ML20043B358

From kanterella
Jump to navigation Jump to search
Notice of Violation from Insp on 900305-0409.Violation Noted:Operability Not Demonstrated Until 900309 Following Closing of Containment Air Lock Exceeding 72-h Requirement
ML20043B358
Person / Time
Site: Seabrook 
Issue date: 05/08/1990
From:
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
To:
Shared Package
ML20043B357 List:
References
50-443-90-08, 50-443-90-8, NUDOCS 9005290179
Download: ML20043B358 (1)


Text

W

.a;2 ll l

41 ENCLOSURE _1 R

NOTICE OF VIOLATION U

Public Service Company of New Hampshire Docket No.

50-443 Seabrook Unit 1 License No. NPF-86 g.

h 4

During NRC inspection from March 5 - April 9,1990, a violation of NRC require-l ments was identified in accordance with the " General Statement of Policy and

,i Procedure for NRC Enforcement Actions," 10 CFR, Part 2, Appendix C.

That vio-1ation is listed below:

1 Technical Specification 4.6.1.3(a) requires in part that, following each closing of the containment air lock, operability shall be demonstrated within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />.

Contrary to the above, folinwing the closing of the containment air lock on February 13, 1990, operability was not demonstrated until March 9, 1990, which exceeded the 72 hour8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> requirement.

This is a Severity Level V Violation (Supplement 1).

Pursuant to 10 CFR 2.201, the Public Service Company of New Hampshire is hereby required to submit to this office, within 30 days of the date of the letter transmitting this Notice, a written reply including:

(1) the reason for the violation, if admitted; (2) the corrective steps which have been taken and the results achieved; (3) the corrective steps which will be taken to avoid further violations; and (4) the date when full compliance will be achieved. Where good cause is shown, consideration will be given to extending this response time.

The reply required by this Notice is exempt from the clearance procedures of the Office of Management and Budget as required by the Paperwork Reduction Act of 1989, PL 96-511.

l OFFICIAL RECORD COPY IR SEABROOK 90 0003.0.0 9005290179 900508 PDR ADOCK 05000443 Q

PDC

. -.