ML20052A329

From kanterella
Jump to navigation Jump to search
Informs That Review Per RO-269/82-07 Has Determined That Plant Design & Const Predate Std Re Westinghouse SAI-1 Type Relays Not Meeting Full Surge Requirements
ML20052A329
Person / Time
Site: Oconee Duke Energy icon.png
Issue date: 04/09/1982
From: Parker W
DUKE POWER CO.
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
RO-269-82-07, RO-269-82-7, NUDOCS 8204280206
Download: ML20052A329 (1)


Text

_.

DUKE POWER COMPANY Powzu Duttmixo ~ ' lO P ~

422 SouTu Cnuncu STazzT, CHANtDTTE, N. C. asa4a l

I wituAu o. pAnwen,an.

v.cr pacsior , .l2 [PD lg j, g , d g ,

troc,o cA.c.7o4 ser. p.ooverio 372-4o83 April 9, 1982 9 4 Mr.. James P. O'Reilly, Regional Administrator , O l U. S. Nuclear Regulatory Commission s b s. @,. Y g,4 'g I

Region II l 101 Marietta Street, Suite 3100 2 7 l Atlanta, Georgia 30303

{ g' QO'@R I l

A. 2

! Re: Oconee Nuclear Station

, @ @'#9" N Docket No. 50-269 >

i?

hit l ,} Y

Dear Mr. O'Reilly:

On March 12, 1982 your office was notified of a reportable occurrence involving l Westinghouse SA-1 in service at the Keowee Hydro Station. Reportable Occurrence l Report R0-269/82-07 providing details of this incident was to have been submitted I to you by April 9, 1982. The original determination of reportability was based on identification by Westinghouse that the SA-1 type relays do not meet the full  ;

surge withstand requirements of ANSI C37.90 - 1978. However, subsequent review l has determined that the design and construction of the Oconee Plant and the Keowee Hydro Stations predate--the establishment of this standard.

Duke Power Company has had these relays in service for years in both safety and non-safety applications without any failures attributed to surges. Additionally, the surge withstand requirements of ANSI C37.90 - 1978 were not a design criteria or a regulatory requirement for this application. Hence, it is considered that this occurrence is without safety significance and is not reportabic.

Very truly yours, m, . y () , \ ,

William O. Parker, Jr JFK/php cc: Document Control Desk Records Center U. S. Nuclear Regulatory Commission Institute of Nuclear Power Operations Washington, D. C. 20555 1820 Water Place Atlanta, Georgia 30339 Mr. W. T. Orders NRC Resident Inspector Oconee Nuclear Station 6FFICIAL COPY e e mL. ,

820428o106 ,

/ O l

- -