November 12,198i BLRD-50-438/81-40
[.
S D
b.
K".
James P. O'Reilly, Director g
Office of Inspection and Enforcement 2
DE01 1981> H U.S.
'uclear Regulatory Commission Regioa II - Suite 3100 9
u.s. g, 7 1
k 101 Marietta Street Atlanta, Georgia 30303
\\
6
/
Dear Mr. O'Reilly:
BELLEFONTE !.UCLEAR PLANT UNIT 1 - INTERNAL LACK OF FUSION ON NAVC0 SPOOL PIECE - BLRb-50-438/81 FOURTH INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspcotor R. V. Celenjak on May 20, 1981, in accordance with 10 CFR 50.55(e) as NCR 1467. This was followed by our interim reports dated June 19,
-August 26, and September 29, 1981. Enclosed is ou, fourth interim report.
i We expect to submit our next report by December 29, 1981.
If you have any questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.
Very truly yours, TENNESSEE VALLEY AUTHORITY 4 h4w L. M. Mil Ls, Manager Nuclear Regulation and Safety Enclosure cc:
Mr. Victor Stello, Jr., Director (Enclosure)
Office c.f Inspection and Enforcement U.S. Nuclear Regulatory Commission Wechington, DC 20555 i
tWFfEMLCOPM t
$E0"2?&ggggg;kr
~~
s'
\\
' E 27 e
An Equal Opportunity Employer
),
h s
ENCLOSURE BELLEFONTE NUCLEAR PLANT UNIT 1 INTERNAL LACK OF FUSION ON NAVC0 SPOOL PIECE BLRD-50-438/81-40
.10 CFR 50.55(e)-.
FOURTH INTERIM REPORT -
Description of Deficiency An internal lack of fusion, approximately 1/8 inch wide and 21 inches long, was discovered during the installation of a spool pitce supplied j
by NAVCO. This internal lack of fusion was found during tile radiography of a circumferential butt weld. The radiograph overlapped an adjacent longitudinal we)d of the spool piece and indicated that it exhibited the lack of ws]d fusion. The spool piece is 12 inches in diameter, stainless steel SA312 TP304 welded pipe located in the Spent Fuel Cooling System.
Corrective Actions TVA is still in the process of evaluating the subject deficiency. The spool piece is being evaluated at' TVA's Singleton M terials Laboratory.
a I
I
!l
.