Text
c APPENDIX A NOTICE OF VIOLATION Brown Boveri Electric, Incorporated Switchgear Systems Division Docket No. 99900740/81-02 As a result of the in';pection conducted on October 26, 27, and 30, 1981, and.
in accordance with the Interim Enforcement Policy, 45 FR 66754 (October 7, 1980), the following violation was identified:
Paragraph 21.51(b) of Title 10, Part 21 of the Code of Federal Regulations states in part, "Each individual, corporation, partnership, or other entity subject to the regulations in this part shall prepare records in connection with the design, manufacture, fabrication, placement, erection, installation, modification, inspection, or testing of any facility, basic component supplied for any licensed facility or to be used in any licensed activity sufficient to assure compliance with the regulations in this part. After delivery of the facility or component and prior to the destruction of the records relating to evaluations (see paragraph 21.3(g)) or notifications to the Commission (see paragraph 21.21), such records shall be offered to the purchaser of the facility or component."
A Gould-Brown Boveri letter, dated February 9,1981, to Bechtel Power Corporation states in part, "The BBE evaluation of this condition indicates that this type of condition is not reportable to the NRC under the require-ments of 10 CFR Part 21."
The condition was inadequate separation between Class IE/Non-Class IE conductors in six 480 volt load center isolation relay cabinets.
Contrary to the above, a record of evaluation had not been prepared for the identified Class IE/Non-Class IE conductor separation problem in the 480 volt load center isolation relay cabinets installed at the Palo Verde Nuclear Gent: rating Station, Unit Nos.1, 2, and 3.
This is a Severity Level VI Violation (Supplement II).
~
8201130201 811224 CT PDR GA999 EHVBBC 99900740-PDR
_