CONSUMERS POWER COMPANY DOCKET N0. 50-155 BIG ROCK POINT PLANT AMENDMENT TO FACILITY OPERATING LICENSE
'Ainendment No. 52 License No. DPR-6 1.
The Nuclear Regulatory Commission (the Commission) has found that; A.
The application for amendment by Consumers Power Company (the licensee) dated September 18, 1981, as supplemented January 29, and March 10, 1982, complies with the standards and requirements of the Atomic Energy Act of 1954, as amended (the Act), and the Cothmission's rules and regulations set forth in 10 CFR Chapter I; B.
The facility will operate in conformity with the application, the provisions of the Act, and the rules an~d regulations of the Commission; C.
There is reasonable assurance (i) that the activities authorized by this amendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in compliance with the Commission's regulations; D.
The issuance of this amendment will not be inimical to the common defense and security or to the health and safety of the public; and E.
The issuance of this amendment is in accordance with 10 CFR Part 51.of the Commission's regulations and all applicable requirements have been satisfied.
O e
l l
8204080394 820402 DR ADOCK 05000155 PDR
I 2-2.
Accordingly, the license is amended by changes to tne Technical Specifications as indicated in the attachment to this license amendment and Paragraph 2.C(?) of Facility Operating License No. DPR-6 is.hereby amended to read as follows:
Technical Specifications G
The Technical Specific ~itions contained in Appe'ndix A as revised' through Amendment No. 52, are he'reby incorporated in the license! The licensee shall operate the. facility in acco'rdance with the Technical Specifications.
3.
This license amendment is effective as of the date of its issuance.
FOR THE NUCLEAR REGULATORY COMMIS$104 k-
~
i Dennis M. Crutchfield Ch f Operating Reactors Branch #5 Division of Licensing
Attachment:
Changes to the Technical Specifications Date of Issuance: April 2,1982 9
a e
9 4
r_-
'[ "
-1.'"
h;;
~
ATTACHMErlT TO LICEriSE AMErlDMENT fl0. 52 FACILITY OPERATIfiG LICEftSE T10. DPR-6 DOCKET T10. 50-155 Revise Appendix A Technical Specifications by removing the page identified below and inserting the enclosed page. The revised page includes the cap-t!Joed amendment number and marginal line indicating the area of change.
f :-
PAGE
. 3a(Table 4-1)
,e e
4 9
4 S
e w
e 4
e e
. HYDR 0 STATIC TEST PRESSURE / TEMPERATURE LIMITS,
^
FLANGE BELTLINE FRES$URE LinlTS PRES $URE LIMIT lal l
l-BELTLINE TEM PE R ATU R E TEMP.
RATE OgCHANGE 4 F/HR) 60 F 110 F 160 F 210 F 260 F
< 120*F 0
0 848 950 1262 1600 300 20 805 904 1108 1529 40 762 858 1054 1458 2294 60 721 812 1001 1390 2194 80 478 766 948 1322 2096 100 637 721 896 1256 1996 HEATUPP'R'ISSURE/TEMPERATUREL,lMiTS FLANGE BELTLINE PRESSURE LIMITS PRESSURE LIMITis)
BE LTL I N E TEMPERATURE (SEENOTE3WHENREACTORISCRITICAL)
T EM P.
RATE OF 0[F/HR)
CHANGE
(
60 F 110 F 160'F 210*F 260'F
< 150'F 0
632 709 868 1196 1875 300 20 598 670 818 1124 1755 40 56 4 631 769 1054 1642 531 593 722 987 1534 60
+
80 408 -
556 675 922 1832 300 46 5 519 631 860 1335 C00LDOWN PRESSURE / TEMPERATURE LIMITS FLANGE BELTLINE PRES $URE LIMITS PRESSURE LIMITlal DELTLINE TEM P ER ATU RE (SEENOTE3WHENREACTORISCRITICAL)
TEMP RATE OF CgANGE 60*F 110*F 160*F 210*F 260'F
< 150*F 0
632 709 868 1196 1873 300 20 600 674 827 1143 1795 40 568 640 787 1C90 1717 60 537 605 747
,1039 1642 80 505 571 707 988 1568 100 474 537 668 938 1495 CRITICALITT TEMPERATURE LIMITS: THE MINIMUM TEMPERATURE AT WHICH A CRITICALITT (EXCEPT FOR LOW POWER PHYSICS TESTING) CAN TAKE' PLACE IS 120*F WATER TEMPERATURE NOTES
- 1. DURING A NSS$ HYDR 0 STATIC TEST THE PRIMARY SYSTEM WATER TEMPERATURE CAN EXPEED 212*F WITHOUT ENTERING THE TECHNICAL SPECIFICATION POWER OPERATION DEFINITION FOUND IN SECTION 1.2.1.
HYOROSTAfic TESTS ARE PERMIS$1BLE ONLY WITH THE REACTOR SUBCRITICAL.
j
- 2. TABLES ARE A*PLICABLE FOR 1.25 EFPY FROM THE END OF THE 1982 REFUELING OUTAGE
- 3. HEATUP/COOLDOWN PRESSURE LIMITS ARE APPLICAB,LE AT TEMPERATURES AT LEAST 40'F HIGHER WHEN THE REACTOR IS CRITICAL.
- 4. FLANGE PRESSURE LIMITS ARE NOT DEPENDENT UPON THE TEMPERATURE RATE OF CHANGE i
- 5. ALL PRESSURE LIMITS tRE IN PSIG 4-3a Amendment No.,,( M 52
.