ML20030B057

From kanterella
Jump to navigation Jump to search
Topical Rept Evaluation of BAW-1623, Control Rod Guide Tube Wear Measurement Program. Issue Adequately Addressed for B&W Facilities & Considered Closed
ML20030B057
Person / Time
Site: Rancho Seco
Issue date: 07/24/1981
From:
Office of Nuclear Reactor Regulation
To:
Shared Package
ML20030B056 List:
References
NUDOCS 8108050133
Download: ML20030B057 (2)


Text

f[,

),,

UNITED STATES s.,

g NUCLEAR REGULATORY COMMISSION y,

t'

.; C WASHINGTON, D, C 20555 k.....,/

Enclosure SAFETY EVALUATION REPORT BY THE OFFICE OF NUCLEAR REACTOR REGULATION CONTROL ROD GUIDE TUBE WEAR IN FACILITIES DESIGNED BY BABCOCK AND WILCCX (B&W)

A degradation of control rod guide tube walls was observed during post irradia-tion examinations of fuel assemblies removed from several pressurized water reactors.

In the investigation of this problem the NRC requested information from B&W designed facilities related to the susceptibility of their facilities to significant guide tube wear. B&W prepared report BAW-1623, June 1980,

" Control Rod Guide Tube Wear Measurement Program" for the B&W Mk-B User's Group to provide this requested information. The findings of this report are as 4110ws.

Several flow-related mechanisms may cause Control Rod Assembly (CRA) vibration and guide tube wear; two of these appear to be the most probable.

The first is turbulent flow along the rod or crossflow across the control rods in the upper j

internals, resulting in wear at the lower tip of the rod when in the park posi-tion. The second hypothesized mechanism is axial ficw inside the guide tube and a turbulent vibration response.

In both cases, an increase in primary coolant flow could result in higher rod vibration and possible higher wear; however it l

is felt that turbulent flow with some possible crossflow in the internals area is the most probable cause of rod vibration.

B&W's 15x15 array fuel assembly design includes 16 Zircaloy guide tubes for the control rods. Each CRA has 16 stainless steel clad control rods connected to a stainless steel spider which is in turn connected to the drive mechanism. Full length guidance for each CRA is provided by tL guides in the upper plenum assembly and in the fuel assembly. The control rod tip always remains inside the fuel c sembly guide tube during normal operation.

When the control red is in the full out (parked) position, the tip of the control rod is approximately nine inches inside the fuel assembly guide tube.

The CRAs and guide tubes are designed with flexibility and clearances to permit freedom of motion within the fuel assembly guide tubes throughout the stroke of the CRA.

The B&W upper reactor internals design, in addition to the full-length guidance for the CRAs, has two features that minimize crossflow excitation and turbulence on the CRAs. The first is an upper plenum, which directs approximately 82% of the flow in an axial direction while allowing only 18% of the flow to be taken 8108050133 810724 PDR ADOCK 05000312 P

pop

6/

out directly into the outlet nozzles. This strong. tendency towards axial flow will minimize any dependence of CRA vibration on outlet nozzle location..The second feature is the use of the full-length upper plenum tubes enclosing each CRA in the upper reactor internals.

These full-length tubes provided additional protection for the CRAs against crossflow and turbulence.

Fuel assemblies were selected from across the core and for various effective full-power days (EFPD) of control rod operation in the safety position to determine -the effect of core-position, time, fluence exposure, To obtain the effect of flow rates on guide tube wear, fuel as-semblies were exsmined at Oconee 1, Oconee 3, and Rancho Seco, the nominal etc.

Two

, flows of which run from approximately 109 to 114% of design flow.The first concern is t potential areas of concern were investigated.

any one guide tube could wear through at the control rod park position (approximately 9 inches from the top of the control rod guide tube).

The second concern is that smaller amounts of wear in all 16 guide tubes in a fuel assembly could cause high stresses in that fuel assembly.

i The results from the Rancho Seco examination (high flow rate) indicates that the largest measured wear was 57% (through-wall wear).

In general, the wear was located approximately 9 inches down from the top of the guide l

tube, which. corresponds to the location of the lower tip of the control This location also cor-l rods of the safety banks in their park position.

responds to the control rod park position for control banks in some reactors.

Four Rancho Seco fuei assemblies indicated wear ranging from 6.9 to 14.9%

for one and one half :ycles of operation. The other five assemblies i

examined indicated no wear.

I The results from the Oconee examination (low flow rates) indicate less wear than Rancho Seco, with a maximum measured indication of 27% (in Oconee 3).

The average wear for each Oconee fuel assembly was low, with a maximum i

l of 6.7%.

The second concern was that each guide tube would have some wear and that A. stress analysis was performed chat unacceptable stresses could occur.

This showed that through-wall wear for a single tube was acceptable.

Two analysis also considered the case with some wear in each guide tube.

types of wear.were considered - localized wear on only one side of the l

The reeults of this tube and uniform wear around its circumference.

analysis show an allowable of 100% wear for localized (one-sided) defects l

Therefore, if the average -

and 55% wear for uniform circumference wear.

wear in any fuel assembly (average of 16 tubes) does not exceed 55% uni-form wear, the fuel assembly will maintain a positive design margin.

. J

- The-results of both the Oconee and Rancho Seco measurements show small average wear with the maximum average of 14.9% for one Rancho Seco assembly with 1 1/2 cycles of operatiori. The 14.9% was one-sided wear which.is compared to an allowable' wear of 100%.

s The results from the Rancho Seco statistical analysis indicate the pro-bability of one guide tube wearing.a hole is very low and is not expected.

l The probability that a hole'will-occur in 150 weeks of operation is 0.000011. The results from this analysis also indicate that the proba-

. bilityt of the average of 16 tubes in one assembly reaching 55% wear is also very low and is _ not expected. The probability of the average of 16' tubes reaching 55% wear is 0.000001 for 150 weeks of operation. This

' case assumes unifonn circumferential wear, which is not expected. The more likely case.is wear occurring on only one side of the guide tube.

This. case has a higher allowable wear (100% versus 55%) and hence a'signi-ficantly smaller probability of reaching this wear.

(The assumed maximum core residence time for a fuel assembly with an installed CRA is 150 weeks.)

The NRC staff has found that the B&W Report accounts for all of the major l

l variables that affect the control rod guide tube wear. process. Based on '

our review, we conclude that the control' rod guide tube wear has an acceptably low likelihood of keeping within allowable wear limits.

Dated:

' JULY 24581 I

j l

l

\\

s

.\\

I L

~

n.,.