2L "B"

Boric Acid Transfer Pump 2 Local / Remote 3

HS-4251C "B"

SSW Pump 2 - Local Control 4

HS-4519C "B"

CCW Pump 2 - Local Control 5

HS-4519B "B"

CCW Pump 2 - Local / Remote 6

HS-2452E "B"

Turbine-Driven AFW Pump - Local Control 7

HS-2452D "B"

Turbine-Driven AFW Pump - Local /

Remote 8

FK-2459B "B"

Turbine-Driven AFW Pump To Steam Generator 1 - Valve Control 9

FK-2460B "B"

Turbine-Driven AFW Pump To Steam I

Generator 2 - Valve Control 10 FK-2454C "B"

Motor-Driven AFW Pump 02 to Steam Generator 3-Valve Control 11 FK-2454D "B"

Motor-Driven AFW Pump 02 to Steam Generator 4-Valve Control l1 12 1/1-PCPR2L "BB" Pressurizer Heater Backup -

Group B Control 13 43/1-PCPR2L "BB" Pressurizer Heater Backup -

Group B Local / Remote 14 FI-183B "C"

Boric Acid Filter Recovery Line

- Flow 15 1/1-8104L "B"

Emergency Boration Valve - Control I

e ?

=.g

iI TABLE 1E (Continued)

ITEM NO TAG NO.

TRAIN FUNCTION / DESCRIPTION I

16 43/1-8104L "B"

Emergency Boration Valve Transfer -

Local / Remote c

17 TR-433F/443F "C"

(2 Pen Recorder) Wide Range Reactor Coolant Temp. Hot Leg. Loop 3 &

Loop 4 18 HS-5409B "BB" Containment Recirculation Fan 02 -

Control 19 HS-5409C "BB" Containment Recirculation Fan 02 -

Local / Remote 20 HS-5417C "BB" Containment Recirculation Fan 04 -

Control 3

21 HS-5417B "BB" Containment Recirculation Fan 04 -

Local / Remote 22 FI-2463D "C"

AFW to Steam Generator 1 - Flow 23 FI-2464D "C"

AFW to Steam Generator 2 - Flow 24 FI-2465B "C"

AFW to Steam Generator 3 - Flow 25 FI-2466B "C"

AFW to Steam Generator 4 - Flow

('

26 PI-2476B "C"

Motor-Driven AFW Pump 02 - Suction Pressure 27 PI-2454B "C"

Motor-Driven AFW Pump 02 - Discharg Pressure

' @u

8 2L-455CF "C"

PRZR Spray VLV Position Indicator 29 ZL-455BF "C"

PRZR Spray VLV Position Indicator 30 HS-5180F "C"

STM Generator Blow Down Drains 31 43/1-456FT "B"

Pressurizer PORV Trans Sw p

32 1/1-456FL "B"

Pressurizer PORV Control Sw 33 ZL-PCPX1F "C"

RCP No. 1 Running Light 34 ZL-PCPX2F "C"

RCP No. 2 Running Light I

i i

TABLE 1E (Continued)

ITEM NO TAG NO.

TRAIN FUNCTION / DESCRIPTION 35 ZL-PCPX3F "C"

RCP No. 3 Running Light 36 ZL-PCPX4F "C"

RCP No. 4 Running Light 37 MLB-63 "C"

(Monitor Light Box) 38 FI-4259B "C"

SSW Pump 2 -

Flow 39 PI-4253B "C"

SSW Pump 2 - Discharge Pressure 1

40 V-1EA2-L "B"

6.9 kV Bus 1EA2, Voltage 41 F-1EA2-L "B"

6.9KV Bus 1EA2, Frequency 42 A-1EA2-2L "B"

E 6.9KV Bus 1EA2, Alternate Offsite Source - Amperes 43 A-1EG2-L "B"

6.9KV Bus 1EA2, Onsite Source-Amperes J

44 A-1EA2-1L "B"

6.9KV Bus 1EA2, Preferred Offsite Source-Amperes 45 CS-1EA2-2L "B"

6.9KV Bus 1EA2, Alternate

~-

>I Offsite Source Breaker-C Control Switch E

46 CS-1EG2-L "B"

6.9KV Bus 1EA2 Onsite Source

'g Breaker-Control Switch i

47 CS-1EA2-1L "B"

6.9KV Bus 1EA2, Preferred Offsite Source Breaker-Control Switch I

48 43-1EA2-2 "B"

6.9KV Bus 1EA2, Alternate Offsite Source Breaker-Selector Switch 49 43-1EG2 "B"

6.9KV Bus 1EA2, Onsite Source Breaker - Selector Switch 50 43-1EA2-1 "B"

6.9KV Bus 1EA2, Preferred Offsite Source Breaker -

Selector Switch I.

TABLE 1E (Continued)

ITEM NO TAG NO.

TRAIN FUNCTION / DESCRIPTION

.I-51 LI-503A "C"

Steam Generator 3 - Level 52 LI-504A "C"

Steam Generator 4 - Level 53 PI-534B "C"

Steam Generator 3 - Pressure u

54 PI-544B "C"

Steam Generator 4 - Pressure 55 LI-460B "C"

Pressurizer - Level 56 LI-2479B "C"

Condensate Storage Tank - Level I

57 HS-2451C "B"

Motor-Driven AFW Pump 02 -

Control Switch 58 HS-2451B "B"

Motor-Driven AFW Pump 02 - Local /

Remote 59 1/1-APCH2L "B"

Charging Pump 2 - Control

.s 60 43/1-APCH2L "B"

Charging Pump 2 - Local / Remote

=

61 NI-32F "C"

Source Range - Neutron Pwr I

62 HS-4251B "B"

SSW Pump 2 - Local / Remote I!

63 ZL-2476B "B"

Aux FW PMP Suction Pressure L

64 ZL-2454C "B"

Mot Drvn AFW PMP O2 Disch to r

SG 3 Contr VLV J

65 ZL-2454D "B"

Mot Drvn AFW PMP 02 Disch to i

SG 4 Contr VLV I

66 ZL-2459B "B"

Turb Dr AFW PMP Disch to SG 1 Contr VLV a

67 ZL-2460B "B"

Turb Dr AFW PMP Disch to SG 2 i

Contr VLV l3 I

~ l

i:

I TABLE 1E (Continued)

ITEM NO TAG NO..

TRAIN FUNCTION / DESCRIPTION 68 43/1-8153FT "B"

RCS Excess Letdn. Trans Switch 69 1/1-8153FL "B"

RCS Excess Letdn. Control Switch 70 HC-2325 "C"

Steam Generator 1-Porv L

71 HC-2326 "C"

Steam Generator 2-Porv 72 HC-2327 "C"

Steam Generator 3-Porv 73 HC-2328 "C"

Steam Generator 4-Porv 74 HC-606 "C"

RHR Disch. Control Valve g

75.

HC-618 "C"

RHR Min. Flow valve 76 HC-455C "C"

PRZR Spray Valve

-)

I o.-

+

h 1

I 1

i

. \\

t I

TABLE 2A PROCEDURE TO BE FOLLOWED FOR FIRE AT HSP

.(Only Train "A" Equipment Required)

OPERATOR'S WORK STATION PROCEDURES CR 1.

Trip the Reactor & Turbine / Generator CR 2.

Start CR A.

Diesel Gen.

"A" & Auxiliaries p

A.1 CS/IDG 1E, CS/IDG IN, HS-3375A(F.0)

Transfer Pump No. 1

}

CR A.2 CCW PP No. 01 HS-4518A CR A.3 SW PP No. 01 HS-4250A CR A.4 Chilled Water Recirculation PP No. 01 HS-6700 CR B.

Charging PP No. APCH1 1/1-APCH1 CR B.1 Boric Acid Transfer PP

.I No. APBAl 1/1-APBAl CR C.

Aux. Feedwater PP #01 HS-2450A

~

CR D.

Emergency Fan Room Coolers such as CR D.1 Diesel Generator "A" Room Fans HS-5691 A, B,

C, D,

&E CR D.2 Electrical Area Train "A" t n Emergency Fans El-810'-O" l

HS-5684B (SE-17) HS-5684A (SE-18)

!gE CR D.3 CCW Pump Emergency Fan j

HS-5800 (SE-09)

CR D.4 Aux. Feedwater PP Emergency Fan HS-5676A (SE-07)

I.

c I

I TABLE 2A (Continued)

WORK STATION PROCEDURES CR D.5 Charging PP Emergency Fan HS-5802 (SE-03)

If CR D.6 RHR PP Emergency Fan (CSD)

HS-5668A (SE-01)

CR E.

RHR PP #01 (Cold Shutdown) 1/1APRH1

's Stop During HSB & HSD)

CR A fire at the HSP will not spuriously mispo-tion Train "B" valves.

Motor Operated Valves will fail "as is" and position indication will be lost since power supply is presumed not available.

Process indication correspond-ing to valve "open" or "close" is shown on t

Table 2B.

1

-l g

LI 1

.-I 4-I h

4 I I

I i I

TABLE 2B VALVES REQUIRED FOR SHUTDOWN (HSP FIRE)

I REQUIRED CR INDICATION VALVES TRAIN DESCRIPTION POSITION O_R CONTROL 1.

HV-2491B "B"

AFW to STM GEN No. 1 Open HS-2491 2.

HV-2492B "B"

AFW to STM GEN No. 2 Open HS-2492 3

3.

PV-2453A "A"

Aux. Feedwater Press Control Open FK-2453A 4.

PV-2453B "A"

Aux. Feedwater Press Control Open FK-2453B 5.

HV-4393 "A"

SW to Diesel GEN. "A" Open HS-4393 6.

1/1-8351A "B"

Seal Inj. Inlet RCP No. 1 Open FI-145*

7.

1/1-8351B "B"

Seal Inj. Inlet RCP No. 2 Open FI-144*

8.

1/1-8351C "B"

Seal Inj. Inlet RCP No. 3 open FI-143 9.

1/1-8351D "B"

Seal Inj. Inlet RCP No. 4 Open FI-142

(,'

10.

1/1-8110 "A"

Chhrging PPS Min.

Recir. Valve Open 1/1-8110 f~

11.

1/1-8111 "B"

Charging PPS Min REC RC.

Valve Open None*

l 12.

1/1-8801A "A"

Boron Inj. Isol. Valve Close 1/1-8801A 13.

1/1-8801B "B"

Boron Inj. Isol. Valve Close None*

ie 14.

1/1-8104 B"

Charging PPS Inlet Control Valve Open FI-183*

r 15.

1/1-8106 "A"

Charg PPS Disch to

.I '

CVCS Isol. Valve Close 1/1-8106 16.

FCV-110A "C"

Charging PPS Inlet Valve Close 1/1-FCV-110A

  • Local Manipulation of Valve Required.

( -.s ga*-q w e y,we - gw - g

<=v

,Fe

=

w+v-t e-

--Pr*

i~

6 TABLE 2B (Continued)

,I REQUIRED CR INDIC,ATION VALVES TRAIN DESCRIPTION POSITION

.O._R_CONTROL I

17.

FCV-121 "C"

Pressurizer Level 4

Control Open FK-121 18.

HV-4515 "B"

CCW Train "B" Isol.

I Valve Close None 19.

HV-4525 "B"

CCW Flow From Non Safe-Guards Loop Open FI-4536A, i

4675-4677, 468 p

4689, 4683-i 4685,4679-4681 20.

HV-4527 "B"

CCW Flow to Non Safe-Guards Loop Open FI-4536A, 4675-4677, 468 4689, 4683-t 4685,4679-4681 21.

HV-4700 "B"

CCW Flow Inlet Header to RCP Open FI-4536A, E

4675-4677, 468 3

4689, 4683-4685,4679-4681 22.

HV-4708 "B"

CCW Flow Return Header lb from RCP Coolers Open FI-4536A, 4675-4677, 468 4689, 4683-4685,4679-4681

[

23.

HV-4514 "A"

CCW Train "A" Isol.

Valve Open HS-4514 l

24.

HV-4524 "A"

CCW Flow to Non Safeguard Loop Open HS-4524 25.

HV-4526 "A"

CCW Flow to Non Safeguard Loop Open HS-4526 26.

HV-4699 "A"

CCW Inlet Flow tc RCP e

Coolers Open HS-4699 1

1,.

  • Local Manipulation of Valve Required

' :i

}f I

TABLE 2B (Continued)

REQUIRED CR INDICATION VALVES TRAIN DESCRIPTION POSITION O_R CONTROL I

27.

HV-4701 "A"

CCW Return Flow From RCP Coolers Open HS-4701 28.

HV-4286 "A"

SW Disch. Isol. Valve Open HS-4286 29.

1/1-8702A "B"

RHR Suction Isol. Valve None (HSD, HSB) Close 1/1-8701A (TR"A" Close)

(CSD) Open None p

1/1-8701A (TR"A" Open) or FI-618 30.

1/1-8702B "B"

RHR Suction Isol. Valve None (HSD, HSB) Close 1/1-8701B (TR"A")

(CSD) Close None 1/1-8701B (TR"A" Close J.

or FI-619) 31.

1/1-8701A "A"

RHR Inlet Isol. Valve (HSD) Close 1/1-8701A (CSD) Open 32.

1/1-8701B "A"

RHR Inlet Isol. Valve (HSD) Close 1/1-8701B (CSD) Close 1/1-8701B l'

33.

HCV-?O6 "C"

RHR Disch Control Valve Open HC-606 34.

FCV-618 "C"

RHR HX Bypass Flow Close FK-618 35.

FCV-610 "A"

RHR Min. Flow Valve Close 1/1-FCV-610 36.

1/1-8809A "A"

RHR Disch Isol. Valve (CSD) Open 1/1-8809A

'E 37.

1/1-8716A "A"

RHR Cross Connect Close 1/1-8716A q

) Jg 38.

1/1-8812A "A"

RHR Suction Cross l

Connect Valve Close 1/1-8812A

  • Local Manipulation of Valve Required I

I' TABLE 2B (Continued) i l

REQUIRED CR INDICATION 3

VALVES TRAIN DESCRIPTION POSITION OR CONTROL 1.

E 39.

1/1-8808A "A"

SI Accumulator Tank Isolation Valve (CSD) Close 1/1-8808A 40.

1/1-8808B "B"

SI Accumulator Tank None-Manual I

Isolation Valve (CSD) Close By Jumpering

@ MCC I

41.

1/1-8808C "A"

SI Accumulator Tank 1/1-8808C Isolation Valve (CSD) Close 42.

1/1-8808D "B"

SI Accumulator Tank None-Manual Isolation Valve (CSD) Close By Jumpering

@ MCC 43.

PV-2325 "A"

SG No. 1 PORV Close PK-2325 44.

PV-2327 "A"

SG No. 3 PORV Close PK-2327 45.

PV-2326 "B"

SG No. 2 PORV Close PK-2326 bJ 46.

PV-2328 "B"

SG No. 4 PORV Close PK-2328 47.

PV-5180 "C"

SG Blowdown Drains Close PK-5180 48.

HV-4395 "A"

SW to Aux Feedwater PP Close HS-4395 i

49.

1/1-8149A "A"

Letdown Isol. Valve Close 1/1-8149A 50.

1/1-8149B "A"

Letdown Isol. Valve Close 1/1-8149B 51.

1/1-8149C "A"

Letdown Isol. Valve Close 1/1-8149C 52.

PCV-455A "A"

Pressurizer PORV Close 1/1-455A 53.

PCV-456 "B"

Pressurizer PORV Close 1/1-456 54.

HV-2333A&B "A"

Main Steam Isol. &

Bypass Valve Close HS-2333A 55.

HV-2334A&B "A"

Main Steam Isol. &

' l Bypass Valve Close HS-2334A l

  • Local Manipulation of valve Required

.l TABLE 2B (Continued)

REQUIRED CR INDICATION VALVES TRAIN DESCRIPTION POSITION OR CONTROL 56.

HV-2335A&B "A"

Main Steam Isol. &

Bypass Valve Close HS-2335A 57.

HV-2336A&B "A"

Main Steam Isol. &

Bypass Valve Close HS-2336A 58.

HV-4512 "A"

CCW Isol. Valve Open HS-4512 59.

HV-4513 "B"

CCW Isol. Valve Close None*

C 60.

HV-8154 "B"

RCS Excess Letdown Close 1/1-8154 I

  • Local Manipulation of Valve Required I

l FI I

a

'I I

' 1

l TABLE 3A PROCEDURE TO BE FOLLOWED FOR FIRE AT STP

.(Only Train "B" Equipment Required)

I OPERATOR'S WORK STATION PROCEDURES B

CR 1.

Trip the Reactor & Turbine / Generator CR 2.

Start CR A.

Diesel Gen. "B" and Auxiliaries q

A.1 CS/1DG2E, CS/1DG2N, HS-3377A (F.0)

Transfer Pump No. 1 CR A.2 CCW PP No. 02 HS-4519A CR A.3 SW PP No. 02 HS-4251A CR A.4 Chilled Water Recirculation PP No. 6701 HS-6701 I

CR B.

Charging PP No. APCH2 1/1-APBA2 Boric Acid Transfer PP No. APBA2 1/1-APBA2 CR C.

Aux. Feedwater PP No. 02 HS-2451A i

..E CR D.

Emergency Fan Room Coolers such as:

CR D.1 Diesel Generator "B" II Room Coolers HS-5695 A,

B, C, D,

&E CR D.2 Electrical Area Train "B" Emergency Fans El-852'-O" HS-5686A1(SE-16) HS-5686B1 (SE-15)

CR D.3 CCW Pump Emergency Fan HS-5801 (SE-10)

CR D.4 Aux. Feedwater PP Emergency Fan HS-5678A (SE-08)

I' I

I.

TABLE 3A (Continued)

WORK STATION PROCEDURES L.

I CR D.5 Charging PP Emergency Fan HS-5803 (SE-04)

I CR E.

RHR PP No. 01 (Cold Shutdown) 1/1-APRH-2 (Stop during HSB and HSD)

CR 4.

While the above equipment is started, I'

other operators trip the power circuit breakers at the MCC for all Train "A" motor-operated valves in flow line of safe shutdown systems to preclude spurious signals from mispositioning these valves.

CR 5.

Verify position of Train "A" valves using process indication available in the control room. See Table 3B.

99 4

e 4

f l

l

?

