June 7,1990
'J e<
r Docket No. 50-295 DISTR:' T:
f"M
,. t,
NRC & Local PDRs PDill-2 r JZwolinski RDudley CPatel CMoore OGC-WF1
, cA EJordan ACRS(10)
.Mr. Thomas J. Kovach PDIII-3 Gray DHood Nuclear. Licensing Manager Comonwealth Edison' Company-Suite 300.
OPUS West 111 1400 OPUS Place L
Downers Grove, Illinois 60515
-l
Dear Mr. Kovach:
SUBJECT:
NRC BULLETIN 88-01, " DEFECTS IN WESTINGHOUSE CIRCUIT BREAKERS" (TACNO.67/41)
On February 5,1988, NRC Bulletin 88-01 was issued and requested holders of 1
L operating licenses or construction permits to provide letters of confirmation 4
l-to the NRC of the completion of specified inspections on Westinghouse DS l
series circuit breakers. Addressees who do not have DS series circuit c
breakers in Class 1E service were requested to provide a letter to the NRC i
stating this fact.
l l
Your response dated January 22, 1990,. confirmed that you have performed the I
requested inspections on all relevant circuit breakers and that corrective i
actions, when needed, have been completed in accordance with the NRC 1-Bulletin.
Thus, your response to Bulletin 88-01 is satisfactory for Zion, Unit 1, and TAC No. 67741 is closed.
Sincerely,
' Original signed by l
Chandu P. Patel, Project Manager i
Project Directorate III-2 Division of Reactor Projects - III, IV, V and Special Projects i
Office of Nuclear Reactor Regulation l
i l
l' cc: See next page s
DOCUMENT NAME: TAC 67742 CIRCUIT BREAKERS d [F Dudley fA)PD/PD111-2 Office:
1-2 PM I-2
-3 Surname:~
org CPatel/tg D
R j
Date:
/ ( /90 6 /1 /90
/
L/g/90 b
9006130361 900607 PDR ADOCK 05000295 O
PDC D Foi ip c.
.~. -..
c [i
- p>wouq'o UNITED STATES
~y 8
d
. NUCLEAR REGULATORY COMMISSION -
wAsumatow, o, c. rosos -
i
. i 4) f June ~7,-1990
- ...+[
j Docket No. 50-295 Mr. Thoinas J. Kovach '
l Nuclear Licensing Manager 1
-Commonwealth Edison Company-Suite 300 I
OPUS West 111 1400 OPUS Place Downers Grove,. Illinois 60515 1
Dear Mr. Kovach:
SUBJECT:
NRC BULLETIN 88-01, " DEFECTS IN WESTINGHOUSE CIRCUIT BREAKERS" (TACNO.67741)
-l On February 5,1988, NRC Bulletin 88-01 was issued and requested holders of operating licenses or construction permits to provide letters of confirmation
~to the_NRC of the completion of specified inspections on Westinghouse DS l
series circuit breakers.
Addressees who do not have DS series circuit'
. breakers in Class IE service were requested to provide a letter to the NRC
. stating this_ fact.
Your response dated January 22. 1990, confirmed that you aave performed the requested inspections on-all relevant circuit breakers and that corrective actions, when needed,-have been completed in accordance with the NRC Bulletin. Thus, your response to Bu11etin'88-01 is atisf actory for Zion, q
Unit 1, and TAC No. 67741 is closed.
Sincerely, h'fofh Chandu P. Patel, Project Manager-Project Directorate 111-2 Division of Reactor Projects - III, IV, V and Special Projects Office of Nuclear Reactor Regulation i
cc: See next page y
l E'-
t-
y
<.-p
.)
1 e,'g l
g, "'
~i 1Mr.-ThomasJ.Kovach.
~ Zion Nuclear Power. Station Comonweal.th Edison. Company' Unit Nos. I and-2 CC' Robert'J.- Vollen,-Esquire' i
109 North
Dearborn Street:
f
.. Chicago. Illinois:60602-iDr. Cecil Lue-Hing.
tDirector'of Research and Development Metropolitan. Sanitary District.
of. Greater Chicago-
-100 East Erie Street:
Chicago,!!111nois 60611 Phillip Steptoe, Esq.
Sidley and Austin One First National Plaza Chicago, 11.linois 60603 Mayor of' Zion-Zion, Illinois 60099 Illinois Department of Nuclear Safety.
Office of Nuclear Facility Safety 1035 Outer Park Drive
-Springfield,. Illinois 62704-U.SL Nuclear Regulatory Comission i;
- Resident inspectors Office-t 105 Shiloh Blvd.-
[
Zion,: illinois 60099 Regional Administrator, Region III m
~
U.S. Nuclear Regulatory Commission L..
799 Roosevelt Road, Bldg. #4
' Glen Ellyn, Illinois 60137
. Robert Neumann
' Office.of Public Counsel l
State of-Illinois Center 100 W. Randolph Suite 11-300-
' Chicago, Illinois 60601 z.
.