4 DUKE POWER COMPANY DCCKET NO. 50-369 MCGUIRE NUCLEAR STATION, UNIT 1 AMENDMENT TO FACILITY OPERATING L' CENSE Amendnent No.12 License No. NPF-9 1.
The Nuclear Regulatory Coranission (the Conmission) has found that:
A.
The application for amendmnt to the McGuire Nuclear Station, Unit 1 (the facility) Facility Operating License No. NPF-9 filed by the Duke Power Conpany (licensee) dated January 11,198, couplies with the standards and requirenunts of the Atomic Energ Act of 1954, as amended (the Act) and the Commission's regulations as set forth in 10 CFR Chapter I; B.
The facility will cperate in conformity with the application, the provisions of the Act, and the regulations of the Comission; C.
There is reasonable assurance: (1) that the activities authorized by this anendment can be conducted without endangering the health and safety of the public, and (ii) that such activities will be conducted in conpliance with the Conmission's regulations set forth in 10 CFR Chapter I; D.
The issuance of this license amendment will not be inimical to the comon defense and security or to the health and safety of the public; E.
The issuance of this amendacnt is in accordance with 10 CFR Part 51 of the Comission's regulations and all applicable requirements have been satisfied.
2.
Accordingly, the license is hereby amended by page changes to the Technical Specifications as indicated in the attachacnts to this licensa anendment and paragraph 2.C.(2) of Facility Operating License No. hPF-9 is hereby amended to read as follows:
(2) Technical Specifications The Technical Specifications contained in Appendix A, as revised through Amendacnt No.12, are hereby incorporated into this license. The licensee shall operate the facility in accordance with the Technical Specifications and the Environmental Protection Plan.
?88988 ?o!88b8h
~~>
.._ o... e eos om>
OFFICIAL RECORD COPY usom ini-mwa me ronu m oo-aomacu ono
2-3.
This license amendment was effective January 11,19P2.
FOR THE NUCLEAR REGULATORY CO*it'1SSION
(
Elinor G. Adensan, Chief Licensing Branch No. 4 Division of Licensing
Attachment:
Technical Specification changes Date of Issuance: January 29, 1982
- NOTE: SEE PREVIOUS WHITE FOR CONCURRENCE I
OFFICE)
..bh.I.h.4. b.h...k!...hk..kh... 4.....
...h O M..........
.. OE b O..........
..p LO.
4...... n.} /. R L.....
r sunswE)..*pnn nca n/hmc.
- RBir.kel........*GHolahan........*EKetchen..
....E h s am....
..Rf esco...
..l[.
.b........1 lb b2.-. -- l/.22/82.-
.. 1/.p.g.82--. - LM/.82.-..
D ATE )
. -. - - - -.. - ~ ~..
NRC FORM 318 (10@) NRCM 024o OFFICIAL RECORD COPY uso m i i-m.co
?
~
~
. y
\\ \\) ) 9 N L 3.
This license amendment j,p effective as of du date vi..,a e:ac.
FOR THE NUCLEAR REGULATORY COMitISSION Elinor G. Adensam, Chief Lichnsing Branch No. A Divis' ion of Licensing
Attachment:
Technical Specification changes
\\
Date of Issuance:
s
\\
s
\\
e<#
2.T 3
3
- tkh. $+g*'
4e db w
o,,,c.,.Laaty. a..s.....n.L:.ta..'s........oad.t..Q.'..
.....at U.......Taaa s Aa:up.t.....
..Xs.t.*A.S.#.
.on _.> munnehmc......aai.ru t..........c ao.i a a m.
.EAdansan........ RTedemo....
e->.u.st.aa..............u.si.aa..........u\\.'.'uat......uuaa.....u....ia2....
..u....ia2......
Nac ronn ais o0-80) NRCM ONO OFFICIAL RECORD COPY usa m m i-m m
~0-7 ATTACINENT TO LICENSE AMENDMENT NO.12 FACILITY OPERATING LICENSE NO. NPF-9 DOCKET NO. 50-369 Replace the following pages of the Appendix "A" Technical Specifications with the enclosed pages. The revised pages are identified by Amendment nunter and contain a vertical line indicating the area of change. The corresponding overleaf pages are also provided to maintain document coupleteness.
s Overleaf Aanded Page h
3/4 5-12 3/4 5-11 omca >
sunnAus >
orre >
Nnc ronu ais tio-soi nncu o24o OFFICIAL RECORD COPY usapo --ass-eea
[
ENERGENCY CORE COOLING SYSTEMS 3/4'. 5. 4 BORON INJECTION SYSTEM BORON INJEC110N TANK LIMITING CONDITION FOR OPERATION 3.5.4.1 The boron injection tank shall be OPERABLE with:
A ainimum contained borated water volume of 900 gallons, a.
b.
Between 20,000 and 22,500 ppm of boron
- and c.
A minimum solution temperature of 145 F.
APPLICABILITY:
MODES 1, 2 and 3.
ACTION:
With the boron injection tank inoperable, restore the tank to OPEFABLE status within I hour or be in HOT STANDBY and borated to a SHUIDOWN MARGIN equivalent to 1% Ak/k at 200 F within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br />; restore the tank to OPERABLE status within the next 7 days or be in HOT SHufDOWN
\\,
within the next 12 hours1.388889e-4 days <br />0.00333 hours <br />1.984127e-5 weeks <br />4.566e-6 months <br />.
SURVEILLANCE REQUIREMENTS 4.5.4.1 The boron injection tank shall be demonstrated OPERABLE by:
Verifying the contained borated water volume at least once a.
per 7 days, b.
Verifying the boron concentration of the water in the tank at least once per 7 days, and Verifying the water temperature at least once per 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />.
c.
- For a period of seven days commencing on January 11, 1982, and running through January 18, 1982, the boron injection tank shall be OPERABLE with between 2,000 and 22,500 ppm of boron.
1 McGUIRE - UNII 1 3/4 5-11 Amendment No. 12
El PGENCY-_ CORE COOLING SYSTEl'S
/
,_ HEAT TRACING
~
LIPITING-CONDITIO TFOR OPERATION 3.5.4.2 At least two independent channels.of heat-tracinp shall be '0PEPABLE
'for the boron injection tank and for the heat traced portions of the associated flow paths.
APPL ICABILITY:
MODES 1, 2 and 3.
ACTION:
Vith only one channel of heat tracing' on either the boron injection tank or on-the heat traced portion of an associated flow path OPERABLE, operation may continue for up_ to 30 days provided the tank and flow-path temperatures are verified to -be greater than or equal to 145 F at least once-per 8 hours9.259259e-5 days <br />0.00222 hours <br />1.322751e-5 weeks <br />3.044e-6 months <br />; otherwise, be in at least HOT STAND 8Y within 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in HOT SHUTOOWN within~ the following 6. hours.
.k SURVEILLANCE REOUIREPENTS 4.5.4.2 Each heat tracing channel for the boron injection tank and associated flow path shall be deconstrated OPERABLE:
At least once per 31 days by energizing each-heat tracing channel, a.
and b.
At least once per_24 hours by verifying the tank and-flow path temperatures to be _ greater than or equal to 145 F.
The t a nk --
temperature shall be determined by neasurement. The flow path temperature shall be detemined by either measurement or recir-culation flow until. establishment of equilibrium temperatures within the tank.
-McGUIRE - UNIT 1 3/4 5-12
..