$l

(

1 l

l' I

TABLE 3B VALVES REQUIRED FOR SHUTDOWN (STP FIRE)

I t.

Required CR Indication Valves Train Description Position

& Controls 1.

HV-2493-A "A"

AFW to Steam Open HS-2493-A Gen No. 3 2.

HV-2494-A "A"

AFW to Steam Open HS-2494-A Gen No. 4 3.

PV-2454A "B"

Aux Feedwater Open FK-2454A Press Control SG No. 3 4.

PV-2454B "B"

Aux. Feedwater Open FK-2453 Press Control 5.

HV-4394 "B"

Sw Diesel Gen.

B" Open HS-4394 6.

1/1-8351A "B"

Seal Inj. Inlet Open 1/1-8351A I

RCP No. 1

~

7.

1/1-8351B "B"

Seal Inj. Inlet Open 1/1-8351B RCP No. 2 8.

1/1-8351C "B"

Seal Inj. Inlet Open 1/1-8351C

'=-

RCP No. 3 9.

1/1-8351D "B"

Seal Inj. Inlet Open 1/1-8351D RCP No. 4

10. 1/1-8110 "A"

Charge PPS Min.

Open None*

Recire. Valves

11. 1/1-8111 "B"

Charging PPS Open 1/1-8111 Min. Recire. Valve

12. 1/1-8801A "A"

Boron Inj. Isol.

Close None*

l3-Valve

13. 1/1-8801B "B"

Boron Inj. Isol.

Close 1/1-8801B Valve l

  • Local manipulation of valve required..

v twm v

mme w

m m-w

l' Table 3B (Continued)

Required CR Indication Valves

. Train Description Position

& Controls L

14. 1/1-8104 "B"

Charging PPS Inlet Open 1/1-8104 Control Valve U

15. 1/1-8105 "B"

Charg PPS Disch to Close 1/1-8105 CVCS Isol. Valve L

16. FCV-110A "C"

Charging PPS Inlet Close 1/1FCV-110A Valve

17. FCV-121 "A"

Pressurizer Level Open None (Open Control ICS-8387B)

18. HV-4515 "B"

CCW Train "B" Isol.

Close HS-4515 (8387B)

Valve

19. HV-4525 "B"

CCW Flow from Non-Open FI-4536A,4675-Safeguard Loop 4677, 4687-4689, l

4683-4685, 4679-4681 or HS4525

.I

20. HV-4527 "B"

CCW Flow to Non-Open FI-4536A, 4675-Safeguard Loop 4677, 4687-4689, 4683-4685, 4679-4681 or HS4527 5

21. HV-4700 "B"

CCW Flow Inlet Open FI-4536A, 4675-Header to RCP 4677, 4687-4689, 4683-4685, 4679-4681 or HS4700

,,g

22. HV-4708 "B"

CCW Flow Return Open FI-4536A, 4675-3 Header from RCF 4677, 4687-4689, Coolers 4683-4685, 4679-I 4681 or HS4708

23. HV-4514 "A"

SW to Diesel Gen.

Open None*

"A"

24. HV-4524 "A"

CCW Flow to Non Open None*

Safe Loop

  • Local manipulation of valve required. -

l:

Table 3B (Continued)

Required CR Indication

(+

Valves Train Description Position

& Controls

25. HV-4526 "A"

CCW Flow to Open None*

1-Ncn-Safe Loop i

26. HV-4699 "A"

CCW Inlet Flow to Open None*

RCP Coolers I

27. HV-4701 "A"

CCW Return Flow Open None*

From RCP Coolers I

28. HV-4287 "B"

SW Disch. Isol.

Open HS-4287 Valve

29. 1/1-8702A "B"

RHR Suction Isol.

Valve (HSD, HSB)

Close 1/1-8702A (TR"B")

CSD)

Close 1/1-8702A

30. 1/1-8702B "B"

RHR Suction Isol.

(HSD,MSB)

Close 1/1-8702B (CSD)

Open 1/1-8702B

31. 1/1-8701A "A"

RHR Inlet Isol. (HSD) Close None-1/1-8702A l~'

Valve (TR"B")

1 l

(CSD) Close None-1/1-8702A (TR"B")

32. 1/1-8701B "A"

RHR Inlet Isol. (HSD) Close None Valve (CSD) Open 1/1-8702B(TR.B)

{

None*

j

33. HCV-607 "C"

RHR Disch Control Open HC-607 EE Valve t.

i

34. FCV-619 "C"

RHR HX Bypass Flow Close FK-619

35. FCV-611 "B"

RHR Min. Flow Valve Close 1/1-FCV-611 i

36. 1/1-8809B "B"

RHR Disch Iso.

(CSD) Open 1/1-8809B Valve

37. 1/1-8716B "B"

RHR Cross Connect Close 1/1-8716B

38. 1/1-8812A "A"

RHR Suction Cross-Close 1/1-8812A m

l,

connect l

  • Local manipulation of valve required. I l.

l

Table 3B (Continued)

I Required CR Indication Valves Train Description Position

& Controls

39. 1/1-8808A "A"

SI Accumulator (CSD) Close None-Manual By Tank Isolation Valve Jumpering @ MCC I

40. 1/1-8808B "B"

SI Accumulator (CSD) Close 1/1-8808B Tank Isolation Valve l

41. 1/1-8808C "A"

SI Accumulator (CSD) Close None-Manual By I

Tank Isolation Valve Jumpering @ MCC L

42. 1/1-8808D "B"

SI Accumulator (CSD) Close 1/1-8808D Tank Isolation Valve

43. PV-2325 "A"

SG No. 1 PORV Close PK-2325

44. PV-2327 "A"

SG No. 3 PORV Close PK-2327

45. PV-2326 "B"

SG No. 2 PORV Close PK-2326

46. PV-2328 "B"

'SG No. 4 PORV Close PK-2328

47. PV-5180 "C"

SG Blowdown Drains Close PK-5180

48. HV-4396 "B"

SW to Aux Feedwater Close HS-4396

49. 1/1-8152 "B"

L tdown Isol Valve Close 1/1-8152 7

50. PCV-455A "A"

Pressurizer PORV Close 1/1-455A

51. PCV-456 "B"

Pressurizer PORV Close 1/1-456

52. HV-2333A&B Main Steam Isol &

Close HS-2333A Bypass Valves (Two Train SW)

[I

53. HV-2334A&B "B"

Main Steam Isol. &

Close HS-2334A Bypass Valve d

54. HV-2335A&B "B"

Main Steam Isol. &

Close HS-2335A

}

Bypass Valve

55. HV-2336A&B "B"

Main Steam Isol. &

Close HS-2336A Bypass Valve

56. HV-4512 "A"

CCW Isol. Valve Close None*

  • Local manipulation of valve required. I

I Table 3B (Continued)

I Required CR Indication Valves Train Description Position

& Controls I

57. HV-4513 "B"

CCW Isol. Valve Open HS-4513

58. 1/1-8154 "B"

RCS Excess Letdown Close 1/1-8154 I

II t

5 I

1 LIm 1

i

,'I Li I

~ I I

f I.

I TABLE 4 HIGH PRESSURE / LOW PRESSURE INTERFACES Item H.P.

L.P.

Valves In Flowpath I

Pressurizer Relief 2235 3

1PCV-455A, 1PCV-456 (PORVs)

,I RCS Letdown 2200 510 1 LCV-459, 1-8149 A,B,C to Regen. HX RCS Excess Letdown 2200 40 1-8154, 1-8153, 1HCV-123 i,

thru Excess Letdown HX to RCDT

' l1 RCS to RHR 2235

-400 1-8701A,B; 1-8702 A,B n

l!l l;!

I cl

!I m

I

~

lI '

I

l I

1 TABLE 5 ALTERNATE SHUTDOWN ANNUNCIATORS TAG NO.

DESCRIPTION ANN. BOX / POINT ZA-8701AF RHR Loop 1 Isol.

ALB-4B/3.5 Valve ZA-8701BF RHR Loop 2 Isol.

ALB-4B/4.5 Valve ZA-STP-1 Shutdown Transfer ALB-6C/4.1 Panel Door Open ZA-STP-2 Shutdown Transfer ALB-6C/4.2 Panel Local Override ZA-HSP-A Hot Shutdown Panel ALB-6C/4.3 Local Override ZA-HSP-DAB Hot Shutdown Panel ALB-6C/4.4 Door Open ZA-S691 Diesel Generator ALB-llB/3.18 Fans Local Override u

'l n

j 4

I

l:

I TABLE 6 JUNCTION BOXES AND LOCATIONS I

The following valves are equipped with Junction Bones for manually disconnecting CR Circuitry and Connect Local Control the HSP.

at VALVES JUNCTION BOX / LOCATION X

Y Z

PV-2325, 2327 JB IS 1053 / Safeguard 859 4903 4852 Bldg.

1 JB IS 1277/ Safeguard 856 4903 4852 Bldg.

JB IS 1238/ Safeguard 837 4923 4780 7

Bldg.

PV-2326, 2328 JB IS 1051G/ Safeguard 859 4883 4896 P

Bldg.

JB IS 1276/ Safeguard 856 4883 489C Bldg.

T JB IS 1237/ Safeguard 837 4923 4776 Bldg.

=

FCV-618 JB IS 942/ Safeguard 857 4923 4778

~

PCV-455C HCV-606

I c

4 i

ll

' k, I

. ~

I

l.

I 4.0 DETAILED ANALYSIS OF SHUTDOWN LOGIC SKETCH (XB-2323-1800)

I Sketch XB-2323-1800, Attachment No.

1, Sheets 1 through 15, defines the logic paths required to achieve hot standby, hot shutdown and cold shutdown for CPSES Unit 1 or 2.

The downstream side of a control condition symbol I

is marked with a

small x to show the required logic paths.

Adjacent to the control condition are boxed revision numbers which correspond to the paragraph I

numbers in the column titled " Revisions" in the boxed section beginning with paragraph 4.1.1.

Tabulated below are the vital compenents and safe E

shutdown systems that are lost in a

postulated design basis CR fire as shown by cross-hatched areas on the F

~

shutdown logic sketches.

Paragraphs listed under "Section" discuss revisions required to regain control of circuits lost.

9 SYSTEMS & EQUIPMENT REQUIRED FOR HOT STANDBY (HSB) i

[

System Shutdown Logic Sketch Section Reactor Trip XB-2323-1800. Sh. 4 4.1.1 Steam Gen. Press Control XB-2323-1800. Sh. 10 4.1.2 Steam Gen. Inven-tory Control XB-2323-1800. Sh. 9A 4.1.3 d

RCP Seal & Cooling Integrity XB-2323-1800. Sh. 8 4.1.4 l

RCS Inventory v

Control XB-2323-1800. Sh. 6 4.1.5 RCP Tripped XB-2323-1800. Sh. 1 4.1.6 RCS Press Control XB-2323-1800. Sh. 5 4.1.7 RCP's Running XB-2323-1800. Sh. 1 4.1.8 I

~

I.

SYSTEMS & EQUIPMENT REQUIRED FOR HOT SHUTDOWN (HSD)

System Shutdown Logic Sketch Section SG Inventory Control XB-2323-1800. Sh. 9A 4.2.1 Reactivity Control XB-2323-1800. Sh. 7 4.2.2 I

RCS Press Control XB-2323-1800. Sh. 5 4.2.3 RCS Inventory XB-2323-1800. Sh. 6 4.2.4 5

Control RCS Seal Integrity XB-2323-1800. Sh. 8 4.2.5 ry SG Press Control XB-2323-1,800. Sh. 10 4.2.6 I

SYSTEMS & EQUIPMENT REQUIRED FOR COLD SHUTDOWN (CSD)

System Shutdown Logic Sketch Section

't Misc. Control XB-2323-1800 Sh. 3A & 3B 4.3 Systems Component Cooling XB-2323-1800 Sh. 11A & B 4.4 Water System I

Service Water XB-2323-1800 Sh. 13A 4.5 System Chilled Water XB-2323-1800 Sh. 13 4.6 System Diesel Gen. Aux.

XB-2323-1800 Sh. 14 4.7 i,

AC Power XB-2323-1800 Sh. 15A 4.8 Availability ISB 15C 1

Ia El 3

'I I

' I

I.

I 4.1 HOT STANDBY (HSB) ANALYSIS 4.1.1 Reactor Trip (XB-2323-1800, Sh. 4)

I Flow Diagram Channel and ICD No.

Revisions Case / Train **

1.* Local operation at the switchgear.

W In this analysis, it is assumed that

'I if a design basis fire occurs in the

~

CR, CSR or HSP the 3

operator trips the reactor at the CR or locally at the switchgear.

4.1.2 Steam Generator Pressure Control (XB-2323-1800 Sh. 10) 2323-M1-0202 514F

1. Add new press trans-1 8758D39 524F mitters at steam gen-

"C" e

Sh 13 erators 1 and 2 2323-M1-0202 2325

2. These valves are af-2323-M1-2202-01 2326 fected by a CSR or CR 2327 fire.

To prevent spur-I 2328 ious signal opening these valves, following junction boxes provided

'I with switches to dis-Connect control room controllers and connect local controllers at the HSP See Table 1E & 6 Valves PV-2325 "A"

l PV-2327 PV-2326 "B"

PV-2328 i

k l

I

' \\

I.

2323-M1-0202 2324

3. Provide SEl-Switch for 3

2323-M1-2202-02 2334 each set of main &

"A" 2323-M1-2202-10 2335 bypass isolation valves I

2336 at the STP and control switch at the HSP.

4 I

e-fl F1 I

.n

~

I I 4

l l ~I li?

l$

m

.I These numbers correspond to boxed numbers on logic diagrams, See Attachments 2 to 7.

Number: Case; Letter: Train l

'I w-

e I

4.1.3 Steam Generator Inventory Control (XB-2323-1800 Sh. 9A) 1-Flow Diagram Channel and ICD No.

Revisions Case / Train **

2323-MI-0206 2450

1. Move HS-2450 B from the 4

2323-M1-2206-01 HSP to STP "A"

2323-M1-0206 2453

2. PT-2453 required to "A"

2323-M1-2206-03 avoid pump runout cau-sed by depressurized SG; required steam line/ feed line break.

Protection against steam /feedline breaks not considered for alternate shutdown.

HSP loading station for AFW flow made indepen-44 dent of control room power supplies.

2323-M1-0206 2456

3. For valve FV 2456 pro-3 2323-M1-2206-03 vided a sel. switch at "A"

STP and local control switch at HSP.

I 2323-M1-0202 501

4. Provide additional 1

W 8758D39 502 wide-range level trans-

"C" f

Sh 34 mitter at steam genera-tors.

2323-M1-0206 2478 5.

Local level indicator 1

l 2323-M1-2206-07 L1-2479 available at "C"

storage tank.

New level l 'g transmitter added to in-dicate at HSP using exist-I ing indicator.

Preferable to using existing local indicator.

l 2323-M1-0239 5180

6. Provide PV-5180 on Steam "C"

l 2323-M1-2239-01 Generator Blowdowns Sys-l tem with control switch and solenoid valve.

l-2323-M1-0206 2491

7. These Train "B" valves 3

2323-M1-2206-10 2492 covered by Case 3.

"B" l l

. ~

4.1.3 (Continued)

I 1

Flow Diagram Channel and ICD No.

Revisions Case / Train **

7 1

2323-M1-0302 5676

8. Existing local fan cool-

"A" 2323-M1-2302-06 er control modified to be independent of CR circuitry.

Selector and control switches located r

locally at the Mfr.

1

-supplied control panel.

'I

!I

~

II I

r

i I

..J

(

l I

I I

l' I

4.1.4 Reactor Coolant Pump Seal Integrity (XB-2323-1800 Sh. 8)

Flow Diagram Channel

'd and ICD No.

Revisions Case / Train **

The RCP seal integrity met by use of B.A.

transfer PP, centrif-ugal charging PP and valve line up in the flow path.

L' 2323-M1-0253 8351A

1. A. RCP seal inlet iso-3 E

2323-M1-2253-16 "B"

lation valves 1/8351 "B"

J "C"

A,B,C. & D are Train D

"B" valves covered by Case 3.

2323-M1-2253-03 145 B.

Indicators located in "C"

p.

144 CR, can be used du-1 143 ring STP or HSP fire 142 to indicate closed RCP seal inlet isola-tion valves.

Edge wise flow meters also 1.-

provided locally.

2323-M1-0250 PCPX1 C.

RCP & Spray valves "C"

'r.

2323-M1-2250-OS PCPX2 provided with run-i*

PCPX3 ning and position in-

~

PCPX4 dication lights at 2323-M1-0251 PCV-455B HSP. If pumps are run-r z

2323-M1-2251-03A PCV-455C ning and corresponding spray valves are open, the RCPs are tripped at the switchgear.

I II I

' 0

4.1.5 RCS Inventory Control (XB-2323-1800, Sh. 6)

Flow Diagram Channel and ICD No.

Revisions Case / Train **

2323-M1-0251 459F

1. Add new level trans-1 2323-M1-2251-04 mitter at the pressur-

"C" izer (459F) 2323-M1-0253 8149A

2. For valves 8149A, thru 4

2323-M1-2253-13 8149B C,

move Sel. switch "A"

e-8149C from HSP to STP.

2323-M1-0261 8801A

3. For valves 8801A and 3

p 2323-M1-2261-01 8801B 8801B, see Case No. 3 "A"

2323-M1-0255 APCHIL

4. Move Sel. SW 43/1 4

r 2323-M1-2255-01 APCHIL from the HSP "A"

to STP.

2323-M1-0255 121

5. Add Sel. SW. at STP 2a 2323-M1-2255-12 for Local / Remote Con-

"C" trol.

ICS 8387A manual valve can be used during STP Fire if FCV 121 closed.

2323-M1-0303 5802

6. Existing local fan 2323-M1-2303-06 cooler control modi-fied to be independent of CR circuitry.

2323-M1-0255

7. For valve 8106 (Tr"A")1 3

2323-M1-2255-18 8106 added Sel. switch at "A"

the STP, and control switch at the HSP l

2323-M1-0255 8110

8. For 8110 (Train "A")

3 2323-M1-2255-19 8111 added Sel. switch at "A"

the STP and a local "B"

control switch at the HSP For 8111 (Train "B")

add a monitor light at l*l the HSP (Open Positioni l

2323-M1-0253 8153

9. Add selector & con-3 2323-M1-2253-14 trol switch at the "B"

'a HSP

~.

