Text
..
e TENNESSEE VALLEY AUTHORITY CH ATTANOOG A. TENNESSEE 37401 400 Chestnut Street Tower II j
August 26, 1981 BLRD-50-438/81-40
/\\
8\\
h Mr. James P. O'Reilly, Direc we 5?.
Office of Inspection and Enforcement A
C U.S. Nuclear Regulatory Commission gi q.'
I Region II - Suite 3100 sF 101 Marietta Street o
6 g
Atlanta, Georgia 30303
Dear Mr. O'Reilly:
BELLEFONTE UUCLEAR PLANT UNIT 1 - INTERNAL LACK OF FUSION ON NAVC0 SPOOL PIECE - BLRD-50-438/81 SECOND INTERIM REPORT The subject deficiency was initially reported to NRC-0IE Inspector R. V. Crienjak on May 20, 1981, in accordance with 10 CFR 50.55(e) as NCR 1467 This was followed by our first interim report dated June 19, 1981. Enclosed is our second interim report. We expect to submit our next report by October 1, 1981.
If you have any questions concerning this matter, please get in touch with D. L. Lambert at FTS 857-2581.
Very truly yours, TENNESSEE VALLEY AUTHORITY l
L.
M.' Mills, Man ger Nuclear Regulation and Safety Enclosute cc:
Mr. Victor Stello, Jr., Director (Enclosure)
Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 gh s
//
8109010340 810826 '
DR ADOCK 05000 An Equal Opportunity Employer
~
O ENCLOSURE BELLEFONTE NUCLEAR PLANT UNIT 1 INTERNAL LACK OF FUSION ON NAVC0 SPCOL PIECE BLRD-50-438/81-40 10 CFR 50.55(e)
SECOND INTERIM REPORT Description of Deficiency An internal lack of fusion, approximately 1/8 inch wide and 21 inches long, was discovered during the installation of a spool piece supplied by NAVCO. This internal lack of fusion was found during the radiography of a circumferential butt weld. The radiograph overlapped an adjacent longitudinal weld of the spool piece and indicated that it exhibited the lack of weld fusion. The spool piece is 12 inches in diameter, stainless steel SA312 TP304 welded pipe located in the Spent Fuel Cooling System.
Correctito Actions TVA is performing an analysis in order to determine the safety significance of this condition. The spool piece has been removed and is being evaluated at TVA's Singleton Materials Laboratory.