ML20043A790
| ML20043A790 | |
| Person / Time | |
|---|---|
| Site: | Oyster Creek |
| Issue date: | 05/11/1990 |
| From: | Fitzpatrick E GENERAL PUBLIC UTILITIES CORP. |
| To: | NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM) |
| References | |
| 90-03, 90-3, NUDOCS 9005230130 | |
| Download: ML20043A790 (2) | |
Text
.,
f
.- - + e M:;4.if 7Nuclear
- :',rg e see
~
OPU Nuclear Corporation Forked River,New Jersey 08731-0388 609 971 4000 Writer's Direct Dial Number:
May ll,1990
'U.S. Nuclear Regulatory Commission Attn Document Control Desk Washington, D.C.
20555 Dear Sir
Subject:
Oyster Creek Nuclear Generating Station
-l Docket No. 50-219-Special Report 90-03 Enclosed is Special Report 90-03 which is submitted in accordance with Technical Specification 3.12.B.
If any questions'or comments shoald arise, please contact Mr. John Rogers, Oyster Creek Licensing Engineer at 609-971-4893.
Very truly yours,
/
f C //
W e
s n
n tor Oyster Creek EEF/JJR/jc Enclosure cca Mr.. Thomas Martin, Administrator Region 1 U.S. Nuclear Regulatory Commission 475 Allendale Road King of Prussia, PA 19406 NRC Resident' Inspector Oyster Creek Nuclear Generating Station Mr. Alexander Dromerick U.S. Nuclear Regulatory Commission Mail Station Pl-137 f
j Washington, DC 20555
.//[,F
)
9003230130 900511
/ I PDR ADOCK 05000219 GPU Nuclear Corpora $ ibis a subsidia,y of the General Public Utilities Corporation j
' t 1
OYSTER CREEK NUCLEAR GENERATING STATION Forked River, New Jersey 08731 special Report 90.-03 ReDort Date Occurrence Date 4/12/90 i
Identification of occurrences i
Fire Diesel Pump 1-1 was removed from service to install a modification and was not restored to a functional status within seven (7) days as required by i
Technical specification 3.12.B.
Deectiotion of occurrence The Fire Diesel' Pump 1-1 was taken out of service to install a modification which replaced the existing pressure switch / recorder mechanism with an upgraded design.
The installation, testing and return to service required eight (8) days.
Analysis of occurrences l
Maintenance on the Fire Diesel Pump automatic start pressure switch / recorder mechanisms was becoming a burden to the Oyster Creek Nuclear Plant.
The switch / recorder mechanisme were difficult to calibrate to within the desired tolerances and no replacement parts were available due to the obsolete design.
As the Fire Diesel 1-2 was functional during the time period the modification was being insta11od in fire diesel 1-1, the safety significance.of this event was minLmal.
I Corrective Action:
1 The modification to Fire Diesel Pump 1-1 pressure switch / recorder me8hanism was completed, tested and returned to functional status on 4/20/90.