.na UNITED STATES GOVERNMENT Memorandum m
I}. H. Grier, Senior Reactor Inspector DATE:
April 10, 1967 Division of Compliance, HQ m u J.
P. O'Reilly, Senior Reactor Inspector
, f, (' ' \\
)
Region I, Division of Compliance SUBJECWANKEE ATCMIC ELECTRIC COMPANY DOCKET NO. 50-29 D
t The attached report by our field inspector of a visit to the g
subject facility on March 20 - 22, 1967, is forwarded for
- s.
information.
One item of noncompliance was noted and a Form
.Ur AEC-592 was issued. This item concerns plant operation for two and one-half months with the primary coolant pH less than 5.0, j4' 4 "If?
the minimum value listed in the Technical Specifications.
f.
The following items, discussed in the report, are considered to
-6 be of special interest:
I' 1.
Three significant train wrecks have occurred recently in the g
vicinity of the Yankee plant on the routes that would have t
been used by the fuel shipment cask.
The cask was not in-volved in the accidents.
F i,
2.
A throttle valve to the main turbine failed to close com-pletely due to a buildup of chemicals on the valve stem -
boron and phosphate.
This situa tion may become a general problem for plants that have high concentratio ns of chemA als T
in their systems and operate for extended periods of time.
3.
Additional organizational changes are described in the report.
l These changes represent a reduction in the nuclear experience k
level at Yankee.
m, \\. *h j
~
of
Attachment:
(
CO Rpt. No. 29/67-1