ML20040E522

From kanterella
Jump to navigation Jump to search
First Interim Deficiency Rept Re Heat Tracing Tapes Not Meeting Chemical Specs,Initially Reported 811224.Util Evaluating Problem.Next Rept by 820125
ML20040E522
Person / Time
Site: Bellefonte  
Issue date: 01/25/1982
From: Mills L
TENNESSEE VALLEY AUTHORITY
To: James O'Reilly
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
References
10CFR-050.55E, 10CFR-50.55E, NUDOCS 8202050031
Download: ML20040E522 (2)


Text

.

r

. TENNESSEE VALLEY AUTHORITY

. /RC REgggfj

~ ' # 'IIIA, g y CHATTANOOGA. TENNESSEE 37401 400 Chestnut Street Tower II January 25, 1982 MN ^ S: 0" BLRD-50-438/82-06 BLRD-50-439/82 Pt l s i

e Mr. James P. O'Reilly, Director

/,

Office of Inspection and Enforcement S

U.S. Nuclear Regulatory. Commission O,,CEM

. (E \\

,s FEg i.

Region II - Suite 3'00 uny,k, ISS2cs 9

101 Marietta Street Atlanta, Georgia 30303 n~ J;;;?t. y e

n~:

Dear Mr. O'Reilly:

/

js y c,

-A BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - TAPES FOR HEAT TRAC NOT MEET CHEMICAL SPECIFICATIONS - BLRD-50-438/82-06, BLRD-50-439/82 FIRST INTERIM REPORT The subject defic'.ency was initially reported to NRC-0IE Inspector D. Quick on December 24, 1981 in accordance with 10.CFR 50.55(e) as s

NCR 1692. Enclosed is our first interim report. We expect to submit our.next report by April 14, 1982.

If you have any ~ questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.

Very truly yours, TENNESSEE VALLEY AUTHORITY l

L. M. Mills, nager l

Nuclear Regula ion and Safety 1

Enclosure I,

cc:

Mr. Richard C. DeYoung, Director (Enclosure)

Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC-20555 OFFICIAL COPY 8202050031 820125 PDR ADOCK 05000 An Equal Opportunity Employer M

c

ENCLOSURE BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 TAPES FOR HEAT TRACINO DO NOT MEET CHEMICAL SPECIFICATIONS BLRD-50-438/82-06, BLRD-50-439/82-06 10 CFR 50.55(e)

FIRST INTERIM REPORT

- Description of Deficiency Permacel FT-160 is a pressure sensitive tape supplied to TVA by the heat trace system vendor, Chemelex Division, Raychem Corp., Redwood City, CA.

Upon receipt, TVA evaluated PT-180 per Purchase Specification PF-4121,

" Purchase Specification for Pressure Sensitive Tapes for Use.on Stainless Steels or Other Corrosion Resistant Alloys," which establishes the total halogen content and the leachable halide content acceptable in pressure sensitive tapes that may be used on stainless steel. TVA's Singleton Materials Engineering Laboratory Report B-198 establishes that the leachable halide content of PT-180 exceeds PF-4121 guidelines.

In addition, the sulphur content of PT-180 exceeds PF-4121 guidelines, but this has been determined to be a nonsignificant condition in accordance with 10 CFR 50.55(e) guidelines because sulphur has no adverse effects on stainless steel pipe.

Purchase specification PF-4121 which is referenced above is applied only to indefinite quantity term (IQT) contracts which are administered by site personnel. However, PT-180 was supplied under a contract which was administered by Engineering Design personnel, and PF-4121 was not a part of the procurement documents. Consequently, this is not consicered a 10 CFR Part 21 nonconformance.

Interim Progress TVA is evaluating the deficiency and will supply additional information in our next report.

~-

-