4 a

.mm.4

l.

I 4.1.6 Reactor Coolant Pump Tripped (XB-2323-1800, Sh. 1) l I

Flow Diagram Channel Revisions Case / Train In the event of CR or CSR fire, offsite power may not be lost.

RCPs are powered from offsite source and, if available, hot I

standby forced cooling is pos-sible.

However, a fire in these locations could result in loss I

of all protective relaying associated with the RCP and auxiliary systems needed to hs keep the RCPs running.

Hot 3

standby natural circulation in-troduces simplifications of control design as concluded in discussion with Westinghouse.

Depending on the severity of the accident, the operator has option to select either forced or natural circulation.

The design was revised to have:

A.

RCP running light at the HSP a

B.

Ammeter at the switchgear (for local operation)

I 4.1.7 Reactor Coolant System Press.

Control.-(XB-2323-1800, j',Q "

aSheet-5) lv,

Flow Diagram Channel and ICD No.

Revisions Case / Train I

2323-M1-0251 455F

1. Add 1 uide range (0-3000 psig) 1 8758 D 39 Sh. 12 pressure transmitter at the pressurizer and use exist-ing pressure indicator 455 at the HSP.

This covers q

HSB, HSD to CSD RCS pres-sure.

2323-M1-0251 PCPRlL

2. Move selector switch of 4

7247 DOS Sh. 12 group A heaters 43/1-PCPRIL from the HSP to STP. J

f.

I 2323-M1-0251 456

3. To avoid LOCA caused by 3

2323-M1-2251-03 455A I

spurious closing & opening "A"

of PORV's (456 & 455A) during a CR Fire, PORV o'

PCV 455A is provided with a Sel. SW at STP and a y

control switch at HSP.

For valve PCV-456 same "B"

with PCV 455A except that Sel. & control switches are located at HSP.

4.1.8 Reactor Coolant Pump Running (XB-2323-1800, Sh. 1)

Refer to 4.1.6.

4.2 Hot Shutdown (HSD) Analysis 4.2.1 Steam Gen. Inventory Control (XB-2323-1800, Sh. 9A)

Same as 4.1.3.

4.2.2 Reactivity Control (XB-2323-1800, Sh. 7) 4.2.3 RCS Pressure Control (XB-2323-1800 Sh. 5)

Same as 4.1.7 l

4.2.4 RCS Invento'ry i

Control (XB-2323-1800 Sh. 6)

Same as 4.1.5

'{

i -

4.2.5 RCS Seal Integrity (XB-2323-1800 Sh. 8)

Same as 4.1.4 4.2.6 SG Pressure

'1 Control (XB-2323-1800 Sh. 10) i Same as 4.1.2 I

Flow Diagram Channel and ICD No.

Revisions Case / Train l'

, I l~

I 2323-M1-0255 8104

1. Motor operated valve 3

2323-M1-2255-16 1/1-8104 is powered from "B"

I Train "B" bus.

This valve using the handwheel. Indi-t.

cating light added at HSP.

I 2323-M1-0255 110

2. To block flow path via "C"

2323-M1-2255-03 (8444)

FCV-110A, if power is lost and instrument air is not available, close manual valve ICS-8444.

I 2323-M1-0257 APBAIL 3.

For boric acid transfer 4

2323-M1-225% G1 pump Train "A" only, relo-

"A" cate selector switch from HSP to STP.

FI c

il 3

r

'2

- I I

!I il I

' I

l I

4.3 COLD SHUTDOWN (CSD) ANALYSIS SH. 3A AND 3B Fldw Diagram Channel and ICD No.

Revisions Case / Train 1.

2323-M1-0251 PCPRIL

1. Pressurizer pressure con-7247D05 Sh. 12 trol: same as Revision No.

2 of Section 4.1.7.

Remai-ning heater groups disabled via switchgear local opera-tion.

I 2323-M1-0250 413F

2. Provided new strap-on RTD's 2323-M1-2250-03 424F on RCS hot legs and 2 2-Pen 433F recorders at HSP.

443F 2323-M1-0255 121 3.

Covered by 4.1.5.

2323-M1-2255-12

<l 2323-M1-0262 8808A

4. During HSB & HSD, these "A"

i 2323-M1-2262-04 8808C valves may be closed or l

8808B open.

However, when the 8808D RCS reaches 1,000 psig the valves should be closed.

The MCC are pro-

"B" vided with jumpering ca-pability.

Indicating lights are alto provided at the MCC.

2323-M1-0202 2325

5. To avoid spurious signal "A"

2323-M1-2202-01 2327 junction boxes JB #IS 2326 1053!) (Train "A") &

"B" 2328 1 -0151 G (Train "B")

are rI provided with switches to close these valves.

2323-M1-0251 455F

6. To cover the entire pres-1 I

2323-M1-2251-04 sure range of the RCS, a "C"

wide-range pressure trans-mitter (0-3000 psig) added with indicator at HSP.

I

~ I

l.

I 2323-M1-0251 455A

7. To prevent at LOCA these "A"

2323-M1-2251-03 PORV's are closed, Train "A" valve is provided with a transfer switch at STP and control switch at HSP.

"B" l

456 For Train "B" similar to Train "A" except selector and control switches are located at HSP.

2323-M1-0251 455F 8.

For CSD,PI455B is used at 1

2323-M1-2251-04 HSP "C"

2323-M1-0260 APRH1 9.

Revise control wiring of 3

2323-M1-2260-01 RHR pumps to add Sel.

"A"

'I Sw at the STP for local /

remote operation and con-trol switch at HSP for Train "A" pump.

y 2323-M1-0260 8701A 10A. For valve 8701 A&B provide 3

)J 2323-M1-2260-05 8701B a SEL. switch at STP and "A"

'g a keylocked control switch 3

at HSP.

Isolate the two lines during HSB & HSD to prevent LOCA.

2323-M1-2260-05 8702A 10B. For valve 8702A, valve is

~

manually open via hand-wheel at start :f CSD.

Sufficient time is avail-able for manual operation before CSD.

2323-M1-0260 606 11A. HCV-606 valve is normally pg 2323-M1-2260-02 open and fails open.

Valve g

can be manually opened VIA JB #IS-942 (previously added to address cold shut-I down from outside the control room).

No design changes required.

i,l I

' I

l I

2323-M1-0260 618 11B. Same as 11A 2323-M1-2260-04 "C"

2323-M1-0263 8812A 11C. RWST to RHR suction valve "A"

2323-M1-2263-06 (8812A&B) be disconnected at the MCC and manually I

closed prior to RHR oper-ation.

No modifications, except procedural.

2323-M1-0263 8811A 11D. During cold shutdown, this 2323-M1-2263-06 Ig valve must be closed to prevent reactor coolant from E

flowing to the containment f'

sump. The MCC is provided with jumpering capability.

i Indicating light is provided at the MCC.

F

  • E 2323-M1-0263 8809A
12. 8809A, same as (11C) above "A"

E 2323-M1-2263-06 I

2323-M1-0263 610

13. Valve FCV-610 RHR Mini "A"

2323-M1-2263-06 L.

flow; no changes needed as HCV-606 can be opened.

2323-M1-0260 8716A

14. Valve 8716A to be manually

=

2323-M1-2260-US closed by disconnecting power at MCC & manipulating handwheel.

m 1

I y!

I I I

1 I

I 4.4 COMPONENT COOLING WATER ANALYSIS (XB-2323-1800, SH.-11A AND 11B)

Flow Diagram Channel L

and ICD No.

Rev.isions Case / Train 2323-M1-0229 4518

1. Relocate selector switch 4

u 2323-M1-2229-03 of pump No. 1 from HSP to STP J

2323-M1-0303 5800

2. Modify control circuitry to 2323-M1-2303-06 have two sets of fuses in CR & at Local control.

2323-M1-0229 4525 3A. For HV-4525, HV-4527, and 3

2323-M1-2229-02 4527 HV-4515.

Provide valve

'E 2323-M1-2229-04 4515 position light at HSP.

Trip "B"

valve power at MCC.

Any valves out of alignment would be manually operated via handwheel.

4524 3B. For valves 4524, 4526 &

3 0

4526 4514 add Se1. switches at "A"

4514 STP and control switches at the HSP.

2323-M1-0231 4699

3. For HV-4699 & HV-4701 3

2323-M1-2231-03 4701 similar to 3B above.

"A" 4700 For HV-4700 & HV-4708 3

m 2323-M1-2231-05 4708 similar to 3A above.

"B" 1

I 2323-M1-2231-01 4675

4. No change.

These process 2323-M1-2231-01 4676 indicators used during STP 2323-M1-2231-01 4677 or HSP Fire.

They substitute

.g 2323-M1-2231-01 4679 for valve-position indication.

3 2323-M1-2231-01 4680 2323-M1-2231-01 4681 2323-M1-2231-01 4683 l

2323-M1-2231-01 4684 2323-M1-2231-01 4685 2323-M1-2231-01 4687 2323-M1-2231-01 4688 2323-M1-2231-01 4689 c-I lI ii

-e0-I

. I l.

4.5 SERVICE WATER SYSTEM ANALYSIS (XB-2323-1800, SH. 12A) 1.

Flow Diagram Channel I..

and ICD No.

Revisions Case / Train 2323-M1-0233 4250

1. Service water pump No. 1:

4 2323-M1-2233-01 move switch HS4250B from "A"

HSP to STP I

2323-M1-0233 4286

2. Service water pump No. 1 4

2323-M1-2233-05 discharge isolation valve "A"

HV-4286: provide a selec-tor switch at STP and local control switch at HSP.

2323-M1-0234 4393

3. Same as 2 above 4

2323-M1-2234-02 "A"

2323-M1-0234 4395

4. Valve HV-4395: use hand-g 2323-M1-2234-02 wheel operation only.

No 3

design changes required.

1 4.6 CHILLED WATER SYSTEM ANALYSIS (XB-2323-1800, SH. 13)

{I 2323-M1-0311 6700

1. Chilled water recircula-3 2323-M1-2311-01 tion pump #05; provide "A"

selector switch at STP and control switch at HSP

,3 2323-M1-0311 HS-XT

2. A fire at the CR affects 3

2323-M1-2311-01 the automatic start-up of the water chiller control.

2323-M1-0302 5684B1

3. Modify control circuitry to 2323-M1-2302-08 5684A1 provide two sets of fuses:

in CR & at Local control.

4.7 DIESEL GENERATOR AND AUXILIARIES ANALYSIS (XB-2323-1800, SH. 14) 2323-M1-0302 5691A

1. Room ventilation fans 2323-M1-2302-10 5691B protected in case of CR fire.

5691C Local selector & control 5691E switches provided.

g 5691D

!i I

. I

I i.

4.8 AC POWER AVAILABILITY (XB-2323-1800, SH. 15A, B, & C) t, For Diesel Generator and On-Site Standby Power System, Train "A" transfer switches, located on Hot Shutdown

Panel, were relocated to STP.

Modifications, including separately fused circuits to the equipment, were provided to isolate effects of postulated fire.

See Table 1B for STP details.

See Table 1D for HSP details.

5.0 CONCLUSION

The design and procedural modifications called for by this study, when implemented, will permit CPSES to meet the intent of BTP APCSB 9.5-1 for alternate shutdown capability despite a crippling 1) control

room, 2) cable spreading room, 3) STP or 4) HSP fire.

6.0 LIST OF ABBREVIATIONS CSR Cable Spreading Room CR Control Room HSP Hot Shutdown Panel L.

STP Shutdown Transfer Panel HSB Hot Standby HSD Hot Shutdown CSD Cold Shutdown CCW Component Cooling Water SSW Service Water VLV Valve

.I SG Steam Generator RCS Reactor Coolant System RHR Residual Heat Removal e

PP P.p I

PPs Pumps 1

FW Feedwater I

  • I U

).

I l-

7.0 REFERENCES

1.

TGH-5820, September 21, 1979 2.

TCP-411, 1/21/80, Office Memo from J.C. Kuykendall to H.C. Schmidt 3.

Office Memo from H.C. Schmidt to J.T. Merritt, 5/23/80

Attachment:

Minutes of Meeting with NRC lI 4.

NRC Docket Nos. 50-445 and 50-446, 6/9/80 i

l 5.

CPPA-3353, 6/13/80, Office Memo from B.J. Murray to i

J.C. Kuykendall 6.

CPP-3381, Office Memo from Wayne Varnell to J.T.

Merritt i9 7.

CPP-3416, 6/27/80, Office Memo from D.E. Freeman to Warren Chapman 8.

Memorandum from DJC to HRR, 7/2/80 1

9.

WPT-3654, 8/8/80 10.

GTN-48361, 8/15/80 11.

CPPA-6097, 8/15/80, Office Memo from J.T. Merritt to H.C.

Schmidt 12.

GTN 48802, 9/10/80 13.

GTN-48840, 9/12/80 14.

GTN-49003, 9/19/80 15.

GTT-7220, 9/29/80 16.

Office Memo from R.A. Jones to J.T.

Merritt, 9/30/80 E

17.

Office Memo from J.S. Marshall to R. Estes, 9/30/80 l g 18.

Office Memo from J.S.

Marshall to R.L. Estes, Log 3

No. 2810, 9/30/80

,7 19.

WPT-3758, 10/1/80

! e 20.

GTN-49253, 10/1/80 21.

GTN-52615, 4/6/81

~

I

ll I

22.

GTN-52459, 3/27/81 23.

GTN-52229, 3/17/81 I

24.

CPPA-9392, 4/6/81 i,

25.

CPPA-11954, 8/18/81 i

e i

.I I

I

!I

'I 4

I g

-e -

I

SMUTDOWN LOGIC DIAGRAMS 77/1 cgm 6Xtf' f l.

j

~

1.0 DEFINITION 88. 0 NOTE $s_

CRAPHIC REPRE$ENTAll0N OF PROCEDURE REQUIRED 10 ACMIEVE $PECIFIC

l. TME$E DI AGRAMS DEPICT $MUTOOWN PRIMS 08JECTIVE.

AVAILABLE TO THE OPERATOR FOR IME $PECIFIC PURPOSE OF SMUTOOWN 2.0 REACTOR OPERATIONAL MODES uMOER r0$1ulATED FIRES CON $10EREO IN THE PLAMI FIRE MAIARD ANALY$l$.

j OPERAtl0NAL REACTivlTY 1 RATED THERMAL RVERAGE C00LANI

2. IME $Muf00NN PATHS SM0WN MAVE BEEN E

MODE CONDI T ION.N EFF POWER TEMPERAiuRE SCREENEO TO ELIMINATE THOSE f

IExCLUDING DECAT ME All NORMALLY AVAILABLE PATH $ KNOWN 10 SE OlFFICULT TO ACHIEVE UNDER M0T $iAN08Y

  • 0.9g 0

m 3 goof POSTULATED FIRES.

~

200 F *1 vg* 350* F NOT SMUT 00WN

  • 0.99 0

A COLO $NuiOOWN

  • 0.99 0

s200'F

3. FOLLOWING THE PRELIMINARY $CREENING F0R vI ABLE $MU100MN PAIM$ UNDER 3.0 SYMBOLS PO$iUL ATED FIRE CONDITIONS.

AVRILABLE FETERNATE 880TH IN$l0E 4 OuiSIDE IME CRI HAVE BEEN $NOWN.

~

PROCE$$ INFORMAfl0N i

3.8 RN0/0R OPERATOR ACTION w

i

(

l' CONTROL CON 0lil0N 3.2

(

~

TERMINAL POINT 33 ISPECIFIC 08JEClivEl 3.4 0FF PAGE CONNECTOR

\\...

EQUIPMENT DE$iROYE0 BY A CR,C5% OR A MSP FIRE DEtl$10N LOGIC q

x_

LOGIC OUTPUT *x* Exl$1 IF AND ONLY IF ONE 3.1 x-0ESIRED LOGIC PATM N\\ _

A

=

B

- On MORE LOGIC INPUI$ A.B.C EIl$1.

q 3.3 A

3 LOGIC OUTPUT *x* Exi$i IF AND ONLY IF ALL B

LOGIC INPUTS 9.8.C Exl$1.

3.6 E

NOT i

TEXAS UTILITIES SERVICES INC.

1980 Ni ATION JOB NO. 2323 ACENT FOR DALLAS POWER & LIGHT COMPANY SKETCH NO.

e aa._a E aK h TEXAS ELECTRIC SERVICE COMPANY gg.2323-1800 i

" W -"

TEXAS POWER & LIGHT COMPANY a

40 rint rRotteriou n.entists SMEET NO. 0 0F l$

T nc l=cen auctism {rttclr.s.

I$$uto FOR SHUTDOWN LOGIC'. DIAGRAMS

'g

'Sy een o c mo.

f JOS NO.II-2323-025 i

,w I.

C).

1 L

n

es

)

[ STE AM CENERATOR se 4.1.2 se

<x ex

( PRESSURE CONTROL h

SMEET 30

\\

4.1.1

[ STE AM CENERATOR I

v sf 4.3.3 v

REACTOR TRIP j

( INVENTORY CONTROL

<w ex

$ MEET 4 SMEET 9A M$8-MOT $1AND8Y 434

)'

RCP SEAL INTEGRITY

"![$0 U

N se

/s CR-CONTROL ROOM SMEET S REM / MAN-REMOTE / MANUAL C8-C9NTROL BOARD 4 I*S )(

C$ INVENTORY CONTROL

![gf"

" IA"EL

/s

$HEET 6

^

i4

.... r,E,.s,,,,,[o T

t.a X

(

lf X

X I$

?

s

.j (RCsrREssuRE Tu.i.7

( CONTROL j

j

$HEET S V

v sf I

T X 4

'.8 x{

X

( RCP s RuMNiNG

)

s LJ LJ b

sf

\\

HOT M0T STAND 8Y j

$A

$1AN08Y ATURAL CIRCULAll0N sf f

.C.

MODE 15 FORCE 0 COOLING COOLING

/s

'8 SHT. 15C

)(

/

g m

u HOT sTAN08Y a

d TEXAS UTILITIES SERvlCES INC.

8980 3

N iR ATION JOB NO. 2323 3

1d

"""8" DALLAS POWER 4 LIGHT COMPANY jd featLHJh TEXAS ELECTRIC SERVICE COMPANY 3 ggg

~

TEXAS POWER 4 LIGHT COMPANY n

uco rint enotrctioN amatvsis

==

sNEET NO. I OF 35 c

j"""*li.c l=c.l xuaa "y o njo.

