s.o m g$fIhNk epgg hj;G M '*

QQC Q U?

N ;.c-[

Q n

M M...... _

4 ce P

March 9,1982

'3 REC &lM

  1. 3F-0382-04 P

File: 3-0-3-e g

pgpy7;ggg>

~

n em un e n*s.

Mr. Harold R. Denton, Director g

axcemsa Office of Nuclear Reactor Regulation 9

U. S. Nuclear Regulatory Commission

p Washington, D. C. 20555 6

SUBJECT:

Crystal River Unit 3 Docket No. 50-302 Operating License No. DPR-72 Technical Specification Change Request No. 94 Reactor Protection System Response Times

Dear Mr. Denton:

Florida Power Corporation hereby submits three (3) originals and forty (40) copies of Technical Specification Change Request No. 94, requesting amendment to Appendix A of Operating License No. DPR-72. The requested change provides new response time limits for the Reactor Protection System Instrumentation in order to avoid spurious reactor trips associated with the Reactor Coolant Pump Power Monitors (RCPPM) and to correct previous errors. As part of this request, proposed replacement pages are enclosed.

In addition, as requested by members of your staff, Florida Power Corporation offers the following additional information:

1)

Florida Power Corporation will develop methodology for in-place response time testing of the entire Reactor Coolant Pump Power Monitor String by June 15,1982. One string will be tested at the first plant outage of four (4) weeks or greater duration, after methodology has been developed.

If in-place test methods cannot be developed, alternate methods or analyses will be provided to your staff for review and concurrence.

2)

Florida Power Corporation will evaluate the possibility of power supply anomalies being the source of the spurious RCPPM trips. However, as has been noted in the various conversations with the staff, the power supplies to the RCPPM circuitry, except for the self-powered devices (Current Transformers, Potential Transformers, and Watts Transducers), are battery backed, vital, Class IE supplies with appropriate redundancy.

3)

Within six (6) months, Florida Power Corporation will either acquire actual type-test data on the GE supplied current and potential transformers or will justify continued use of analytical methods as equivalent to testing.

' O/

o

.f 8203170603 820309 PDR ADOCK 05000302 P

PDR General Office 3201 Tmny-fourth street soutn. P O Box 14o42. St. Petersburg. Fiorda 33733 e 813-866-5151 L

Mr. Harold R. Denton March 9,1982 Page 4)_

A summary of the allocated and "actuai" response times for the various stages of the RCPPM design evolution is provided in Table 2.

Also enclosed is a signed copy of the Certificate of Service of Technical Specification Change Request No. 94 to the Chief Executive Office, Citrus County, Florida.

The action supplements our submittal of March 4,1982, and as such, no further license fees are considered necessary.

Should there be any questions, please contact this office.

Very truly yours, -

A David G. Mardis Acting Manager Nuclear Licensing EWF/ mig Enclosure cc: Mr. J. P. O'Reilly, Regional Administrator Office of Inspection & Enforcement U. S. Nuclear Regulatory Comission 101 Marietta Street, Ste. 3100 Atlanta, GA 30303

UNITED STATES OF AMERICA NUCLEAR REGULATORY COMMISSION

= IN THE MATTER OF

)

)_

DOCKET NO. 50-302 FLORIDA POWER CORPORATION )

CERTIFICATE OF SERVICE D. G. Mardis deposes and says that the following has been served on the Chief Executive of Citrus County, Florida, by deposit. in the United States mail, addressed as follows:

Chairman, Board of County Commissioners of Citrus County Citrus County Courthouse Inverness, FL 32650 One (1) copy of Technical Specification Change Request No. 94 requesting amendment to Appendix A of Operating License No. DPR-72.

FLORIDA POWER CORPORATION d

q D G. Mardis Acting Manager Nuclear Licensing SWORN TO AND SUBSCRIBED BEFORE ME THIS 9TH DAY OF MARCH,1982.

ADtWh W

Notar9 pblic l

Notary Public, State of Florida at Large My Commission Expires: May 29,1984

)

(NOTARIAL SEAL) i L

STATE OF FLORIDA COUNTY OF PINELLAS D. G. Mardis states that he is the Acting Manager, Nuclear Licensing, of Florida Power Corporation; that he is authorized on the part of said company to sign and file with the Nuclear Regulatory Commission the information attached hereto; and that all such statements made and matters set forth therein are true and correct to the best of his knowledge, information, and belief.

M D. G N ardis' Subscribed and sworn to before me, a Notary Public in and for the State and County above named, this 9th day of March,1982.

AufwT f Notafy Public Notary Public, State of Florida at Large, My Commission Expires: May 29,1984 i

l

_