ML20040E649
| ML20040E649 | |
| Person / Time | |
|---|---|
| Site: | Bellefonte |
| Issue date: | 01/26/1982 |
| From: | Mills L TENNESSEE VALLEY AUTHORITY |
| To: | James O'Reilly NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II) |
| References | |
| REF-PT21-81 10CFR-050.55E, 10CFR-50.55E, NUDOCS 8202050209 | |
| Download: ML20040E649 (2) | |
Text
-
s 3
=O-E' i
- TENNESSEE VALLEY AUTHORITY NRC REClN!
4 CH ATTANC>OG A, TENNESSEE 374N ', *
~
, q q g, -
400 Chestnut Street' Tower II d
I January 26, 1982g p q 28 A3 08 7
4 s
'BLitD-50-438/81-41 BLaD-50 439/81-43 1-t e
Mr.,; James P. O'Reilly, Director e
, Of fice of Inspection and Enforcement
' U.S., Nuclear Regulatory Commission s'
' *-c -,e.,E i
Rigion II - Suite 3100 g
Fend
!c82s h
101 Marietta Street g
gatlanta, Georgia 30303 3,4 c p gre m o j
.a~~,n
(\\
Dea'r.Mr. O'Reilly:
BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - BOP ISOLATOR CABINET -
'i ' ~
BLED-50-438/81141, BLRD-50-439/81 FINAL REPORT s
The subject deficiency was initially reported to NRC-0IE Inspector R. V. Crlenjak on May 27, 1981 in accordance with 10 CFR 50.55(e) as NCR 1472. This was followed by our first interim report dated June 26, 1981, our revised first interim report dated July 10, 1981, and our second interim report dated September 25, 1981. Enclosed is our final report. We consider 10 CFR Part 21 applicable to this deficiency.
If you have any questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.
Very truly yours, TENNESSEE VALLEY AUTHORITY v L. M. M 1s, Manage Nuclear egulation d Safety i
Enclosure cc:
Mr. Richard C. DeYoung, Director (Enclosure)
Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 OFFICIAL COPY 8202050209 820126 g/{'gy PDR ADOCK 05000438 J
S PDR An Equal Opportunity Employer
-. =.
/
/k' s - e ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 BOP ISOLATOR CABINET BLRD-50-438/81-41, BLRD-50-439/81-43 10 CFR 50.55(e)
~~
FINAL REPORT Description of Deficiency During receiving inspection of balance-of-plant (BOP) isolator cabinet 2IX-ISOL-262-G at Bellefonte, TVA employees found tnat a conductor was pulled out of. terminal lug TBA-5A-5.
The conductor is on the Class IE side (input) of the cabinet. The BOP isolator cabinets are used to effectively isolate electrical Class IE from non-Class IE instrumentation. This was a one-time occurrence and has not happened on any other isolator cabinet.
This condition was apparently caused by interference of the door-looking mechanism with the internal wiring. This defect may be generic to the other isolator cabinets at Bellefonte provided'by E. Max, Incorporated.
Safety Implications The interaction of the door locking mechanism and isolator wiring represented a deficiency which could have resulted in damage to the isolator sufficient to preve7t its proper performance. Had this condition remained uncorrected, the safe operation of the plant could have been affected in that the feedback from non-Class IE instrumentation could have interfered with the operation of Class IE instrumentation.
Corrective Action TVA will rework the damaged termination to assure proper continuity of the circuit. To prevent recurrence, the terminal blocks located nearest the door-locking mechanism will be moved toward the rear of the cabinet such that a minimum of 1/2-inch clearance is provided between the internal wiring harness connected to the terminal blocks and the inside front edge of the cabinet. This corrective action will be taken on all E. Max, Incorporated cabinets and is expected to be completed by April 15, 1982.
No other cabinets provided by E. Max are used at other TVA plants.