0 ruc r.c.

Issue 0 FOR SHUTDOWN LocIC ot AGRAMS J08 NO.II-2323-02s r

r J-3 N

~

l g

?kh r

= =Lw -

- f'

_2 uma sans amo muss amm e

l FROM 350'F DOWN b

, hP 4.2.5 )R

$G 1::vE::10Rf CONTROL

4. 2. 8 s, F0 LM l

J

^

$NEET 9R SHEE1 8 5

(acac'"c"'a')

' ' ' X RCS PRESS. CONTR

  • *' )(

$NEET 5 v/\\

CS INVENTORY CONTROL

  • * * )'

fj i

5H((I 6 gg

^

NOTES:

{j

)(

l. CONTROL ROOM POSTULRIED FIRE COINCl0ENT WRIM g

3 LOSS OF OFFSITE POWER

't

'i i

LJ

.i

$G PRESS. CONTROL

)(

,g LJ

),,,,,, )

)

o M3I $HUTOOWN d

4 l

i TEXRS UTILITIES SERVICES INC.

JOB NO. 2323 i Ril0es ih 3980 N N RCENT FOR J

DALLAS POWER & LIGHT COMPANY SKETCH NO

'j

'8

.%

  • filme TEXAS ELECTRIC SERVICE COMPANY xB-2323-1500 n

f TEXAS POWER & LIGHT COMPANY SHEET NO. 2 0F B5

=

FIRE PROTECTION $NAtTSIS A

WED 3

d one o

c. *# ac =c..ntian etcc e.e.

Issuto fon SHUTDOWN LOGIC DI AGRAMS

'5y Jos no.a s-23n-o2s j

w

-.....7 4

rm J

Q

.i NNAIN1Ad2.*$

^

~

I sem nas sem um use

=

mas see som aus een

  • ' ~ * ~ ~ ~

= -++:--=-

.:_. u.

.y-

~,.

1 t

m N

o 2 at M

.O m a 1 F as m

o-gf"5 "A R

.3 M

i O

EM ata

- <w =

l 3

-c5 S's Og" ce-2:

m "a

2.

Md.

I' at"L k Y o

5 cop Et*

  1. Ac e

3 g ::; *f ey i (

"4 tiri M

u s.

=

252 *ho-4 f

,,, E ;

=

1 2"E 3 if

$ ~8 "g2 i l

Es* 25's fl 0

m ou e

a 35 r "w

ar_g =zs a

5 q

w e

E EM-J'##5 *558 9/

s *."" "."~~

8

.a,f s

Msea5 E

g

,-aga 3

u z,-

~

e (3

e wt*u-8 A

s-s-

ssse a

w=

sa o

se o

s/

ur a

a u

2 1

==

r'-

a. = 2 g

t a sc:

/'/

aa. /c,/

}. ls. -

=

mw, r'

. tit /

/,w

=

e e

z e

oo o e og

=..

d p s3-m eo

,C, w=

g W

EPo e

g ti, ? '

O o w '-

fvi

.g,?

es8 go ef,8 o

x ee e

ss ve

-as

  • r

' ass qj

/ --

g

/ --

%)

=

4".

.I n

g 9'

n Fl d5 W :

E gl r:

Q E

~

L~

V8 b

' I{

M fl2 Fl

{.- -

L-b b

o 8

8 8

E" E

"o R

()

a o

a o

()

()

w w

ke a.

l$

N e

OO S.O SO 6

z n g:

gI:

g em

-z e u o

o o

r a

a.

e o

-as ole

-c, c,

eic, o

a s

s

=

u w

w os a

u c3 g

a oh f

E

// [) [/

b b$ t,/../

/

S E

o c

g gy

=g

,,,= 7 p =~.=.8=ew 8c c, u~i ~ w,-

g

.~-o

~-o

-g-

.../,/

2-g,c

... /

o 2

=

a d

m oos

/-

go go/

75Y 7.%.Y, $2" og $

S. abi,.022

,e v* - e.,* w/.

"we

, e.a c, 2, o

>gw-o-

=

s.

a c

www vow Wy, s

a.

-ew ca a

taa tad J>

c p c.J J hm

,ge-

  • Q O Q) 3 / Bf_

',@l w.

't w,

.e.

s.w

/ i'

//

Est

?t'

//t &

ccw w

d h=

g L -.

J

\\

s' l

Fl E

9 t

n F1 C

F1

}-

c

_L c

E u

e 56 4

z-c Eb LA-g c-

/\\ /Y E3 O

EE

~

S S

S i

d-

=5 g 8/-.

m w

v w

w o $

rf< < '

r '

i,,/.c/ p.e/..c/

a;;;*,

it a

/

A 8

E O

". i

/k= 2' o.2

/.c /

^

n'r s' n--

o

=

zy.

zW,

o o

=Y, zY.

o8o n

m

=

-r w/

E

/ g w,

.e,k$,

b,k $

. e,k $

E,k$

//o.

So

/

'ddd

}s

. 'gu,

/

=

n

-o es v..

an -

ac ~ -

e-n -

ese O

/me

~

een m

,eg w

w

~

w.

~ew

~ew new new ececo mE-ww/

=

un n

n EC

/E:p MT7

/EE 7z0 7:0 75 713 YTTTY

- n w

am a

/\\ /\\

/ T'.

/T' E0E IOE E0E E0E IIZRC ss ar i w,

n eri me, min an are nr. we me

-m

-n wi m

=

u

-a

,n

~e

. -. _.. ~..

l Q.C. N00E lin

/

l t

$ MEET ISC CCW FLOW 10 RHR \\

RC5 UMP ISEALC00LERf i

TEMP 4350*F PRESS og25PSIG SMEET IIA FCA6 0

-s' flotE ITY1 s

RNR HlNI

I ISMEET 3Al II*A*I 3

\\ PL0is_VLV. _'

s

'IFROM(DNTROLROOM(j\\l/1-APRM-1 Rt1R'f UMP 'Ist 'ST A' RTE'D

.,3 g$"C t

J

's gggf*6 g,

g M

g l

~

srt0N <0Nr.N tcG'a50L.vatVc -

3 rim

]

hl[$0 L

Ul$,

CW FLOW 10 MHR HI gy

$nEET IIA I

Rh8 L

OPEN ITIN1_

UG 0

(OPEN)

'N PPS VLV

',O 1

OL. F R0st

\\PL0nevtyk II*A*I'l

\\(LOW COWT s

d 8812EIN',\\ '

CLOSE

. fTTE RnR EMERGENCY \\

COLO 8'

\\ \\

70guse IF.A.I.I FAN C0ll UNIT

/

IAVG *200 F [

hA U

Op W

$HEET 13 HR l'NLE Ts

'I*A*3*I 8'

\\lSQL.V AL VE N N8702Ax \\ '

is

\\

OPEN [lMl e3 RHR LOOh lutEtx (F.A.I*I l

N ISOL; V AL VE N '

NOTES:

In 86 4 \\ \\

et ogg l((El m

r

1. RHR HEAT EECHANGER OUILET FLOW CouTROL VALVE MCV-606 CONTROLLED FROM SUMP coNThot\\

X n

4t*lO MR MP JUNCil0N BOI Jeal59's2. ONLY FOR

\\

IRRIN *A* EQUIPMENT D

gf g H

ROM RHR LOOP-INtEfx CONNECigVl(

' IF. A. I.I

2. RNA HEAT EXCHANGER STPRS$ VALVE

's \\87018s \\'

CLOSEC FCv-610 CONTROLLED FRON JUseCIION a

80I Je sl59182

\\l50L.VALVEN '

d N\\8702ex \\ ^

^@0h[fg[

~

COLD SHUTOOWN E

Isa0N2 235 N"$N!iANAil04 TEXAS UTILITIES SERVICES INC.

JOB NO. 2323 AcENT r0R DALLAS POWER & LIGHT COMPANY SKETCH NO.

1*4e a H__4_%

TEXAS ELECTRIC SERVICE COMPANY XB-2323-1800 TEXAS POWER 4 LIGHT COMPANY SHEET NO. 38 0F 15

=

a ut o ring en0irttion amatrsts

'5[oan j o. lc a.l"$'lac =ca{=ctraafnecjr.

Issuto r0n SHUTDOWN LOGIC OlAGRAMS J08 NO.II-2323-o25 c+

a I

e

..g M

M M

M M

M M

M M

M M

M M

i5

'tNOTE 3

' NOTE 3 9

I

\\0

\\ \\U 4

n

, x 2

\\ E

\\ E S

\\*

\\\\.

m E

ENf -

ENE E

b is-U 5

RG N.

R '.x "5

AEN "Ed' 8

x E n.E T$

P2 J

o --

i i4

'EewE y\\-

y'_3' 0:s tJ._'

Ig 3Y E

2_,

1;r

  • n TO

,oy3-

.oy.

O b55.

, EAT zS 30 j

2S

'x it

.N bR S

'ist "23

]

NOTE 21C NOTE 2 Jb N01E I

]

4 I

2 5

1 8

y if a6 E

l$

6 E

E o

o E

E E1 a

a 1

3 i

j 5

L I

.5 a

22 E5 Ei 22 IT Ea

-L o

e 5

5 g

E.

E E

E E3 EE 78 5

Il C3 C$

"M Ei Io M

$8 Ea -

T

$E j

f "i

f.

.gz t

r if i

1'

'l

'l

'l gy[gg f

i O

()

3. REACTOR ulLL TRIP FOR a Ignalg TRIP CON 0ill0N C01hC10Emi ulin 44110 inERnAL POWER GREATER Inte lot.

g

2. TUR81mf TRIP thPUTS WMICn APPgan ON WE$f!NGMOUSE dug.724700$

SnEET 2. l$ Snous SEPAAAf ttr Om

(

iMIS SMEET lu CADER 10 DEPICI POSSIBLE OPERATOR ACitos.

t

.3. REDUNDANT ThlP-TRAlu "A* SN0mm.

TRAlu '3* $3ntLAR.

s CONTROL & SMUTDOWN OunP TRIP FLulO l

R005 RELERSE 10 TRIP TUR8INE U

ERCTOR TRIP d

REnCTOR IRIP,

les0 N N E $w!iAd kil0N TEXAS UTILITIES SEhVlCES INC.

JOB NO. 2323 AGENT FOR D

DALLAS POWER & LIGHT COMPANY SKEICit NO.

M4MS_%

TEXAS ELECTRii $ERvlCE COMPANY X8-2323-1800

d J

n- "

TEXAS POWER 4 LluiT COMPANY SnEE1 a0. t 0F IS Wo, i i rint rnortction anaLMIS 155uto ron SHUTDOWN LOGIC.,l AGRAMS

"[osu l o. lc agm j.wc.' uc6 an) 6 c jr.e.

O se so.n.nn-cis a

~

,, 7 G

r.

em.*

+- @g.4(w J..

,~

.... i

. d _..

< a -<

' i

--a i

l

\\

man aunt same man uma mes sun sem ses mee ame une uma sus same am man ung

l}'

^

3CS PRESSURE CONTROL 1-8000a. N 'N PORv noiDR ortr.aTED et0Cx entvE IRE 0'D. FOR PSB) f sa)e000ei ClosEO j

"E " "'"

R.C. N00E I PORV*S OR BLOCK 5

5HEET I5C l-8010A

/

f "

/

V VA VE CLOSED PRE 55URIZER SAFEiy VRLVE$

fg 4

\\

E

=

prs SAMPLING R00n PI-467, P(v-455A*t18.8)

REMOTE nrNURL CONTROL PREitentIER

}

'E

Pd.EES'Oel

' ff] =

' * ""'E'

  • E'"'

h h01E 1 MSO PANEL

'g j] '

P-53

'f PEE 55URl!ERN) gf 3.PcPg L m

\\

\\

,#[g timEtEllED/0EENERGilE03 e

4 i

m

',U J

'r t'

P stLDOP x,

8 4

. C04TPOL 1;

)

PRES $uRjlER yfg.pcpngt

/

P(-405 L'00 8'

j (Chtt0llED/DEENERGilED

-# l/

u PRESSURilERPREssuRE]

NOTE $e sf INDICRIION j

g I. PROVIDED CHARCING FLOW CONTROL is

/

AVAIL ABLE AND PRES $uRIZER HEntER$

RRE DE-EmERGilEO IMEN PRES $UnilER Ea x

{

RELIEr CAPACliv IS NOT REQUIRED FOR NOT STAND 87 !asATURAL CIRCULAll0NI.

f

{]

2. PRE 55 uni!ER HEATERS ARE REQUIRED I

IF PRES $untlER $ PRAY VALVES OPEN srcRIDusLv.

5 U

RCs PRESSURE CONIROL d

H58 E1 N!ind4TIDu TEXAS UTILITIES SERVICES INC.

JOB NO. 2323 1980 30 RGENT t0A d

0ALLAS F0WER & LICHT Cf,RPANY

!J

{**1gMM TEXAS ELECTRIC SERrlCE C07;PANY 3 ggg TExRS POWER & LIGHT COMPANY snEET No. 5 W n

==

rine rRo1EctioN ANALV3:s A

id o Issue 0 70R SHUT 00WN LOGIC OI AGRAMS t$

" [ om lo lo.a. $ lac{wc. aanlneclr.s.

J08 m0.Il-2323-025

[..

i t

p.4 r

a m

o _.

e m

ses uma num num een uma ame ses amm seus amm sums aus ums aus mas aus

i

~. - - -. _..

m N

o m

o N

d2 B

  • A E

3' o

=~

z M2 2 m

"a

==

o, y

e u

5 CE E g

IBI *5 I

A s

a E

O ow o

u o

=

m as 3

-u-5 m g - =- 5_

53 o

=

._ p m,

u

~8 n-w =, u.,

o a

AA e

o

- d e b eE5 E

a

\\/

~

e e

u a

o

s ow e t;

C E

j$gO E

i i '

~

z ow-m w

5 5

E rl o

o e

2x 7N

=

s J(I s:#

.G

'j g

E:

h, l

[]

E T8 t

E E

j, 2

w.

()

()

E O

O i

o a

4.

g F

d

~

i 2

g 5

a 88 8

E I

E E

S ge a

5 5_ 5_

g wo s

3" Q

E E

o s

a a

8 5

5 I

E

! h 4

50 d

A f

5 5

50 E

E i

fl 5

o 3.g s

oc w

25

-S E

8 g

o E.

$.$ o!"

I

.(p

d..*

A.

2 *2 O

fl J

. f..

o

- 3y 5

5' s

C ll:

w c,

E

/N /A T-l2

/\\ /N

{

S

'V r

m d

f f

0 e

e b

t is-A o

7 7

7 7

7 7

7;.7~7' r

y 5

hd s

2

/ / / / / / V / / /

X l

V f / / 4 d d V Y Y

' s y s e

=

~

s E. g a s es e y y # # R d z d d r

+

h RRRi_FiksiEEZZMMEMM E i

I sM h

e a

5 5

w

_.I.

77-i

/ /

s n y V V e - -

w

) '

r-fj' I}

p a

9Q JL 4f

[ s*.i

{

yt Ii >.

U I;;

f q

)

mo o

s 3

T 2

0 S

w Lu 3

0 I

B 2

8 0I F

0 Pl s

e n

l 3

?

E I

O H2 N

L N

C3 0

I2 u

g E-y 8

KB m

t L

f A

0 SX y

J n

u f

s n_

LA U

e N

l A

t N

C Y

t N

Y N s

Y NA a

o.

I N

N 3

AP S

P M A S

m P

M MO E

R A

y OC C

O R

}

C l

E C G

L lyO y

T C A

lR R

H I T ID a

V H TT AO E nGI R G CN m

S a I

rLE C

R S

S L EC u

I G

T M

E N 4

O C

I E L

GRI R T AER N

I E

N m

5 WT W

W L

OC O

O m_

\\

I PE P

D a

T L

U SE T

S U

A A

H S

L S A

L A X S

E AX s

X T

7!

DE u

E T

a T

_~

L x

m O

N R

O ND T

m 3j

\\j

\\/,

T I

u f

A OS n

CC N

A M

T T

T6 Y4 O

N A

T N

s NE PT ID 6

I OM E

M CA RE GE VS u

T Y

OR NH IH a

s E

CL Bu

!S T

E Ir 5

G C

U0 6

H Rr sA RM S

Ou cE AO A

3 BS RM HR E

0 CF R

,Y 1

N f

[(

0 8s I

a v

i m

s u

sv X

t Gv nu n

n e

s N

r i

o a

o m

T t

+

u c

s r

i s

o I

n ml P

a

~

m

_~

t n

n u

~

X C

R I

73

]

]

H e.

Ct f

e r

O0 TN

-~

c m

e t

M a

e T

an A

l e

P i

t r

cu g

1 N N n

OE R.

r m

a 2

LP c

m FO C(

a l

N e

P 1#b N

e M

R R

n U

T E

P MI P

e E

E NC O

r N

N T

G l

M L$

.I O

O E

l N

q R

A u T

Ts 4

s.

s N

A Y

L E

0 F

.P 1

i O

UL P

S R

NA C.n I

A.M 8

d A

O A N A

WA u

1 m'

B MA Rs c

Br OR C

I 0

LT C

ll 5

t s

E SI y\\

A w

o N

I B&

a y

SS t

C P

7

\\0 E

S II T

e NK 1

T i

n E

A m

WN E

T 0A CO A

E E

I o

OA E

E A

S U"

D H

!l L'

CN lE IL I

HT D

H E

tA O

5 g

g5 C

0 I

)D S

O 5

H N

A N

4R E

R 4

2

'&o m

0 C 0(

vL V4 B

$2 E

hK S

I C(

L4 R

P l

C.

8 R4 B

Mb SF f<1.

]\\

C.

IP

(-

m k (-

V8 E

(

A nR A

a AO e

p p

Y l l 33 l l

l l

]

N j

k d

,w lf j) -

"{!

f

i i

l' j

f U

,9!

