PLANT SYSTEMS 3/a.7.6 CONTROL ROOM EMERGENCY VENTILATION SYSTEM l'

i LIMITING CONDITION FOR OPERATION i

3.7.6.1 Two independent control room emergency ventilation systems

'L.,

e shall'be OPERABLE.-

.5 l

\\i APPLICABILITY:

ALL MODES.

ACTION:

MODES 1, 2, 3, and 4:

With one control room emergency ventilation system inoperable,

~ ' ['

restore the inoperable system to OPERABLE status within 7 days d

or be in at least NOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUT 00WN within the following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

s With both control room emergency ventilation systems inoperable i

[where inoperability of one or both' systems is due solely to failure of the system (s) to maintain the control room at a posi-tive pressure of g 1/8 ihch W6 relative to outside atmosphere or to adjacent spaces,. but able to maintain ther control' room at a 6,)

positive pressure of 11/16 inch WG), restore at least one system

/15:

to operable status within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> or be.in at least HOT STANDBY within the next 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and in COLD SHUTDOWN within-the'following 30 hours3.472222e-4 days <br />0.00833 hours <br />4.960317e-5 weeks <br />1.1415e-5 months <br />.

i MODES 5 and 6:

With one control room emergency ventilation system inoperable,

.h a.

restore the inoperable system to OPERABLE status within 7 days or initiate and maintain operation of the remaining OPERABLE control room emergency ventilation system-in the recirculation mode of operation.

+

b.

With both control room emergency ventilation s'ystems inoperable, suspend all operations involving CORE ALTERATIONS or positive reactivity changes 6 speci6CAhe^ 3.0 4 Anlnot a f f C ^l')le -

h The. provi s # o M e c,,

SURVEILLANCE REOUIREMENTS i

4.7.6.1 Each control room emergency ventilation system shall be demon-strated OPERABLE:

At least once per 31 days on a STAGGERED TEST BASIS by initiating a.

flow through the HEPA filter and charcoal adsorber train and verifying that the train operates for at least 10 hours1.157407e-4 days <br />0.00278 hours <br />1.653439e-5 weeks <br />3.805e-6 months <br /> with the TROJAN-UNIT 1 3/4 7-18 Amendment No. 77, 26.