Transamenca Z "'"'"a*20:1s.

550 85th Avenue P.O. Box 2161 OaMand Cantornia 94621 h

(415)577-7400

.ll

[ G111--%

December 9, 1981

[

jj j

e Director, Office of Inspection & Regulation d'I 138 %

U.S. Nuclear Regulatory Commission

-; W s, amu sagg,

p.

Washington, D.C.

20555 W'

NA l'-Q

Dear Sir:

s In accordance with the requirements of Title 10, Chapter 1, Code of Federal Regulations, Part 21, Transamerica Delaval hereby notifies the Commission of a potential defect in a component of a DSR or DSRV Standby Diesel Generator. There exists a potential problem in the Governor Lube Oil Cooler Assembly which could result in engine non-availability.

Transamerica Delaval has supplied the DSR and DSRV series engines with the potential defect to the following sites:

Middle South Energy Grand Gulf S/N 74033/36

%.4'l Gulf States Utilities River Bend S/N 74039/40 e v. e t1 Carolina Power & Light Shearon Harris S/N 74046/49 14d,w W Duke Power Company Catawba S/N 75017/20 4is m Southern California Edison San Onofre S/N 75041/42 >-4 n l h i

Cleveland Electric Illuminating Perry Nuclear Station S/N 75051/54 e t id i a

Tennessee Valley Authority Bellefonte S/N 75080/83 a s2,3 Si Washington Public Power Supply WPPSS #1 S/N 75084/85

%v Georgia Power Company Vogtle S/N 76021/24

  • ia 7

Washington Public Power Supply WPPSS #4 S/N 76031/32 c'?

Consumers Power Company Midland 1 & 2 S/N 77001/04 9

to y

Tennessee Valley Authority Hartsville S/N 77024/35 7

-o ca\\

The Governor and Governor Lube Oil Cooler were manufactured by Woodward Governor Company of Fort Collins, Colorado. The Governor and Lube Oil Cooler were installed and piped on the engine by Transamerica Delaval.

The potential defect exists in the Governor Oil System.

If the Governor Lube Oil Cooler is installed above (elevation) the oil level of the Gov-ernor, the possibility of air being trapped in the system occurs when the oil level in the Governor is low.

l C$l

\\

. 8112160099 811209

>fA r

PDR ADOCK 05000206 S

PDR

Transamerica Detaval lnc.

. {ggg g

i Engine and Ccrnpressor Division hglg 550 85th Avenue P.O. Box 2161

' "' '"'* *' e2 i

=E (415) 577-7400 December 9, 1981 U.S. Nuclear Regulatory Commission Page 2 If air is trapped in the Governor's Oil System, engine starting may be affected. This problem can be eliminated by moving the Governor Lube Oil Cooler to an elevation below the Governor oil level. Some of the engines listed in paragraph 2 may already have the Governor Lube Oil Cooler installed below the Governor Lube Oil level.

A copy of this letter will be sent to each cognizant party listed in paragraph 2 by December 21, 1981. Detailed instructions for moving the Governor Lube Oil Cooler will be sent to each site by January 15, 1982. Parts and technical services required will be furnished by Transamerica Delaval on request and in accordance with each individual contract.

We canuot estimate when this modification will be complete, since the completion date depends on action by the sites.

This report confirms an initial telephone report to Mr. Paul Narbet, Region 5, Walnut Creek, California, on December 9, 1981.

Our evaluation of this matter was concluded on December 8, 1981.

Very truly yours, EE Sq v R. E. Boyer,. Manager Quality Assurance REB:cjb cc:

Mr. Paul Narbet U.S. Nuclear Regulatory Commission 1990 N. Calornia Blvd.

Walnut Creek, CA 94596 l