,}

N C E N ADrouait Ft0N rrg)

Mit43ha \\ \\ RCP SEAL 150LatiDN rrR1

}

g rep 0fynhuAA

~iRGiFDPEN

~

)

N ADE0unTE Ft0N figl 4/

3

\\N RCP SEAL 150LATION IIRl _

,1 Rico n uRA v4Lvf OrgN 1

t g

)

\\

ADEOUATE FLON ITH1 p

\\ INTEGRtTY I"

N/I 3S \\% BC M A tl$0Lafl0N IINI IREc0 yn.uRA

_ VALVE OPEN Y }

\\

ROE 0ue1E FLON ITH1

/

$0LRT10N rfNl RECIP. CHRG. PP \\

FM.SM.

04 CENT. CHRG.

'/

PP #1 RUNNING TDM"

=

7

[ TRIF PCP e 3 OR 2 d

(RUNNING RT $N11CnC(AR J'

4/IMCfly '\\ _% riU

+

RR 4RoqNIN d

rra 4,iw m v]q R Q Q ROWN 3

14 *4 % % ' rm.

g s,iw m bsnu_ N ~

[ TRIPPCPe3 ore Re % RxN m

(RUNNINGR1SN11tnC(An J

rrE]

.c.

/

( COOLER BEARING j

/

RCP

\\

[ CCN 10 tuet OIL T k INTEGRlTY COOT.tNG CCN snEET sie

(

g e

j e0$$"$ [.'"fuhl[hi 0, TEXAS UTILITIES SERV]CES INC.

JOB NO. 2323 1

RGENT FOR DALLRS POWER & L]GHT COMPANY SKETCH NO l 'g R"**Ahla*i lEXRS ELECTRIC SERVICE COMPANY XB-2323-1800 J

" M""

TExRS POWER & LIGHT COMPANY SHEE1 NO. 8 0F 15 Ay A

Nt0 rine PaonenoN a.atisis

=

ue.c.

,cu. iac r.r.

issuco rDa snuiooNN LocIC oinGRans ay om c

~.

..s.

r..

5a5!fA$dib$kbNN$$$

mammannessugum

=

=

=

=

=

=

=

=

E FO-24538 tCRL Pv-auS38 OPEN 18 STERH GENERATOR INVENTORY CONTROL IHSB & CSDI

\\

.F K Qq530s (MSPix (F.0.8 xxxxw I

N!I!*t0)b\\

""28 acv40Ca N g ri-2 sSB I

LOCAL IMO.

\\ \\

\\\\\\\\ \\ \\ \\

50TORNSR1vfM Pup

\\

NOTE $s 3

AtsX.

FMDu53A*1CR) py.2g53A OPEN,fg M.RAI ts1Mtthe i t Al fn=2453C (MSOPt N \\ \\\\ g IF.0.8

,ERCEPT CEDsST(A

1. R00M COOLER SUPPLY k$ 2451 \\

' My-249tB OPEN.[B SI MC 2

0 QC I

SC4 r

gg,g,y,,

N\\lN O

45 5

MSO PANE _L

^

x uP i

N-24M CONTROL _

START r

A b

i SCI sh 7 ux. F.N. SUPPLY 10 SG B 4 2 PW-St00 q g nq L

AUTO PUMP START J

CLOSED g gy y f

MSO PAhEL [i[]=

_ CONDENSATE [g]

CN

\\ Aux F.N PUMP SE-Ol\\

't:3503q

\\

$TORAGE TANN (1 24 h8 L1-247ea MS'R

/ ROOM F AN COOLERS /

Lie 50 URN est. vt CONTHOL ROOM LT-5De ts C' 4

~

$1EAM GENERAIOR

/

$5N

/

LEVEL IN0lCAll0M

\\

FROM $M. 32 \\

' I I

SAMPLE 84 S.G.58

\\

\\ AC PONER ROOM MANUAL SAMPLE A.C. N00E 5 A, -

[]

6 I

O Aux. F.w. surrgy q

g DC PONER ION

,, r S.C. BLONDOWN

.C

\\

\\6 0f Hsb5'8 Fv-2456 OPEN

[5],,

C I l_S ION hEbCA2

\\

I 0

B, j

IF.O.B MIN FOR

. MSP Aufl QPEN{C%%Ng i

w.m.,

)

isB0$5NENSN!iNat:

TEXRS UTILITIES SERVICES INC.

JOB NO. 2323 0N AGENT FOR l

e DRLLRS POWER & LIGHT COMPANY SKETCH NO.

I f*81 eL Qs4 h TEXAS ELECTRIC SERVICE COHPANY gg.2323-1800 TEXAS POWER & LIGHT COMPANY

$ MEET NO. 9A 0F 85

==

n we n ne encircTion anausas

. g d

'5j T

isc ncen auctinn stic r.r.

Issut0 FOR SHUTDOWN LOGIC DIAGRAMS oart onn.

como.

. g 0.... m,.0,5 dkhIT

I t

1 E STEAM GENERATOR INVENTORY CONTROL MSB ACSD

._ ""'jc g

n

_ Manual DPEN N$-2452 \\

E M_-24$2-1 OPfu

\\ \\

V f

V (CRI x ""N"L (F.O.s N

t G',$'Qx'\\,

aa~ua', car =

ga-g~

"" ' a 5 ' ""' ' ' "'

j g

h 2

Hf-245 2 OP(N mamuAL OPEN 80RI MesuhL OPfM IM50s h

2.-d

' ' E TURSINE ORIVEN I

TUR8. TRIP & THRO 11LE VLV. OP!M P

L0W SUCTION PAf$$unE TRIP MV-24948 OPfu IF.A.I.)

h5 9

)

E CONTINUED L

M' ON SM. 9A MV-2462 Orfu 8F.0.1

~

FR2462-8 M$0P F'

\\ \\ \\

'E 'h$hghk Y

MV-2491A CPfm eF.A.I.I Af4 (Mast X

s.s.sr kN f

E L-MV-2459 1F.0.8

(

q0P\\g,h$hg91

\\\\

MV-2492A (F.A.I I s...,

nr4 inA e N

]

E N*

(

MV-2460 EF.0.8 YkO

80h s $hg91

\\s

,I.

]

MV-24938 IF.R.I.I h

ss3 AfM IMA N

C L_

py.2463 IF.0.8

<< e"h*%

a 1

1980 s0 NI ETION TEXAS UTILITIES SERylCES INC.

JOB NO. 2323

+

AGENT FOR y

DALLAS POWER & LIGHT COMPANY SKETCH NO

!; 'H 8*8**1_8% h TEXAS ELECTRIC SERV!CE COMPANY XB-2323-1800 TEXAS POWER & LIGHT COMPANY SMEET NO. 98 0F 85 ring rnotect:Du anaiv5t5 a

uP acca nscan cac r.c.

issuto Fon SHUTDOWN LOGIC DIAGRAMS

[ one l o lc.e.""ll'liac soe no.ss-252s.02s l'

s.

l

_J T ju

\\

TURBINE $1EAM SEALS IURB{NE TRjr' 4/4 TUR8INE 4/1 MSIV's MANUAL tCRt OR '

REI3I

~ST6 FWALv N O C CLOSED

[

i SNEEI T g

J x

.\\

AL O MAM IF.C.I 4/4 M$lv BT JPA MS-233 6 8 I

4 MS-2333-8 T

)

3 ad INSTRUMENT AIR II C N

'\\N\\\\NN-DijnP VALVES CLOSET

' vat VES CLOSLD MS-2335-try T*'I2 4

j

'\\

N iEXCEPT C00LOOWN MS-2336-9 x Bf7B OUMP VALVES 3 ALL OlhER I

(s-av3e'A\\'

P5-2043-A CONDEN$ER VACUUM PERMISSIVE PRRALLEL (T

8 m xx OuMP 4 DRAIN s

  • 5

\\\\\\\\f PATHS CtosfD s

f

,\\.h.

0FFSITE OUMP U _

_DNDENSER A

\\

A. C' g. N00E OM R

[

STEAM LINE

\\

l 11

\\

\\

N j

SHEET ISC C00LDOWN

(

ISOLATION j

g gggg g

0%" vat vE s

)

l" 8n,i"(

J

_nRCutanNc NauR p

Pi.$i4A is.c,i, i

j PUMPS BUNNjNG Pv-2369A.B.C PI-524 Axis.G.28 CONTROL ROOM _

"?

PI-634A 15. 0. St.

g4 P1-544 ANIS.C 4!

STEAM GENERATOR g

$1ERM'00M SV AUTO CONTR0t $;EAM OUMP P325148 'is.htt.

PRES $URE INDICATION

.hOL IC.R.I 3

MSO PANEL fT1_

y P1-54ue IS:G.m

' 51E RM 'ME AS R REM 0TE MANUAL STEAM DUMP I

Nh8L E'R '

~C NTA0L (C.R.s SG PRESSURE

\\

CONTROL j

h vntvE 10 CAL MANUAL MAN 0 WHEEL CONl ROL

~'

~

g' MN TION y

ATM0]PMgRIC s

UMP VALVES x

x

\\

AUTO CONTROL tF.C.I CLosE IM M H50 4 CSDI NOMS d

gg j

p sc.R.)

v LvE TRAIN S.C.

S.C.

Pv-2326 8

2 j

SELF-0PERATED PRESSURE Pv-2327 A

3 CONTROL Pv-2328 8

g IS PER S.G.

MSB) j ITYPICAL FOR EACH

2. Sysitn l$ RE0'0. FOR H

OF 4 $G $1 N0it 2 2/4 $.G. IN MS8. M$0 & CSD.

1 N

SG PRESSURE CONTROL 3

i IHSB & HSDI d

TEXAS UTILITIES SERY1CES INC.

JOB NO. 2323 J

3980 N i Ail 0M Ia AcENT FOR s

I DALLAS POWER & LIGHT COMPANY SKETCH NO.

ik MA* afdLine TEXAS ELECTRIC SERVICE COMPANY XB-2323-IB00 s

TEXAS POWER 4 LIGHT COMPANY h

SHEET NO. 30 0F 85 a

INto !

i 4

i rant PaoirClioN anatvsis j

f l nare l o.a. !r-a. fn'l ac l.rc.l ucu an : ac ir.e.

Issuto Fon SHUTDOWN LOGIC DIAGRAMS h

4 Joe No.is-23:3-02s y,

M 3i$v43A$YiEif$dINIfA 1

w..

s\\STGRisHS-usisa '\\

COMPONENT COOLING WATER SYSTEM nAwuRL *st eT*

TRAIN *R*

i g

\\

CONTROL R0on TYPICAL FOR TRAIN *B"

$15 (OPERATOR LOCK 0Uit BOS 10PERATOR LOCMOUTI N Hg.ggi

\\

" AUTO $1 ART

  • l s \\ AUTO s

CONTROL ROOM n

V 5 HARGE PRESSURE N

CCM Pune si

$tA M

Al

\\ _SSW-PP-A RUN v

y

\\\\

0 OER PRESSUREI SIS tRUTO LOCMOUTI

.'. f

\\

to $$g 805 (AUTO LOCKOUTI x

SMET h k

\\

BLACMOUT SF0 SIGNAL g

\\ SHEET e 328 N

'S' SIGNAL SAFETY INJECT. SEO. SICNAL

\\

CCW FLOW TO s

i H

AN 9

J

\\HS-451ga

" LOCAL" fTI g N\\\\\\

T SO PANEll

\\CCW FLOM TO CHILLE ATER SYSTEM CNOSR 3

A.C. MODE 8 5HEET ISC

' i E

O 00 1

MS-$800 1:4 SMEET 118

/

4 3

CCW ROOM F AN i

.a

\\ CCW FLOW 10 RNR M (O HE & PUMP SEAL P

I\\

C0OLER SHEET 38.

f 1

FR. 5H g0nAntnE pggg g,g,$

33 ise0-s2-2300 nu INSI ALLitl0m TEXRS UTILITIES SERVICES INC.

JOB NO. 2323

g AGENT FOR

,3j' DALLAS POWER & LIGHT CORPANY b1Ld%3ae IEXAS ELECTRIC SERVICE COMPANY 3 ggg s

TEXAS POWER A LIGHT COMPANY SHEET N0. IIA of 15 FIRE Pnottcitou nuntests a

wto l

c.. "*f ac acc l.metena {ettc c.c.

'5[one Issuto FOR SHUTDOWN LOGIC DI AGRRMS o.

'4 JOB N0.ti-2323-025 l

A

.i is i

n5-4536 No-4536 OPEO tF.A.I.

m g-M f

, g H5-4514 NY-4514 OPEN IF. A. I. )

', a g

CCW FLOW 10

\\

NON*SAFEGUARO LOOP q

d TRAIN A SM. IIR /

RCP al CCW FLON l

MS-45tS.

MV-4515 CLOSE IF. A. I. I.

- gj

_ g RCP m2 CCW FLOW

[]

/

E MS-4527.

MV-4527 OPEN (F.A.I.)

U 3

\\

MS-4524 NY-4524 OPEN IF.A.I.)

g 3

j RCP m3 CCM FLOW s

10 SMEEI 8 HS:4525 HV-4525 OPEN f f. A. I. )

MS-4699 HV-4699 OPEN IF. A. I. )

M H5-4700,

Hv-4700 OPEN IF.A.I.)

COOLERS UPPER 4 lower ]j CCW FLOW 10 RCP MOTOR 5

BE ARING L.O. COOLER 1J M5-18 70 8 Hv-4703 OPEN IF.A.I.)

RCP a4 CCH FLOM s

^

H5-47083s.

HV-4708 OPEN (F. A. I.)

m Ng s

x s

SUFFCIENT FLOW m

F1-4675 BCP a 1 MOTOR 4 BEARING COOLERS J

FI-4676 F1-4677 SUFFCIENT Flow e

- FI-4679

~

RCP W 2 MOTOR & BEARING COOLERS Fl-4680 F1-4681 SUFFCIEnf FLOW e

q N F1-4683 RCP w 3 MOTOR & BEARING COOLERS F1-4684 F1-4685 g

SUFFClful Flow e

F1 il687 RCP a 4 MOTOR & BEMING COOLERS

  • g F 1-4688 F 1-44689 y

E

<0 - E,EA. 5.E.5 I

I 1980-82-2300 nw IN5tAttiil0N TEXRS UTILITIES SERVICES INC.

JOB NO. 2323 4

AGENT FOR i

0ALLAS POWER & LIGHT COMPANY I

l NM3!M,h TEXAS ELECTRIC SERvlCE COMPANY 3 800

]

i rInt PnortcTion naam35 --

TEXRS POWER & LICHT CONPANY

{ uto i SHEEI NO. 118 0F 15

, i Issuc0 F0m SHUTDOWN LOGIC DI AGRAMS N i am 'i. {c..!TJ'lisc ac..ucana rac!r.r.

.e. i

g a No.81-2323-025

-4

___ w 56' l

1 I

amm se amm um mum es num sum um ums L

n..+

fr M

M 8

.a.

~

1 m

d ".

  • 2

=A :

4 u

o

=~

z vg i p

m we a

~

t a,

y t

a i

^

l s

?

S

- = e..-

=.

t l

0$

I i 0

t 53 sa

=

5 8

EE. ~o Ws2:ge1 "u,

M z

m

-sw a a m-G

. =. -

w=,u, o

m

-59"

~segE E. '

m voz 2w z

z a

ou=

2 U

W 2 ow

==

g, w o

o g

Cm D

/,!

o mw e C

>e C M

I

@ c e-m

.J Fl

  1. 3s

=

C' t

E o

wzo w

r

--m CC d

  • 2CJ e-C W v L

o

" ~

.5 J

==

= -

u

-=

fl

  • 2 s'

of,l E~

(

g ri

,,s

=

vs

?

v::

I wa f

1.4 as s-

s
B t

fl st 5

E i's

?

E E

.4, g

o O

E e

a a

s Fl Fl

y e

j a

g

.m s

s

- a O

O Fl O

Fl s

a 1

.c y

E i

o o

E

~'

a

_L 5

5; tl s s

8 8

5 R*: 1 E_E5 e

a 2

2 i

2 ".i 22 8

8 g

5 5

?

-52 5

5*

'o E

S Si 1*

5 Y

Y E

5

'1

~

~

d d

i d

5-s c2 6

a?

Jh 3

d'd a

'r !! !!*585

$$6!d dI

--i E5! f f El *8 1 v

3,.1

'A

/ /

d d /

/,

uu y

/

/

/. /N-I I

/.

' /

/.

$' / /

/ / / / 'V V / /

/ /

E

=*

'$' / / =~ / / / / */ */ / /

/. /

i 5

l i t: / /

/ / / / 'V V / /

E' V a

V V

/

V V d

' L' / / 5 / / /j / g u //2

.s i.s i p l

w 22 2

/

j f

" C s' "' e =

m-r-

an r.

m m..,

~

!1I SERVICE NATER SYSTEH-HSB lq

/

TYPICAL FOR TRAIN *B*

TRAIN *A*

'a N

5 i dx N

5800-12R f l

3 SMEET llR l

II S.S.W. TO LUBE OIL COOLERS CENT.

j,g e

CHRG. PUMP 01

$NEET 6

'I,j ie ttS 39

\\

(ERI MANUAL q

/

$.S.W. FLOW 10 I

\\.

s y

\\ ESTAeLisMEO X

OIESEL GENERATOR A 4

f

-4393 I5L_

EN LF All "

$gggy gg 39

\\

(ERI RUTO i'

I

\\

DIESEL GEN. START SIGNAL ll1 l

1 m

A HS-4395xsCRI Mv-4395 OPEN IFRll ff,

'MANURLNSIf)RTg S.S.W. BACM UP TO i!

S.S.W. FLOW TO AUI.

A UPPLY FW RLTERNRIE SUPPLY

$HEET 9R I

i

'b st jj 1980N$N Nn!iOnil0N TEXAS UTILITIES SERylCES INC.

JOB NO. 2323 AGENT FOR DALLAS POWER & LIGHT ConPANY SMETCH NO f

FMt_a_% %

TEXAS ELECTRIC SERVICE COMPANY XB-2323-1800 TEXAS POWER & LIGHT COMPANY

~~

FIRE PROTECTION ANALYSIS

~

SHEET N0.328 0F 15 a

Nt 0 1

Issued FOR SHUTDOWN LOGIC DIAGRAMS m.

l

."$' sac ncce eran

'558 naqs.a.

, omic

o. c o.

