TABLE 3.3-10 FIRE DETECTION INSTRUMENTS INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE

  • Smoke 1.

Control Roon a.

FIU 6-100, Zone 1 1

b.

FIU 6-100, Zone 2 2

c.

FIU 6-100, Zone 3 1

d.

FIU 6-100, Zone 4 1

Total 5

2.

Cable Spreading Room f

l a.

ZIU 6-#2, Zone 1 3

b.

ZIU 6-#2, Zone 2 3

c.

ZIU 6-#2, Zone 3 3

d.

ZIU 6-#2, Zone 4 3

Total 12 3.

Electrical Penetration Area a.

ZIU 6-#5, Zone 1 2

b.

ZIU 6-#5, Zone 4 1

Total 3

4.

Switchgear Room a.

Train A Elevation 69 ft (1) ZIU 6-#7, Zone 1 3

(2) ZIU 6-#7, Zone 2 3

Total 6

TROJAN-UNIT 1 3/4 3-49 8110140233 811008 PDR ADOCK 05000344 P

PDR

\\.

INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABl.E*

Smoke b.

Train B Elevation 61 ft (1) ZIU 6-#6, Zone 3 2

(2) ZIU 6-#6, Zone 4 3

Total 5

5.

Station Battery Rooms L

a.

Train A Elevation 63 ft ZIU 6-#6, Zone 2 1

b.

Train B Elevation 63 ft ZIU 6-#6, Zone 1 1

6.

Containment a.

ZIU 6-#5, Zone 2 1

b.

ZIU 6-#5, Zone 3 1

c.

ZIU 6-#19, Zone 3 1

Total 3

7.

Auxiliary Feedwater Pump Rooms a.

ZIU 6-#16, Zone 1 1

b.

ZIU 6-#16, Zone 2 1

c.

ZIU 6-#16, Zone 3 1

Total 3

8.

Residual Heat Removal Pump Rooms a.

ZIU 6-#13, Zone 1 2

b.

ZIU 6-#13, Zone 2 2

Total 4

9.

Service Water Pump Area a.

ZIU 6-#8, Zone 1 1

b.

ZIU 6-#8, Zone 2 1

c.

ZIU 6-#8, Zone 3 1

Total 3

I TROJAH-UNIT 1 3/4 3-49a

t I

INSTRUMENT LOCATION MINIMUM INSTRUMENTS OPERABLE

  • Smoke
10. Service Water Booster Pump Area a.

ZIU 6-#9, Zone 1 1

b.

ZIU 6-#9, Zone 4 1

Total 2

4 l

11. Centrifugal Charging Punp Rooms a.

ZIU 6-#14, Zone 2 1

b.

ZIU 6-#14, Zone 3 jl_

l Total 2

12.

Emergency Diesel Generator Rooms a.

ZIU 6-#15, Zone 1 2

b.

ZIU 6-#15, Zone 2 2

Total 4

13. Component Cooling Water Pump Area a.

ZIU 6-#9, Zone 2 1

l b.

ZIU 6-#9, Zone 3 1

Total 2

14. Safety Injection Pump Rooms l-l a.

ZIU 6-#13, Zone 1 2

b.

1:U 6-#13, Zone 2 2

Total 4

The fire detection instruments located within the Containment are not required to be OPERABLE during t.'e performance of Type A Containment leakage Rate Tests.

TROJAN-UNIT 1 3/4 3-49b

.I L

PLANT SYSTEMS FIRE HOSE STATIONS i

LIMITING CONDITIONS FOR OPERATION 3.7.8.3 The fire hose stations shown in Table 3.7-4 shall be OPERABLE.

APPLICABILITY:

Whenever equipment in the areas protected by the fife hose stations is required to be OPERABLE.

ACTION:

i a.

With one or more of the t're hose stations shown in Table 3.7-4 inoperable, route an additional equivalent capacity fire hose to the unprotected area (s) from an CPERABLE hose station wihin 1 hour1.157407e-5 days <br />2.777778e-4 hours <br />1.653439e-6 weeks <br />3.805e-7 months <br />.

