ML20050C537

From kanterella
Jump to navigation Jump to search
Forwards Instrumentation & Control Sys Branch Technical Position Re Shutdown Capability from Outside Control Room
ML20050C537
Person / Time
Site: Waterford 
Issue date: 03/19/1982
From: Miraglia F
Office of Nuclear Reactor Regulation
To: Maurin L
LOUISIANA POWER & LIGHT CO.
Shared Package
ML20050C538 List:
References
NUDOCS 8204090033
Download: ML20050C537 (4)


Text

ef DISTRIBUTION:

Document Control:

Docket File NRC PDR LB#3 File Local PDR DEisenhut NSIC RTedesco TERA Docket No: 50-382 MAR 19 1982 FMiraglia TIC SBlack ACRS (16)

JLee 8

k

!!r. L. V. flaurin Region IV Vice President - Nuclear Operations 6'

Louisiana Power and Light Company 142 Delaronde Street l '"

New Orleans, Louisiana 70174 j

p p &g.p pa s:

g

):

m

Dear Mr. Maurin:

y.gy/.j is

,s 7

Enclosed is a copy of the Instrumentation and Con okSystems Branch technical position regarding shutdown capability from a location outside the main control room. This should assist you in understanding staff concerns regarding the safe shutdown analysis for Waterford 3.

Sincerely, Original signed by.

Frc.nk J. Mi.ragli4 Frank J. Miraglia, Chief Licensing Branch No. 3 Division of Licensing

Enclosure:

As stated cc w/ encl:

See next page 8204090033 820319 PDR ADOCK 05000382 A

PDR

..g.g.g#3 p......DL DL:LB on ce >

g

3..

sun ~ = >

3/..../..T.../82 3/

/82 oury

...i Nnc ronu ais po sci sncu em OFFICIAL RECORD COPY usam mi-nao

i Mr. L. V. Itaurin WATERFORD

.Yice President - Nuclear Operations

(

Louisiana Power & Light Company 142 Delaronde Street New Orleans, Louisiana 70174 W. Malcolm Stevenson, Esq.

Monroe & Lemann 1424 Whitney Building New Orleans, Louisiana 70130 Mr. E. Blake Shaw, Pittman,' Potts and Trowbridge 1800 M Street, N. W.

Washington, D.C.

20036 Mr. D. L. Aswell Vice President, Power Production Louisiana Power & Light Company 142 Delaronde Street New Orleans, Louisiana 70174 Mr. F. J. Drummond Project M' nager -_ Nuclear a

Louisiana Power & Light Company 142 Delaronde Street New Orleans, Louisiana 70174 Mr. D. B. Lester Production Engineer Louisiena Powar & Light Company 142 Delaronde Street New Orleans, Louisiana 70174 Lyman L. Jones, Jr., Esq.

Gillespie & Jones P. O. Box 9216 Metairie, Louisiana 70005 Luke Fontana, Esq.

824 Esplanade Ave.

New Orleans, Louisiana 70116 Stephen M. Irving, Esq.

535 North 6th Street j

Baton Rouge, Louisiana 70802 Resident Inspector /Waterford HPS P. O. Box 822 Killona, Louisiana 70066 Dr. D. C. Gibbs -

Middle South Services, Inc.

P. O. Box 61000 New Orleans, Louisiana 70161

_ ~.

LCSR POSLTION FOR REMOTE SHUTD0E'i CAPABIllTY FOR WATERFORD 3 To Meet GDC-19 (As interpreted in SRP Section 7.4)

1) The design should provide redundant safety grade capability to achieve and maintain hot shutdown from a location or locations, remote from the control room, assuming no fire damage to any required sy' stems and equipmnt and

~

assuming no accident has occurred.

Credit may be taken for manual actuation (exclusive of continuous control) of systems from locations that are reasonably accessible from the Remte Shutdown Panel.

Credit may not be taken for manual actions involving jumpering, rewiring or disconnecting circuits.

2)

The design should provide redundant safety grade capability for attaining subsequent cold shutdown through the use of suitable procedures.

_To Meet Appendix K (ECCS Requirements)

3), The design should be such that the manual transfer of control to the remte location (s) should not disable any automatic actuation of. ESF functions while the plant is attaining or maintained in hot shutdown, other than where ESF features are manually placed in service to achieve or maintain hot shutdown.

It is permissible to disable automatic LPCI actuation in this manner only when necessary in order to enabl.e control of the RHR system from the remte location and while operating this system to effect cold shutdown from hot shutdown.

To Meet Appendix R (Fire Protection Requirements)-

4)

The design should provide, as a minimum, non-redundant non-safety grade systems necessary to achieve and maintain hot shutdown from either the control room or i

from a remote location (s) assuming a postulated fire in any fire area, including the control room or the Re. note Shutdown Panel.

Credit may be taken for manual actuation (exclusive of continuous control) of systens fmm locations that are reasonably accessible from the control room or the Remte Shutdown Panel, as applicable. Credit may not be taken for manual actions involving jumpering, rewiring'or disconnecting circuits.

w r-

~

5) 'Ti.te d: sign should provide, as a minimum non-redundant'non-safety grade systems e

necessary to ' achieve and maintain cold shutdown from either the control room or from a rerote location (s).. The design should be such that in the event of fire damage in any fire area, systems could be repaired or nade operable within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> if required for cold shutdown.

For further guidance, see 10 CFR Part 50, Appendix R.

).

O e

9 e

O De G

t 4

a i

j

.