.s 6

y.7 m u m a mte m t G ! n @ t fd d M Q i $ if y l

I E

E E

E E

M M

g

fI

{"$l"$l"0""

CHILLED WATER SYSTEM AR HSB.HSD 4 CSD y

H5-6700 x '

N CONTROL ft00M (MANURL START)

ROOM COOLING PAN $

N CONTROL ROOM IAUTO STARTB s

)

MS-6700 's ft$-5684 RI N EL. 810 *-0" -_

HS-56BO,Bl 's 4 CR.

s t

N II l G 4 A.C. POWER.

( ELECTRICAL TR.-A-j E

A.C. MODE 10 i

L

/

y i

\\ 00M COOLED SMEET 15C

{

kMILLEOWATER INUCLEARI

[1R."A*ELECTRICALOIL}

FAN

%r QECIRC.PUMPSTART Q {7 l'

[.

\\ A.C. POWER h

A.C. NODE 12

\\AUI. FM. PP ROOM 1R

  • R*

y

/

/

f AN C Mll SMi. 9A f

SMEET I5C M

m 7

0.C. POWER "

I p

\\ CCW. PP ROOM

\\gg

.g.

2 FROM SMEET \\ CCN VALVE OPEN. '

/

g

/$Nj.

UNIT itg IIA

/. lCC-ZO3$ 153(MANOALj

'3 l

r

\\CENTRif. CMG. PP N.

MS-I LOCAL (MANUAL.$1 ARip

/ 00M FAN C0ll UNI SMI. 6

$E-03 s

)

LOCAL (AUT0-STARTI NUCLE AR CMILLEO T

\\ RHR PP 800" 1R A-

]

FAN UNji WATER $YSTEM

}

f

$Mi, 38 L

t k

f 3 s

1 N

y

}j iss0NNO EN!iNiil0N TEXRS UTILITIES SERVICES INC.

JOB NO. 2323 i

AGENT FOR DALLAS POWER & LlGHT COMPANY SKETCH NO.

  • _ !j f**e._a fallLh TEXAS ELECTRIC SERVICE COMPANY x0 2323 1800 k

TEXAS POWER & LIGHT COMPANY

$ MEET Is0. I3 of 15 d

h n

J ut o F IRE PROTELT10N ANALT$Is Issuf D FOR SHUTDOWN LOGIC DIRGRAMS

7l onia l o. lce=s.f.'.*iac larcafauctran{steclr.s.

J08 no.Il-2323-025

(

17 P g',

l n.,--

-v e iiih_.m.armtf;Mit=n

l) j 3

5 2

0 a

8 3

0 n

o 2

8 fo 01 m

N H

i 3

an O

H2 C3 i

T2 W

N n

E.

i B

Kg r

A m

O Sg M

u J

s s

t nn Sa o.

t m

{

d C

Y N

YN a

Y NA si.

L.

AP N

I A

S N

P M S

MO o

P M

n M

A E

OC O R

s u

.o a

C C

s I

E C G

o u

1 j

a i

e 1

V T C A

c5 T

s R

HI H D

I n u t i E nGV G i

t t

s$ s=

S0I R t

o 8

I C

g M

F LE L S

I tt n

S G

T o i

[

EN C

O L

I E L

N/

If cRI R T aER O

E N

I ry WT W W

t L

OC O

O

,J I

PE P D

u T

L o,

U SE S U

F T

A A

H S

L S X

S R

L A E

[(

AX X

T DE e

E 1

ie T

d S

n E

o I

n i

R o

n A

s O

n I

i

[

L n

["

d e

I

'c X

a 8L U

i 0

A m

g 5

l i

H

_ =.

g I

u E

Tj

)j U

p D

R

~

O o

Tj }) T>

g, T

s s

ni ni A

@"2 en ta R

f e

tn Fn E

a7 i

si Si N

c" us Ns v

n A

E o

a' t

ni na G

e tN Is s

if is a

,i W,

sI L

S

.e

.r go n

n E

uj o"

o. u
o. u S

n i

,t

,u lj i!

rr Fr E

,n nj tA I

m

,i r"

a$

D l$

)

3 o3 t"

((

[(

V s

3 La

(( [( ((

N n

A o

f N

0 o

l t

i u

C s

E J

9J mv av s

T I

One RI E

F

,J i

J mV c.

r c

_~

e tr, no t

i f

t s

t t

s s

c u.

u e

n u

n o

u.

J t

u u

o A

a R

n n

i n -

s n

N e

a D

s t

m m

o t

L L

c n

n t

c a

a n

s K

n n

u t n s-t a

o a no -

o n

t t

n T

t c

n c

d c.

n 0

c a

a l nn tn nn a

s a

to i ao To i

n a

c t

s t

i w

v e

n t

n o

o a

t n

t w

a v s a

v t

y t

E v

c t

n o

o o

t t

t $

t t

t !

s o S to so o

I i

i u

tT t1 t

t i oi !

ui oi a

ns o

E w

v c

n '

an n

t h

r t

t w

nn T

n o

u a

o.

nT m

i

[n $o o

nR a8 a a

ao uo n

m uo M

h }$

s n

n s

gA c8 c

. c nc ac a

t

- i )

l c d'

{

E t

u oT o3 o u

o" i ac p

t$ t5

- ~a lS J$

H 1{

[

D n

11 1{

E u

\\ \\

N N N N l

h o

sM\\

N N

ra

\\ h N

\\ h N N \\

l s

N o

\\

N \\

N N \\

s

\\ \\

a a

a 8

R A

C 5

ss ss \\

ly

\\

S ss 7t 7o P % $

?

7o 1!

sn sT 9!9 4

u u

st sa su hx ib' I[

6!E D

8 su t

n 8

i a

5!s 8

ns s

j i-(

l s

l nx h

Ink s

H d" s

s S

s n

C.

}

l b

s l l g h h j] } ]

j j ld }

q i

4

$,9 '

]

i'

)1 1

l

8 f l

l

.9 h.=0 es

k. :,,

o ni

~m

=

o-es d y il 5

o

=6 E

~6 E

& % *s E

~

me O-Y-T

} T_J T_f H :"

j 5

a 5

o

=-

=

z YT 1

e o,

s n

+

a i

1 r

a t

2 d

>g

?

is z

E a. e,z o <

a o o o n 3 ce gg s

E e

E 0 5"E Fl Fl Fl Fl T-w o

o w

1" 11.-I1' 1 h,-'1 1 1 ',

[;e.

M E M E o;;

h E i M '

a m

z m

m.

5, 7'.

37' p

7'.

g,

./,)

5i 7'l 2'.

dJ 1

aw-u W

a o a

~-

of

=/

g",

=

=

-o

.o e

wo ma ao wo zu ma so

.o CE 20 do u-wa*u*

i my d

~U 00 dE OM 00 WN 3

ON wo m-

""25e o

'o 9

'a c

4 d

=X T-4d J

s 40 6"

id 20 2"

20 2d id 20 e.

e-

="

3 50Y I

a 8

$._ L, 2C. L ELR E_. L F.'

L L

Q O

Aw'

  • ==

a o

+

3 ow 3

h

\\

g $,w k.

..At e

..At r

3 x

aw-e gg a

g wwwww 88888 we 88888 we

-s

=

1

-a zzzzz GERG h

j g

3 E E 000C0 C0C00 IIll}

.E "t"

il a

l i

~h, f.

N -~

g-y c

l 78 3'l i

v ::

g 4.,

i J

_iiiiF.

i t

t i

io u i o o n on,

4 w;

3_

Fl t

pL E

e e

e e

e e

e e

s E f E

E !

E E f 6 5 E f

~

E c

c h t h t h c

d e c h

,c b

/.

/

/. $.

8 b (a 4

/

/

xm /

/

/

/

. /

b=

=

/

/ /-

,n

=

=

- m-C-

y o~

ma m-m,-

m.

- m-W gw ge g

g go

  1. C A-w We W

E a'

m me ao ao

~c 2M Q6 wE WQ 9W W@

y p

p a-

-s a.nJ C a-n,,,

,=

taJ O 8W C

.o C

e==

,dI" nsJ tC thf OA CW ge,g I

/T' C 6sJ QL tbJ

  • a C

g **

C nnJ~

~

a O

b

^

W W

g g

su.

y W

-g:o.

i l

l 4

j

~

a mi oo so o

m.

og oo

- 5;

-a 2,

-aj

==

az a1 22 c-vu w

c-vu w

j d

c ou

= El dE W

E W

w ao 3G 4G 3C 43 88 88 00 G' 00 5

M b

5

_L

_3 l

.J I,

ill I

I I'll 5

l

Z 7

  • M d$

2 ze z 43 p

zg e a. E E ci

%i m

.E,

1: 8

.a m

=

z e

w w

aw o c

w a

u u

o Q

42 w

-u, e

a cc r

r "o"

d I,_L w!o"3;5-u.

p 8

o o

m u

a 1

m o

w n.e w W e, w o

=

a I

w c

w u,

o q

uo E

Na

~o w

a 9.A

-w e.o,

ma

.m. W ue e

a

-o W

. a

,ye

. o, zw z

o-o-

oug 2

g-se u.

a cW

e. w g

n "a

W

?

d u

o ew

~

e@,

s e

E a

u jhW

?.

)

C w

U ow" l

g i

S I,'

Eo

=

n i

e s,J

[

t.

.y e,

w taf G

^

4.

I n

u W,

'E W. l h,

\\\\

wo 2o

,i

)

2 '

, /

VC

/

,1, e

7, o-9.:.

J, 7-2/

w-

.E

,a

~

' LE

~,e ma

.E

=o E

~a

-o

,- e s.

s e

=m as s,

s ek em u.

o o-o o

o e.-

- o.,e n o.,a 3

e ea Z-ea e _s 3

CW E

CW cn 3I EW G

CW dy e,E E

e Es e e

m e

O b'

b b.

O b

C M

M S

f*

=

3o S

5 33o..

P.

W M

==

m WM-M

=

m Mmm m

m w

w ww w

www w

w w

w www w

w e

e a

o ao o

ooo o o

a o ooo o o

o o

ao o

ooo o o

o o ooo o o

=

a 2

2 22 2

222 2

2 2

E EEZ 2

E E

b 2

o u

u uu u

uuu u u

u o ovu u u

C E

M 4

EC C

EGE G

G E

E ESC C

4 S

o o

.o o o o

o o

o o

oo o

o_ o o

.o Q

.]

e t,

r

~j,

y i

.w

,. wa wa s

.w

.w

.w

.w

.w

..w

.w

.w Tw a

-a

-a na ma

~a

~

~a sa OC D dD (D

C E)

O (D CO ID E OC ID 4D CQ in E3 De m

WG bea E

).s 4 WE a4 lad C had C WG WG lad C WE wE

~$

~$

~$

~$

~$

~$

~$

b UE UG WE WE WE WE WC UE US WM WE JE w

u>

u>

v>

u>

UD um UD UD u>

u>

u>

u>

k kk n

o n

n o

o o

g 1

a o

i,

, o i

o 3

E.

5

"' E E

'E 1

E, E,

E.

E E

5

-SM 8@

w

'i

m. @W

.w

~.w

~.w f

~w o,,,

n. @

~.@

.w t@

~m

-O mo no No No No so so so e

.O a3 na n.a Da D.a ID.o ID a ID e D.a Da

- o.a

-o

-o had W haJ W l*8 W laa W had W

.a Da D.a W a.

h.

h,ad W l.a.s W l.ae W a

had W u

=

u aW had W l

h

.O N

N E

E EO E

E Wb b

_E _b -

N-.

.E__

O.s

,s W

e5

/N

/s

/N g

m

~

m.

O se y s OS Me ma me

==

me aw-aw-

-a

=

MM M

w-d*

d>

d*

O DE O O.

DE DE DE ee est C ee me O

O N

O l

= n a,

m = = =

===_.=_==n_

m m

=,.,,,,....

i N

m

3 5

1 2

0

~

3 0

F 2

5 0

O1 C

N-S 3

I O

H2 C3 O

N T2 N

E-T B

KB E

O SX E

H J

S 5

2 0

3 2

3 C

Y 2

N Y N Y

NA I

N I

RP I

A S

P M P

O S

MO N

N M

A E

OC O R

B C

C C

G O I

E J

V T C R

T I

R Hl H D

ER G y G

SO I R I

C F LE L I

S ST G

4 O

EN C

I E L

G RI R T AER E

N I

WT W W

L OC O O

PE P D

I D'

T L

)

)

T U

SE S U

5 A

A H

1, S

L S o

X S

R L A

?

E E

i RX D

X DE T

o g

?

E T

s T

C c

i a

A a

M N

O I

T h

=

eg' R

n i

M_

T 8

b N

h__ -

B 8

a R

A A5 la a

T T

M

. n H

3

'l h/

I3 E1 0

)

D 8

B O.

9 A

A 3

NT 1

H

's C$

D i

R H

T T

N

?

M S

s H

i is S

a v

}

M F

}

t n

a o

un r

u o

F o

t t

u i

s c

s r

i

}

i b

b i

c

)-

n S

S i

r A

R a

A R

i

'J

'd t

l

,(

n a'

1 T

T I

i M

H H

E 5

S S

S r

. n r.

N M

r

~.

i

)

cu e

\\f a

n 5

3 A

u E9 cu E

D D

k.

a O

T c

N H

r 9

)

T$

a C

Sf t

u R

X i

7

?

NV i

N "n

G n

s i

i a

a e

M N

}

}

}

}

r

{

c o p ru n

f ao

'r

'r 7"

a b

h h

5 R

S A

f t

i i

i f

i 1

T T

i 1

T j

i H

M H

u H

n H

s s

S s

i)

=,-, ~

e I"

s it

~

! '1 ATTACHMENT 2 FIELO CONTROL ROOM (CR) t9 i9 h

tac"L _ _ _ _ _ 1_

_ ]. _ n G Imottaron j

+

T A ANSMI T TE R Ell 4

g

  • 3

,4 l w-20 na g

a l

J*

l b

( J Imaicat0R LEGEND g

l 3

5 Eo "

HOT SHUTDOWN g

PS - POWER SUPPLY PANEL (MSP) 1 l

t l

recunE 1980 4 id ifl0N TEXAS UTILITIES SERylCES INC.

JOB N0. 2323

-d acENT r0n DALL9S POWER & LIGHT COMPANY l

% S_18&%

TEXAS ELECTRIC SERVICE COMPANY d

~ %%"""""

TEXAS POWER 4 LIGHT COMPANY I

rIGURE NO. I JOS N0. 81-2323-025 cacarious.aws se f'

s b e n

s. _,
1

. m,. __ __

~

m RiiRCMM(%1 3 CASE I FIELD CONTROL ROOH (CRI J

O f

}

PS i

I

$]

l 1/E g

-_______.A_

_ T _ V,ianica'oa j

4 IMANSMITTER

' a

! 'q I

I EC On 4

i rs 1

2 I

I W

_____L____ _ _ _ _. A lNDICATOH k

inANSMITTER 73 LEGEND

+ - EX35fl"G HOT SHUTDOWN

+ + - ROCED FANEL t HSPI_

2 PS - POWER SUPPLY i

d ricune a b

1980 N i dil0N TEXAS UTILI!!ES SERVICES INC.

JOB NO. 2323 RGEdi FOR J

DALLAS POWER & LIGHT COMPANY

$l_ic__e _a H_aLh TEXAS ELECTRIC SERV!CE COMPANY

" h """*"

TEXAS POWER 4 LIGHT COMPANY rIcunt No. 2 as camam JOB NO.ll-2323-025

+

f 6

,. s

NY.

nn.....

-.n-..

w.

b

.,n

~

-~^=**'M**"

^

^^~M"**'

          • *MC' mus unut e

amm uma amm sums uma seus num mes suum uma mas uma aus uma

-n-I RTTACnnt%1 4 lf FIELD C0:! TROL ROOM ICA CASE 2 1

.J PS 5

I J

t/E PIO l

.-___--___-__u______

b j

1 v.,,,,,,,,o, i

j TER gjg l

(

- - -.s

)

9 RELAY Es WIRING l

I i

l I

t t.

_-_---_1____

sn l g FlhAL LOCAL /P(nOft

__yST.ATION SCL. $.s.

q CONTROL ELEntmi LEGEND 3/E PS

. - EXISilNO g

++ - Rooto SNUTOOWN TRANSFER PS - POWER $UPPLY l-PANEL ISTPI HOT SHUTDOWN fg PANEL (HSP) lJ FlcuRt 3 1980 N i dil0N TEXAS UTILITIES SERVICES INC.

JOB NO. 2323 AGENT FOR iI 0ALLAS POWER & LIGHT COMPANY

$ *8 _a M.l* %

TEXHS ELECTRIC SERVICE COMPANY 3

l8 TEXAS POWER 4 LIGHT COMPANY

g rIGURE No. S 5

H)8 NO.it-2323-025 N8<mS W8 e en Y,7..

., _ _ _. ~

.y.

g

-- A = ~#snem'M R~

=

4 i

g-cri nJ

.w Or) n c5*

O E

z g

=

e=

O j

$ *c O

[

E MW m

za

~

r 2

- G E W r

o 2 {

u g-s O

m z

>ZG$>

S E

~

h a

b

-~]

$$'E d

z w w l

1

[

O E

I l

l l

8 i

-,,, ';"Na 3

I

$.5,e" u "

l I

a l

l lE *

"$k I

2 1

l l

J ou o

I i

  • I-q*

3 mdI y'

sw l

e "e a ci.

i

  1. %g

~1 r

og w

l i

L_..

l I

I l

w l

l E

d E

[

I-I E '7,

.a l

v E

I I

I A I g

I l

z a

i g$

(

I g

_.__,I E

e g xi,i E

lili

_ _I _ _ _

i o

.J a

l l

E 5

EE

'h' 2

l l

l

==

87 z

e k,

i l

l o

E **

u i

l le a?

~v I

I l?

3 I

r

.- _. a ;

=

l

'* 33 31 l

f I t ~ 1*.::

Eg I

e UN l

l 5

l l

Q l

I I

g i

l I

'is i

I I

l l

5 i

m.y I

ll

_L.. -

E l

l 4

g I

5 l

l l

l l

I Ei l

I

=

__________a Oa N

4

$i 2 a

~

  • - o e

" EI T 0000 5...

s..O I,

Cf II t E7 w *t ur, w1 m m acre w tr-w w== m M

m 1s in in le 1

I 7:

i I

m m

M w

q

-4 1

- T,~4.:m o

=

55 7

z 3

?