Restore the fire hose station to OPERABLE status within 14 days or, in lieu of any other reoprt required by Specification 6.9.1, prepare and submit a Special Report to the Commission pursuant to Specification 6.9.2 within the next 30 days outlining the action taken, the cause of the inoperabil-ity, and plans and schedule for restoring the station to 4

OPERABLE status.

b.

The provisions of Specifications 3.0.3 and 3.0.4 are not applicable.

i SURYEILLANCE REQUIREMENTS s

4,7.8.3 Each of the fire hose stations shown in Table 3.71 shall be j

demonstrated OPERABLE:

a.

At least once per 31 days by visual inspection of the station to assure all required equipment is at the station, Fire hose stations which are not accessible during plant operation shall be inspected during each cold shutdown exceeding 24 hour2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> 2 unless performed in the previous 31 days.

b.

At least once per 18 nonths by:

I 1.

Renoving the hose for in pection and re-racking, and 2.

Inspecting all gaskets and replacing any degraded gaskets in the couplings.

c.

At least once per 3 years by:

1.

Partially opening each hose station valve to verify valve OPERABILITY and no flow blockage.

2.

Conducting a hose hydrostatic test at a pressure at least 50 psig greater than the maximum pressure i

available at that hose station.

J TROJAH-UNIT 1 3/4 7-29 Amendment N:. 18 October 6,1980

- ~.

.. ~, _ _ _. - ~ _

. ~.

1 4

l i

9 TABLE 3.7-4 FIRE HOSE STATIONS i

l LOCATION ELE'/ATION HOSE STATION l

1.

Auxiliary Building 5 ft.

HS-34' I

2.

Auxiliary Building 25 ft.

HS-33 3.

Auxiliary Building 45 ft.

HS-19, 38 4.

Auxiliary Building 63 ft.

HS-29 l

l 5.

Auxiliary Building 7/ ft.

HS-28 6.

Turbine Building 45 ft.

HS-3, 5 7.

Turbine Building 69 tt.

HS-27 8.

Turbine Building 93 ft.

HS-15 1

9.

Control Building 63 ft.

HC-2 l

10.

Control Building 77 ft.

HS-26

11. Containment 45 ft.

CHS-A[a,b]

12.

Containment 93 ft.

CHS-B[a,b]

13. Containment 93 ft.

CHS-C[a,b]

i 4

[a] From Demineralized Water Systen

[b] Inspected Dur:qg COLD SHUTDOWN i

l s

4 1

i TROJAH-UNIT 1 3/4 7-30 Amendment No. 50 October 6,1980

.. -. -., - _., -,.. _ _ - _.. -., _., _. ~, - _.... -, _...

. - _ - =

a l

UNITED STATES OF AMERICA 3

NUCLEAR REGULATORY COMMISSION a

j In the Matter of

)

)

PORTLAND GENERAL ELECTRIC COMPANY, )

Docket 50-344 THB CITY OF EUGENE, ORECON, AND

)

Operating License NPF-1 PACIFIC POWER & LIGHT COMPANY

)

)

(TROJAN NUCLEAR PLANT)

)

i l

I CERTIFICATE OF SERVICE i

I hereby certify that copied f License Change Application 79 to the l

Operating License for Trojan Nuclear Plant, dated October 8,1981, have been served on the following by hand delivery or by deposit its the United States mail, first class, this 8th day of October 1981:

i l

Mr. Lynn Frank, Director State of Oregon Department of Energy 4

Labor & Industries Bldg., Room 102 l

Salen, Oregon 97310 Mr. Robert M. Hunt Chairman of County Commissioners I

Columbia County Courthouse St. Helens, Oregon 97051 i

g i

i d C-J.'W. Lentsch, Manager Gene':ation Licensing & Analysis Subscribed and sworn to before me this 8th day of October 1981.

Lie fr e? D Notary Public of Orgfon i

My Commission Expires:

e,y%(([f7f gf l

l