3 LCR 93-13 NLR-N93067 i

ATTACHMENT 2 INSERTS AND MARKED-UP PAGES REQUEST FOR LICENSE AMENDMENT HOPE CREEK GCNER_iTING STATION FACILITY OPERATING LICENSE NO. NPF-57 l

DOCKET NO. 50-354 l

f 6

[

t l

i i

9305280247 930518 PDR ADDCK 05000354 P-PDR i

e

Ti

~

ii.

~

LCR 93-13 NLR-N93067-1 i

_TJ.CHNICAL SPECIFICATION PAGES WITH PEN AND INK CHANGES i

The following Technical Specifications are affected by this requested amendment:

Facility Operating License No. NPF-57 Technical Specification Page 3/4.4.1.2 3/4 4-4 l

l r

l i

l i

)

e-I t

1 b

4 7.

n

REACTOR COOLANT SYSTEM JET PUMPS LIMITING CONDITION FOR OPERATION 3.4.1.2 All jet pumps shall be OPEPABLE.

APPLICABILITY:

OPERATIONAL CONDITIONS 1 and 2.

ACTION:

With ots or more jet pumps inoperable, be in at least HOT SHUTDOWN within 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.

SURVEILLANCEREQUIREMENTSh 4.4.1.2 All jet pumps shall be demonstrated OPERABLE as follows:

Each of the above required jet pumps shall be demonstrated OPERABLE a.

prior to THERMAL POWER exceeding 25%.of Rt.TED THERMAL POWER and at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by determining recirculation loop flow, total core flow and diffuser-to-lower plenum differential pressure for each jet pump and verifying that no two of the following conditions occur when the recirculation pumps are operating in accordance with Specification 3.4.1.3.

1.

The indicated recirculation loop flow differs by more than 10%

from the established pump speed-loop flow characteristics.

2.

The indicated total core flow differs by more than 10% from the established total core flow value derived from recirculation loop flow measurements.

3.

The indicated diffuser-to-lower plenus differential pressure of any individual jet pump differs frca the established patterns by more than mar 2 b.

During single recirculation loop operation, each of the above required w ear.t -

_fet oumpsashall be demonstrated OPERABLE at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> by verifylng that no two of the following. conditions occur:

1.

The indicated recirculation loop flow in operating loop dif-fers by more than 10% from the establishe ump speed-loop flow characteristics.

tw 2.

The indica total core flow differs by more than 10% from the establishe

  • total core flow value derived from single recirculation loop flow measurements.

pgm 3.

The indicated diffuser-to-lower plenus differential pressure l

1 of any individual jet pump differs from e 4blished@ single recirculation loop patterns by more than l*-Imrer Z The prorisions of Specification 4.0.4 are not applicable provided c.

that this surveillance is performed within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> after exceeding 25% of RATED THERMAL POWER.

pter "Durjng artv[foi ring /ny fue 1 fig o age, d ip /o to o ain nglefioop or/t oo 'oper ion tsel ed a, d s

1 byre ed f th par ers

/is t prov ea sis or tabl hin the eci dr atio hips Com /

pjr so of ea al ta ac dan wi thvtrite a li ed s 1