2??A g

' ; :gg::,

g y,,

5m l

w; -

a m

z

.et Ea o'I {

l 8

ou o

..a ye g

-r I

(J w

. -j~,g

t g

gg, z

z em iE 5 E 1~1 i

5 I

m z

ee

E E a l

ou5

'7 e O'

"w

'"a

~:

u u,.

f 1

s":

a a

m i

l Mgea5 Et y;

I

=

l g

-aw-0=*$,

T3 l

l

-se 5

i 44 rw Cawc a

I l

50

! u4

~

'"g e

a i

e t -

g g w "e l

2 i

i l

s l

I l

l m

s m

+

4 l

i

  1. "w e

I i

O w

w ow Q

i I

l 1

I g

i 2

I I

l I

53 aI l

r I

l I

M"

.Sj ?

b.

8 l

l I

  • 2 i

i e;

hpii e

e i

i i

  • p V8 e

c 8

v0 el e

I l

I gl_

z I

c 3

i is.

i._

I i

las I

w z

I dj "c @

l l

  • g I

E, i

+5 5 d I

a z

E I

O E

I g

E l

5 I

I I

E s

=

i i

i i

E I

I i

1 1

1 6

1 I

I k.

I i

i l

I l

l l

l 1

I i

i I

l I

a o

g aW I

I I

t ya I

goe r------

J

85

?

r gwa s

\\

U+*U f

y il "5

m== num m m m m

-s rus rus

-m m

m -: m m m 3 :s raux~+=

m i

N

\\

m l

N

?

z o

3 3'

  1. 5*

g, E

ds

=s.:

t:"

yw af a~a d

8a; 4

m o,

_e G u*

ue z

+

x r u

9 b $

E kb$

(

E

~I l

E 15' e

d O

gui I

e z

u w

I ll c

-u-o a.

z m

zz i

gggg g

-"*g E

i I

m-I I

$="u-1 l

CE$55 x

a au I

l o

aw a-a 1

I m

mw m

"eg I

l m

ggw I

e y

i I

x ow-w 1

I 1

I I

I 5

Ti i

i i

g *,

el

, ~. ]

v I

I

.$l l 1

zo l

I

  • 2 i

.s i

o a.

c a,,

I e

u.

a o

a

==

2 I

I E

V8 e'

1 l

x 3

y;;;

ea o

w

=

1,:,

@j""

i v'

gr.

m e,-

l l

  • iC
  • 72

$ N 2

5

  1. T-M?h

$ d

-=

0 2

I o a a.

f h

I o

.w I

..4

~.

l.

..y 1

4...

l

- 1 l

a

' J. ~ 1) l l

I I

E 7--_.-a B

1 l

0 a

~

e b

A

.b O

_=

M e.J 9 8a g

y,,.

5**0 i

1 l

  • ' n r r r m yri y,

m w e er w,,,

y y

n 1

1

j erra u ac e i s.

S r 1..r i, r,,

,. r,

.r

.r -,

r, c,,-,

i

.i,,,,,

S

= = === = E=mr hthMW

-rd h4 bihtht 3

1 95 %~

_i-j 4%TYP)

  1. l I

g 6 %[(T YP)g.__ M I

t 6

11 16 21 26 31 36 41 46 iil d

{ h f 42 47-n 2

7 l12 17 22 f

ll'l 7

h 33 h _43 5' jl 3

8 13 18 28 b

9

.s i

___3h

,l y

f10l,_15 h]

"-~

I l

20 25 30 35 40

~

~

00 e

I

1 6ARRIER

{

l'3

=

2 3

k n

i j

nf C 1-d FRONT VIEW-DOOR 5 REMCVED d

SHUT DOWN TRANSFER PANEL d

= ~ ~ " "

cr so u-,,,~.......

e e

i s..

- -~ ~:,,= g ;'- ",-

""7=:~:.e.nn-n-mi

g, i'

[]

{.

!)

.\\

h

-~ ~- --- ~~ ~ ~** $

/

E E

Anaurcar 9 j

1 e., a.

CR Y

Y

]

I A

l A

l A

l HSP l

l l

l 8

I L_

L -. -

L -. -

STP q

I I

I su I

I FC PV 4252 l l

J M.C.

l

'1 A

i M'

EMERLENCY DIESEL l

GEN.*R*

r

.I E.D.

D IL ET.

,g

$$u.pr.eg

' CENIlrUGAL LEGEND:

gn, g CMG..*Pa t My.4395 M.0.-MANUAL OPEN p

u l

TO RUX.

  • ~~

l CCW 9

l FDWTR NY l"'"

t e

u

.,e 10 015CM. CANAL t

ssN SYSTEM in-Cn ring i,

f ise0$$$ NN!raLtirlow TEXRS UTILITIES SERVICES INC.

JOB NO. 2323 AGENT FOR 9

p DALLAS POWER & LIGHT COMPANY i

MINI P 4 10

@*** aLH$h TEXAS ELECTRIC SERVICE COMPANY gg rintrsoracijona=austs TEXAS POWER & LIGHT COMPANY

{

a

  • f' na

$ MEET NO.

'57 tl' om o.

c o.

ac.u aaan rac e.e.

assuto FOR SW SYSTEM CR FIRE l

JOB NO.ti-2323-025 meaeres taoenessas.asas y (

++e-6 (byp

,CN

.....w m

m m

W W

W W

M

m a

1 E, a v e.

3 ea as ns ri ns

,, s

,a l{

CR

,3

\\

l I

8 l

l l

\\

l I

3 l

l HSP

\\

I l

I l 9 l

\\ L

[

ns ns es j h.a STP

\\

8 W

l l

r ik l

l s

i i

i

,s l"

rc l l

l l

l l$

PV 4250 i

~

l l

l l

. I l

I 13 I

l I

I b

.$si l

EMERCENCY 3

ole 5EL GEN.*A*

E.D.

OILEA l

SSW PPal

'CENilFUCAL LEGENDS l

TR.*A*

CMG.PPWI My.4395 M.0.-MANUAL OPEN M.C.-MANUA CLOSE CC" 10 Aux.

r0NTR I

N T CCu 10 DISCN. CANAL SSH SYSTEM g

IB-HSP FIRE 1980 Ni Afl0N TEXAS UTILITIES SERVICES INC.

JOB NO. 2323 iW AcENT FOR DALLAS POWER & LIGHT COMPANY MINI P & 10 i

hayA)ne, TEXAS ELECTSIC SERVICE COMPANY IB 5I a

ugs no rine enorection aman sis TEXAS POWER 4 LIGHT COMPANY snEET No.

d E

N

c

"' t" *(" a" ("t ".e.

Issuto F0n SW SYSTEM CR FIRE JOB NO.ll-2323-02s 8s'mos cease, eses. asis ae

~

p,kh' -

r,A 4

iP z

=

x

i 4

m nW N

E m

o i

t ra 4

N

~

ou sa a

w g

3%

1 u

e o

a. -

==

Z i

i, u,

5 11

=

~

8 O dd 5

m

~

5 44 O

O 7

Ji o

o e=

e u

z

-2>

m.e 24 v

Z C Q. g gg M

o 1 ;

w 0

u "o

5

?

w u l

g E"r w

a e

I wgaa>u e

~

i sq g _, g 4

g m

u

- - -- _ _ _ g L

oo C

wz w u, w

oz z

-o

$ E"g M

e WA g

taJ

].

5 N" O*

N, "D

2 M

![

a y

gwO e-o a

Q.

2 4

i MM

>=

,J 3h O

M LJ

.s e

r, g

a o

M-m

_, m G

4C*

l

.\\..

cxW x

W QW y

N 8

3 Vs.

A 8&.s l

E,,'.

4 d5 C':

E Tod d 3?

"g" I,

o.

w t._o u m j

1 h3 l

^ ' '

sql

a. =

-1 g

I Y8 sh 3y 3

YC.

o o

N w.)

g g

u;

~.,.

I h

"2 in e

N E b"

v. -

g,

-h '

I 15 g

g C

a

.w p

f Y h*

E e

5 N

u

?

a

._ _. Z~

y f

A 3

, ~_-

w r

4 9'

W a

o db 72 j2-m a-a.

M g

v r

o I

r.,....,_,________,._.,,,,,

1

.e_ -, _.

.e%e, m.m-e.,

e-e-.4+-+-mee.

h-N,-me-

- =

ee i

5*

i 4

E 6

I l

(

i

+

g

. : r n - _.

l l

ili,! !

8

! l I

j is" I

a a

N a-p e ji g_

s

.i

/

k. i. i(

@@s - !4 l!

l l

y O~n T l l 8

"_t,

{

l'( ; ~

.,1)

I p.

r,

. is h

lH 1

l i

f.

g_

s

=

R $..

[^^~

qi)

A 14 n.

@e@s s

-

s g p s 1 Q w e-J 'I 'I G w i e c o H ~g e s-s ,; p g. p t-y m i g s,- -.- l , si se .1 'i s _g D_ , h { w g _ ~ - om g 9 -w u C. ss 6 h, $ h p py. g i; r '(M [;l[. _ _g- @n ; r g g j._ _.,__ i j l (I ' ~_I f p., J g 4 _ _ - -_ mQ um h ~~ ~~ h I. _' -.}, o y a ++ s g-l ,2 4 ;!!.i!j;.j l i a m!!! 6 l" s.: 11 ~ 2 _ _1: i_______a ~%]'__.__ 1 s /,T\\ d k W f w ::., e s,______g i gy_________ l g ____=__ I l @--h--------- Mid t l 1 l h....;; c _____________.,i @. __<______,__L lI == l 3 ll h O-~----- =[ a @,,, g i j s. M L1 g s, l -,.s __r1 e _ ar e ' -- - n----. - _= -r _ m n. _a t s s. iw m m e, M Q ~ ..O. s %y;77;.m-P R' n a o

a. m s.n. :;;

} 58 z i n. = 1 p OU D em ,1.<'. oo a = . /W %g

f. r....{ l,.o

=> 7 = y WTJc (?;.. 25 11

:w-N e,,

3 1.. y ,a

t i-35 5
RP

" *= "= ~ %'A ,. a e ("::f 3 5 C $8% 5 E $- u o 'T" 2.9 r;.:t m ! i ;O s -W I (?- E.x msemns 13 m. o m x,mi m o. -= mi 4 md 5*sB o= D-X i s, a.. _ a m E

s aw t;

}4 e c $ y "- ll '. n m g, e EO ON 'y 3_____/. _ _ _ _._ q. re -I D.02. g v er. .'s q. m 1 g ~ e, O O i r t- ~ E l8=

g. L__ g :

0-X is ) si 3 &c'\\ L' t 2.

  • 2 r

Iji l E i rr-(} g f r:..e!, 3 3 a vs m:lo. un =~ ~ 32

p _

_ _J ,l "A o g ~ i a. _.n a. e t a a e -P= = -P s : E l +5! !! $.5 +d! 4 $ !,( I == = = QQ> QQ> o e=aa. e={. j2 3

;. L _ _ _.{ )

m a ~ i s - - - J I \\ 4 o i 1 ~ .e m. s i e e t ';- 21 1 ~ j ~ oo 'I i wm Ih 8 l +hb 1 ,[ i V va i u, n i a. Jb d w. y f e E E Y o e fa A A' W .I I l = _ = = _ _ en n= === m m, e,i - r, -s - i n n =>,= s 'g'- "9 O' ,-"*N. y f

    • gf-

7 ~ ~ ' ' ~ ts 2 of to l9 J in A AAA A A A A A i '3 l V WYW W WWW W CA i i r 1 s l I g n$P l l l T I I i 1 l l y lllM L M L NLD '3 v v v v l ,,P l I l l l l [3 l 2 {T6kOT l 1

I I. i I

I ( 8 1 l $ TOM. LT l l 1 l l 0 "L""l 1 a i, CENERATOM 2 d6 l 6.a e l FONTR PPs3 ny-24328 (3 V% 10

n..

->CONDE NSAT E ) ny-24918 ) <h NDEN$ ATE -[ srsiEn .f4 'f l.J N [] 45$f ha2 CL OR 3 ] rgw ./T: sTUR81NE ORivtN LEGEN3a ' AUX. FEEONATER PP (,j n.0. - MANUAL OPEN g stEnn n.C. - nANUAL CLOSE a CENERATOR 4 g S.G. INVENT 0RV CONTROL se-nsPrlE iw0%"I'30OU"IN!ililArlon TEXAS UTILITIES SERVICES INC. JOB NO. 2323 AGENT FOR DALLAS POWER & LIGHT COMPANY MINI P 4 ID jleteA_ HAM TEXAS ELECTRIC SERVICE COMPANY 38 TEXAS POWER & LIGHT COMPANY a nt T rine enortctio= amatists ~~ .d "j l me l o. lc-a. % nc l.ec.l.ucte.a lrtec lP.E. Issuf0 Fun SMUT 00WN LOGIC PIAGRAMS l xe No.u-23n o2s caa= <=ws.sws .r - Q' b '.i : .1_ _ r z - - r:-- nN **r r 1 ep 2e 9 t ,----___.----7.---- 0 (h 'Q Q 1 W f Y Y YY Y~~'-- CR i l l l 8 I \\ I I I I \\ 8 i l l l I I I I 8 I b IM [b I l /M i Ml I rt D Y I I ID D f l n$r t_ t-t t t ,-.3 j Zstr j na I I l R, l I I PT FT l 2457 l M l CSTOR. _ aq 1 2%54 ,e I l (.. ) b l I sfEAM FT .1, s GE86ERATOR 3 2sE6 89 [.) ~* a6 g a e i E A I y3 Mv-24 M4

f3 N

I rowiR ers2 V i TO bl* ]

n..

W ONDEN$ ATE ) SYSTEM PV-24548 MV -2495:A NDEN$ RTE

IT:

sV51EM l .-+x i 1 N O (.) ~ STEAM 3 O g* CEhERATOR I (-] l S$/ FONTR rr.sg 1

rT:

I bEbENO8 3 stuR81NE ORIVEN (,) M.0. - MANUAL OPEN ' Aux. FEEONATER PP l STEAM M.C. - MANuki CLOSE GENERATOR 2 f s.C. INVENf0RV CONTROL 3C - Sir flRE 1960 mI iTION TEXAS UTILITIES SERVICES INC. JOB NO. 2323' RGENT FOR DALLAS POWER & LIGHT COMPANY MINI P & 10 % * $M TEXAS ELECTRIC SERVICE COMPANY 3g TEXAS POWER 4 LIGHT COMPANY rine rnarectioN amatvsts } A e l issuto ran SHUTDOWN LOGIC DIAGRAMS l "fl anre j o.,c a.%:icl=c.htemlrtec {e.e. JCS NJ.ll-2323-02$ cases sus.aus a Q 1 a.s..... n M m m m m m m J 1 ~ E ) S S S S ~g, l ,s l. - l .s a m e ., m e 2m 2s2e Q p Q p 2$2i I I IMI l l l b as b "5 L' "5 b as , D,' ,I I i' i' I I 3 sir I l l;e-1s-10530]las-is-sosC] I i 1 l r----' l l I I i 1 1 I l I I I g r4 I I l 5 I g I kY l 2335A I l -2327, }5 $.v. l ,Mv-2335B I l g I,, [SG g l SC sei i 3 g y i i 6 7 l I PT PT l l Q j t I ~ i Li LT LT LT a l 52sr Sie 502F $02 501 50lf l L 33gg g f j5 5.v. l g,Mv-233tB l I I -2326 l I_;. i i [ p_ i,, d l'"' b

$!:,,,A

(

  • 1, i

v-2325 l l5 S.V. l " " 23338, I C m3 $C s, 7, g I 1 $.l3364 d Qp t. Pv-2328 l5 S.V. l& ny-2 W 2 b A IMS-t37 w ( Q y n.C

ggggno,

~~_ n.0-MA= A s q w24 au= ' a ru"" 1a b ,4,. ctosg 9 u Pv-Sl80 ,g SC BLOWDOWN DAAIN d $.C. PRES $URE CCNTROL WA-CR FIRE R TEXAS UTILITIES SERvlCES Iht. JOS NO. 2323 W N i kil0N ~ 1980 AC(NT FDA -_.-.-w---- 1W 3 __1-- r-k l J DALLAS POWER & LIGHT COMPANY MINI P & ID __ v__ l 4 _ _. _. _ L_7 {,m_a H6 hm TEXAS ELECTRIC SERVICE COMPANY 4A TEXAS POWER 4 LIGHT COMPANY Sngfl hD. ed 7-H 43- - 7ggg,g; ,g ec. 46r-r rc r. Issd: Fca CR F!rE SG. PRESS. ",7. oat ' o..

o. Ti,P a:

y .I I )g%MN[g, M[: I,). w-,g,,~y.- ~YY .=y' ' ~ ~ ~ ' ' ' ' __',h' M" '7/ j. A j^ *, ',f 'e. g g, m - l 2 ?".as m a Y. ~' a.. v1 ox a m g aa xx zu 2.. .00 3 4,*, 45 y g y ., ggf o

a.,

pf, 'kj ~* _, 12.,. e'. = e, y L __ _ _.._ a w EEE E. a U. M EEE I@J {[E q. z d IT tE O inf e ',,,9. 9 I 8r 0 3"E E r*a c_ __a =; xxx -w_ m w T.w, ~* 3 ,O "E MESEb U3 c m-o* I J y s-3,,,6 0,g*ga -a L-- _J o u, w m s i )- i E' "E5c$ c L 7 M- -. _ _#_ _,J A E 'I ~ 80 G . ;;j e c z a s o w ~ q ,e_ m a. ,f, N ev m .J in, 40 ~--- -- g [g gia = t g a O a ow p 6 6 - ~ __7 o ,,i S a m _g~. Me -u 3 g yg ggg N .g q N. 2, 2. E q(h> MEx o t i 5 E' 11 ll ri a .h, w.a, y s { _m _ QM N = m -i e e.. es. u -e ==e _m. 8'" g + e

  • E E

O. x b 8

3 0
,o o

t : t o g o z El g 3 l

s r,p e

k m = N f _q I

=

3-i l d m O e qs, m

j. 3 t

i I 4 Il

  • /

3 i t ~o l r L-.-... 4 so l.Ii O b a o g e-A A O s c e o "I

  • g t______________J I,

l g g g g g g g g g M M Y m_ _ x-.


._.--_-;.a.

