Forwards Info Re Sustained Degraded Grid Voltage to Resolve SER Confirmatory Issue 1.7.13
ML20033C811
Person / Time
Site: Summer 
Issue date: 11/30/1981
From: Nichols T
SOUTH CAROLINA ELECTRIC & GAS CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
Shared Package
ML20033C812 List:
References
NUDOCS 8112040310
Download: ML20033C811 (2)


Text

I s

,,s.",,

SOUTH CAROLINA ELECTRIC a GAS COMPANY

,"r js POST OFFICE BOR 764

{

{^

'/g CotuMeiA, SOUTH CAROLINA 29218

, I. 5 3

T. C. NICH O LS, J R.

Novmber 30, 1981' db I

V Vict Persectwt A=D G.ou. EntcuTevt 4,

- ~

Nuctran Openmons

]

o,b speAAN Mr. Harold R. Denton, Director

q Office of Nuclear Reactor Regulation 4

U. S. Nuclear Regulatory Ccmmission

[ _.

Washington, D. C.

20555

Subject:

Virgil C. Sunmer Nuclear Station Docket No. 50/395 Sustained Degraded Grid Voltage SER Confirmatory Issue 1.7.13

Dear Mr. Denton:

South Carolina Electric and Gas (bmpany (SCE&G) hereby provides the following information on the topic of sustained degraded grid voltage:

1.

SCE&G Test Procedure SUM-C-1096 Subsysts ES01-E56 for plant testing of simulated degraded grid voltage (Attachnent 1).

2.

ANSI C.57.12.90, Paragraph 14.4.4.1 (1980) describes the analytical method used to calculate degraded voltages and ccmparison of measured voltage versus calculated voltage.

(Attachment 2).

As evident frm the cmparison (Attachment 2), the difference between the calculated and measured voltages are less than 1.2% which is well within the range of instrument error.

Thus, the analytical methods have been confirmed and test results validated.

3.

In respnse to a verbal request frm your Mr. On 01opra of the Power Systems Branch, a test was conducted to determine the effect on safeguards bus voltages when starting the largest non-safety related notors. '1he details of this test are included herein as Attachment 3.

This transmittal provides the information necessary to resolve SER Confirnatory Issue 1.7.13.

Ql If you have any questicas, please let us know.

5 Very truly yours, f (

T. C. Nichols, Jr.

NEC:'ICN:Ikb Attachments cc: See Page 2 8112040310 811130

{DRADOCK 05000395 PDR

f Mr. Harold R. Denton November 30, 1981 Page 2 i

cc:

V. C. - Sumer T. C. Nichols, Jr.

i G. H. Fischer H. N. Cyrus H. T. Rahh D. A. Natnan i

M. B. Whitaker, Jr.

W. A. Willians, Jr.

O. S. Bradham R. B. Clary M. N. Browne A. R. Koon G. J. Braddick J. L. Skolds J. B. Knotts, Jr.

B. A. Bursey J. C. Ruoff NPCF File L