. s y g_w -w m x, i y x --, ; - n n-w ~ = z_. a:l i= g s 2 di. e (.i ll f p i4 s !I 1 li ~ :T e. 't 1 's I v;i p [ g g,i ) et Aldk b ~ r 7 a:=:

n..

w I u ld4 3 ls) I te i a. jei i M .s-p ,l t4 ie l ':.3 m: P'

)

if, i

0 i

n SE 1 l I ~ d~3 k I t E: i ! A l g )q g3 . _ _ _., 1 r j' g.3 i ,,u__.._. _.i i i -8 w 'g. _ l _ _. ,l'---- !d l }; Q j. f l l'

o, L

- _1 i - q e,. l gg l l l .Q. s._. l 8 i jp l

g. _ _

i i .- n h--- -1_ .__...i------, I a! l i s l k-I SE I -., _ _. a i g @c-l ll ll l so i m i i i i i i i L t.

[

-.m:n l j i gi l l 'bl ' E h ihgf h;;y 1 I 1o h-(* I I [ ,, _1.@. - _ _ _ nj l j i t 18sti l 1 I -l E I E o a I ' - -( (-_ __.___a i d; g _ _, "i ..q _ _ _ _ _ _ _ _ ; e n,u ll,3 J 8 I I as ua a u. 2 r. m .,u m r T v N N C' 'N .. ~ ~ ~ ~ l ^"

+ l i lll 2 r E:> , Il j !* l l '!)) II. q j :' E A e!i$$ E 35 l - %e v h h-- l 1,ili g e r----- sil:n i 3, s, I l 5 !l ] l h 5,- !I!! ' t(l l x il

g. _ _

,t__ a,iq g!1_ 'i t g!1_ I! l I il q ! g!I 'i -__---d_J i gl. _l _ .____,;,u-I il'- -- d_ i i l'-- -- --C ] I l 'i ' - -C 3 ~ j g J m t ter I _n. gy }d l I e m l I h 1 -* 7 3 1 ~_:-C g!! _ , t l .g. i .e-y-.;. Q-

g. L _,t_

i gu_ g g j,L l__ __ _ _ _ _ _ g_ i !! = 5

g. g _ _.. _ _ _ _ _ _ _ _

.g i i il s -r g -@-e.__- .::-l e-l l IE g i i r i n! i i i 1 I i s-l I i h h gg ' \\ t l t u __m:g i i 4i l I 'i _.e,, igi ( f, ~ y ' l

g. _ _

1 J l t._.. $ n-s- ( l I @~ 0l --- - -[ h I l I I -I I i I t _ _( _ _< -_a l U E l n'e E 3 p _ _._ N, i l _ _ _ _ _ q, ; in E I t - srs - a*7 - a 1-ar a - ar9 - s:n --ers -m-- tim-ters-m am-w - m -

  • 23-D- M

'w ~ u.J. 'm . --. --------- - MM.s.

f. .- _!$.:sl fril ,qll ., p. .e 1 2 'h. n a ~

  • Q:!j g

5 I lIi 74 = th I ;. r i-a vt 51:!!!!!e-l k r----- 4 o I ilI: 1 8 ___________.Is,;l l o.g g,

g; i g,;

i 11 M b ft m: 9: J tg jj g ______,1 i ll 4 i l _ _ __ _ _ _,; l i __ /__3 u g,. i_ l 1gu_ _ _.r i 2 4 'l'-- - -E ] l (, i _-__,lu__._(___ _ g, , u __ _C ~i I 'N I ^ l qqt j _b:

g. _ _

____,l'---.

g..I _ _

i'---- -b: i ,h..l.,ii _ _ _ 3 ' - - ,E gl - - '~~- ~ ~' l l _ _ _ _ _ g 'l I 1 tt:!!; f W I li gl - - o, L _ _. __ _ _ _g_ l 3 n,.. ; .j l _g_

g. _ _

l d w-7 i i us 3

I' 1

G = n l g lI {

g. _ _

_ _ _ __ 3 l t I L- - a :a I I! l I Q S I I g.__ o . ? i 95 l 1 5,g T i es i i r.s I g F [ j l @--Gd ei l J i if ,f!3 I l l I I I I l ' _ _( .(..________.________._____; b !! h @-l -@t - - e:,. i

g. _gl _ _ _ _ _ _ _ _.qm j l

~.. t

f' ?< + t_ _ !i!!!OEn_4 !i!!"0ER ' A i,< /,,, F p,,,, ,7 AA ~' ,5 i 4 i,, in o

  • /" 8 " A.' " p,I W

';' g

  • l g9 NSP_ __

_ __ _ { __{_ t f F_ g __ t t t jg l l l on on oei sui l l ,s, i l l l , l l S E 'N 1 I l 1 I I i I l l l l l l ,lg ( j t t-g -i t i 1-f i t-j 1-t i

t. }

r-d Ej$ l ( I i l I i i l I l g l l l g f gl r-- J i l 1 i l l l l l !g l l r l I /l3 I l I r---- J l i I l 1 i l l l l l l i i il l l r - -- - - - - - - J l i J,E, gg tg , ; g l r e j"i s.ie i i .------J i i r l l Sc* '\\ 'l'~~~~~~ tg n h ( i Jl I i i i i H_ma==l !! ! [r J l l i k!. l l l I-I l n Il l'l @J' I I I l i I n Y lll rt l d l l l 7 I CvCS PCvid5C ,, -.I Y~~ l l l l l a l l g [, LE100uu i lRCPs2 l l tg i a RCrag ie e e a evt. esse l - RERCTO l !I i

N'j n ' t'f _.'*.Jr-. _J t 7

I y l III i l g r--, yll r,_ _a J l l g CvCs r Aur Spear 8305 l .) I r I l h e. RCPs CvCS 1 +2PflPHlg e a n*' j '" '"" ""iiilih ll $ j a 't i y I ) /"Gst4 l 5 t c 10 CvCS S Pngn ,7,f SE AL uATER i 3 g r FILTER j ( RCS PMS$uRE T L-____ h PRT CONTROL Scal 6A-CR FIM ,.i l iN fN i ifl0N TEXAS UTILITIES SERVICES INC. JOB NO. 2323 1960 00 lg RcENT FOR l, DALLAS POWER & LIGHT COMPANY MINI P & ID

gg esse a_H 4 %

TEXAS ELECTRIC SERVICE COMPANY 6A i l r,c I l TEXAS POWER & LIGHT COMPANY "[,'l oare l o. c,so. ist arca! extras etre P.t. IS$uf0 FOR 8 N O CSR C E JOB NO.ll-2323-025 casar, sus.aws --.m.--------- v r - ?-*** v g TAC $2%ENI$IbN N

K sf a o l its is it it i/I tt Pi sii sii en pu it. it if i,i sfi i, 3 ,p "5' T -t t t t t v t- -t t a ') - - t t t m eq l l 1 t._-, i mi l i i .ui i i c__J i g i I I I I I ai i l I I I I l l l 37, I i i t l t i i H l 9 y 4 I ) i Ir- ' l I l 1 I g g g g l l l 4gl a l r" l l ll r-- J l l I l l g i g l l l l ,'3 3 I ll l r---- J l l I l ~ l g l 5 l l l I il l l r-------- J l 1 1 ,rf, g g g l!l l l g i JM c> is i i i .------a i t, a i SC"3 i is e i r---- d i i i l )y l l [ u - _. - 3 i RCr:31 Il l I' _ j i /M sca: l i i i Idl u a si i i F_j j I l i l g ic_a I t_____ r, l ] y Qj l l l l N0ff e ii e i 8 l 1.lN$f RUMENTAiloss Y lll rg l l l -~- ll gk n$3ngg z m_2 PCv55$C (LE100NN CvC$ i gggl l [r RCPa2 l r,. ,PVC-is 558 ( l l t cs RCPws ie i e I i ~_, I l gl l r,_- _, _"; j i g l / r,J_ _ _j 3,C,V,CS g l l r - - .T. 4 g~-- I[l[ ggg 8105 l _____,jl e . cr g li: Il ] RCPsi CVCS b. t) I h L d' "" 1 I I/I { C C ~ gll INJ. 33$g $3$3 C a ( 1 i \\ uss J Q-){ bv .+ l to Cvts te ti us3 SEAL WATER l 459 R FILI (A jM RCS PRESS s INVENTORY l v , d' $$'af',g t______ l e scal f 19s055300 U"$N!i!ditton TEXRS UTILITIES SERVICES INC. JOB NO. 2323 gi DALLRS POWER & LIGHT COMPANY acENT FOR 1 @t-%Mb TEXAS ELECTRIC SERVICE COMPANY g d l l ~ ~ W. - " TEXAS POWER & LIGHT COMPANY cc i i j, l Daft0==. !cesa, sat necn '=uctran stet 'r,r. 155ufD F0n RCS PRESS s tuvENTORv p CONTROL CSA/CR flRE i JCB =0.18-2 323 025 canme/ous.aws .4 r . - -. - ~ _ _. h mamusewatufstrC?.MDM3152!%d

Im _ - ~, I l o m 1-1 i e: Jm m o_ m a I ,1 m Q

  • C C

C 2 v0 e l 1 t ),5g1 _ "2:~ !

a. ".

9 o _ary,z z k

=*~s

=y a 2.:5EA* lll g-o E r n g_._______________e, _:g g 3 2 d a W'a,:s M r 6 .z >=, ~._ =a M z ~ eE 4 l 8 e g&z w l 8"o 52 i . 5 u = ,_ U_ " n '4 i 5 y I y h.s E u_ => q e x: y, l i ua u 8u m s 1 g I g > M __. J l 3 l t 0;w }9

ja u

~Em~o, $$ o ,E i A A e T 1 ,J g* .s ou 2 ~ 'y e r =J' c se. i 1 6- = e,*,. m m. o r-i co ~

3 en w,

I E e i r-


:m e yjg 7 -

e n. 1<_._____J O o g *- 's L__L 9 1 o _5 ____e _ _ _ _., i ~ 8 ~ I ,II u. d.5 (I g i,1 aa s i ;; tt ea = n 1 s.. l _ _ _ ; _ _.,, i u __ .q_v:.:: e. g v, 1

== 22 ,g ,n, = o no ,i' %~I p F i i i ,s A Gi 3 i OM '~ E n

h. __

i i ~ 4,, )_ _., + a n ,e I i _m, L_ =. y i o u_ oo, l, o o, j o. _, i y i ,i, r os i _ 3+ \\ apy ~ ) <__[ _ _ = =. __l =% I I Wa -= a, i ~ l ~ ~ J g y l<_____J i )gc._ L_______7-- J 6_ g i 1o 1 j- )3

ja C

i J l 1-1 r-Y y___ ____J g Y i l

  • e

~i.-- 1 l GM P tf 6919-f / I r 1 l g DD a _s ]~ I i 6 es -u-oo t _. _ _ _ _ ; FM = 3sn -t/ 8 _ y 1 1 s $5 a s l 5 a-- u-e r-e- w u

r - 12 4 su n.1 u..

e r, n c.a u a a i

I CR S + + + + + sn 7 3o + l I I I l l l l 1 i i i l i "5 I I I I I I I I I I I I I l l 1 I I I I i i l i I I M$r g g g g g g g g g g g g _4 i i l l I I I I l l I g Sir g g g g g g g g g g i t -f i i i t t t i t i L OC AL MS - i AREA l x 5000 5e00 56G2 5802 5668 5666 5676 5676 5665 56ew 5684 56es Sw 3375 5691 5 1 5691 5691 5691 5691 5691 569) 5691 5691 " g l BY ____l \\ / g i vtNDOR

g I

l l l l [ L_. - _ _ __ __,_ I I L___~_-- q----~~'g I I \\ I [

L___,

ll l l l l ll E CHILLED WATER) ! ~'~~~~~' J $ URGE TK j l lg ---~~~7 l 8 I gi k. I 1L--~~--~7 g g DAY IM I I I I ROON FAN ,1, sus a p l q i n l EVAr0RATOR f h E L

  • 7 I!

ROOM F ANS s, I h kh f o. 2 ll c _,j o 1 CCW- / I* i* iE "O 5" EE Il l 9r CONDEN$ER g; w; <3 FyEL Olt sa j f,5 ti {n r* ad TRANSFER r0 JL o ". +_ NATER CMILLER 3

z..

',; S ,. i e E" g wo wu ,)

  • ' j ' 8 NuC.$kFE11
    • d Jd g

m 097 !l pp RELATED 0, 58

o u=f oM o r'M yl o

o J a a._ j CHILLED PATER SYSTEM OIESEL GEN *A* ROOn c c4..r.a$ ( DIE 5EL GENERATOR $ CMILLED WATER 7A.CR flRE I' RECIRC.rr a670: DIESEL CEN. AREA TR *A* I h ise0Y2Y NN!ikd4 TION TExRS UTILITIES SERvlCES INC. JOB NO. 2323 r

+-

AGENT FOR fg -tfl 1-- [ DALL AS POWER & LIGHT CORPANY -- t l j i 24K AMar._hw TEXAS ELECTRIC SERV 1CE COMPANY HINI P & ID 7A f i " "".".*A ~ '** TEXAS POWER & LIGHT COMPANY 5 MEET es0. O y 7,c f '52' we.c..c o. h .u..c..,at.. g g o gy E; gigEM,[p. 355a0,en g ,s. c.,,. . m q_ _ _ _ L ^ ~ ~]?h h' E O n it b' mum ums

.-o--M 19 'F C3 ~ sy @.

  • l l

- l l I I 1 - ![ M i l I I l

  • B ^+'

l l l l l l l l l l l l L OC AL H5 MS ~ M5 91 5694 5691 5g1 Spa 569: 569: x 5800 5600 5302 5802 5668 5666 5676 5676 56e4 560s $6ee Ste. Sw 3M5 5691 5691 ARER l } 7 \\ / 8"7 - ~ ~' I [_a _ r r r r _ _,, ( ( g 3 g g N I 'E"D " l i g j i i ~'~~~~~' I ~~~' ! I l Il ) ChlLLED WATE 7 l SURGE in l' l l t I I I (, l ', IL_-__ DAY in li l l

  • " ' a"

' ' r "' 1 l i i r. EVAPORATOR

  • I I!

ROOM F AN$ E L I h hh I~ I I !* t ll a, e,g FUCL OIL I TARN 5f(R PP 1r CONDLN$tR ad ~= xz a= U*~ WATER CHILLER 2" I U 78 l 6 n J +- g g NuC.SAF E T T id Jd ,d 'S .f E e a,, l RELATED OS f,S (3 ,,f g .y._7 gajg va ) t ott$tt sta -A' d CHILLED WTR. SYSTEM RdOq yLA,61C$t L GETNC#5 DIESEL GEN. AREA i CntLLED WATER d RECIRC.rr as701 TR *A* HSP FIRE l il g l i i 1 I I 1980sNN"oEIw!ikdRitoN TEXAS UTILITIES SERvlCES INC. JOB NO. 2323 l : t l l ActwT roR i ljQ __! j DALLAS POWER & LIGHT COMPANY I i U _I_j l_ P* a H(he; TEXAS ELECTRIC SERvlCE COMPANY i i I 1 I ! l TEXAS POWER 4 LIGHT COMPANY SMEET NO. { CHILLED WATER SYSTEM EM. town. '[f sac.tca auc6taa ete t i.e. 155utD FOR DIESEL CEN. 4 A CR FIRE I j' l oatt t... .ios c. u-a n.c 5 c-= r ~~ A V-9 3;w$a_Nx#~d4-:r.w 4,,mir.% a f ;+%;1J T.L.i M me re: 9 rt;U -.. vi e e amm 1

I __m_., m ll 4 ij p j-n u s ~ 3, m l w s. cu o., O 4 5 s p. .e ) o S j / f

j,

"- ( s' ma m z n g E, O 2 0

  • o p-
  • =

3 =,i z x o / = m i-e - 5 -c - = ue r-m ~ u Ow 3

  • =
  • $ l s

= z >z a sh 3 M ifz i m

a. r i

1 Eg w e a E E O E0 5 EE ! 2, I VI ~

  • 1 r ;;

I ,_ 0 " 5-5 lr 54 weo>g a5 e r-j s - + - - p ~ - Jl l. i c o - c.o

== s -ama m-I r-------- s w=*"* l l lr - - - - - - - - - - -- - J =' 1 "., 3,ay$$ o, "., , s SI-35 atNn 1I03 huj u) E g llg .u. niout alue t3313 a ou w.,a, zo vvvv

~

a " a. m.: ( T e -. -- -.-- ; n

s aw, y

[ , 'yL l l,. - _ _ _ - a,, E JE lll $UU 9835 M T e l stNn if 03 hus w; W z ao ll\\ .u.Nieut uava 13312 ~ vvvv --sil i ; = a llg-----

3. m r

2 A-vo~ ...-. - _ __ 1 l

  • C 55 gl d1 8* J - -Jll 90-35 alum 1tos nu,
  • d j

\\'- ll un 44 n4 ano Ew $755 ,= V

3 p j-

_._.8 vvvv Ipl -.o z i = l e g g, I'! gj f,- i r---- ,_ / l ,,, o nI g! 0 9 _J e En o

  • " M,,, a.3 b

4 f I j; l co-- .n . u..s.t an.1.r.o,) ll m t ~ E85 8"; 8-

j

~ --a vvvv

3 a

[ um l,!.__- e. e .i Il 80-3s 11%q 1:03 l nos *u3 aa *ow2 -t f y y --J h l e = ,r--- e d a l ll o-ot-3G ttNn 1101 2 /,Wp

O a

l nus wa mu = t 3 _;I vvvv A ~. l e o l r - --- a Il --a l 4 t ; ll! m ~ T -- p g, J r-J a c l O U.>- o } T 2, g o c -ww w ru- _L z. l E ~~~~' z c. o o w e e o ax ..E I S


8 I

+-- E 08" I 2 w w z 1g y a o l I Y o I $ ,(-- 3 EM


9 y }-

%;;gg is ,_.k O i 3 u ;

g...--

wo ow s-W11tsM 0311tH3 o e. o1 w. su 3 l wo m.a E .9. WL ~-a m e f,T, ~ 2$ yG y= "n e- = n a Q4 L M sn G M.e e-ua o.a G Qz E V V W? EM WW W3 W3 T1 '9-1 "15 N3 A1 N 'Y O S S S S _ __ _ _ -}}